Plan Review Notes
Plan Review Notes For Permit 06110349
Permit Number 06110349
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-01-30 16:01:47****DENIED*****
  
  
 01.THE ACTUAL ADDRESS OF WHERE THE SCOPE OF WORK IS
 CONDUCTED SHALL BE IN THE TITLE BLOCK OF EACH PLAN
 SHEET.
  
 02.NFPA 101 - 2003 EDITION AND FLORIDA FIRE
 PREVENTION CODE - 2004 EDITION SHALL BE REFERENCED.
  
 03.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION SHALL COMPLY WITH NFPA241.
  
 04.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL
 NOT INTERFERE OR HINDER EMERGENCY ACCESS TO THE SAID
 PROPERTY OR VICINITY THEREOF.
  
 05.SHOW THE LOCATION OF FIRE HYDRANT(S) WITHIN
 300-500 FEET OF THE BUILDING.
  
 06.SHOW/DISPLAY THE NUMERICAL ADDRESS OF THE BUILDING
 ON THE PROPER ELEVATION VISIBLE FROM PREMIER PARK
 DRIVE.AS PER WEST PALM BEACH CODE, THOSE NUMBERS
 SHALL BE NO LESS THAN 6" IN HEIGHT AND 1" IN WIDTH.
 SUITE/UNIT/TENANT SPACE NUMBERS SHALL BE NO LESS THAN
 3" IN HEIGHT AND 1" IN WIDTH.
  
 07.IF A MONUMENT SIGN OR MARKEE IS REQUIRED, A
 NUMERICAL ADDRESS WILL ALSO BE POSTED.IF THERE ARE
 GOING TO BE SEVERAL ADDRESSED BUILDINGS WITHIN THE FED
 EX COMPLEX, A RANGE OF ADDRESSES FROM THE LOWEST TO THE
 HIGHEST WILL BE REQUIRED ON THE MONUMENT SIGN OR
 MARKEE.
  
 08.SINCE THIS WILL BE A SPRINKLERED BUILDING, PROVIDE
 A LAYOUT OF THE FIRE SPRINKLER SYSTEM.
  
 09.FIRE DEPARTMENT CONNECTIONS (FDC'S) SHALL BE
 POSITIONED SO THAT THEY CANNOT BE BLOCKED BY STORAGE,
 VESSELS, EQUIPMENT, ETC.
  
 10.KNOX LOCKING CAPS ARE REQUIRED FOR NEW FIRE
 DEPARTMENT CONNECTIONS.
  
 11.ELECTRONIC SWITCHES IN ADDITION TO CHAIN AND LOCK
 IS REQUIRED FOR DOUBLE CHECK DETECTOR ASSEMBLY.
  
 12.KNOX BOX FOR THE BUILDING WILL BE REQUIRED. PLEASE
 CONTACT THE FIRE PREVENTION BUREAU AT (561) 804-4724
 FOR APPLICATIONS.
  
 13.ALL FIRE DOORS AND WINDOWS SHALL COMPLY WITH NFPA
 80.
  
 14.INTERIOR FINISH FOR WALLS AND CEILING IN EXITS AND
 EXIT ACCESS CORRIDORS SHALL BE CLASS "A" OR CLASS "B".
  
 15.PROVIDE A LIFE SAFETY PLAN SHOWING THE TRAVEL
 DISTANCE TO AN EXIT MEASURED ON THE FLOOR OR OTHER
 WALKING SURFACE AS PER NFPA 1017.6.1*
  
 16.FIRE EXTINGUISHERS ARE TO BE RATED 2A-10BC.
  
 17.SEPARATE SHOP DRAWINGS AND PERMITS ARE REQUIRED
 FOR FIRE SPRINKLER AND FIRE ALARM SYSTEMS.
  
 18.FIRE SPRINKLER SYSTEM IS TO BE MONITORED.
  
 19.FIRE ALARM SYSTEM IS TO BE CLASS A OR FULLY
 ADDRESSABLE.
  
 20.ON SHEET FA0.3, FIRE ALARM NOTE 17, DELETE WORDING
 " SUPERVISORY SIGNAL ONLY" AND INSERT WORDING "A
 GENERAL FIRE ALARM".
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING,
 INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH
 ITEM WAS ADDRESSED
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722