Date |
Text |
2006-12-04 13:03:12 | **** UNSAT **** |
| |
| PERMIT # 06110349 |
| BUILDING # 3 |
| PLEASE KNOW THAT THE ADDRESS SHALL BE PLACE ON THE |
| PLANS TITLE BLOCK AS IT HAS NOW BEEN DESIGNATED TO THIS |
| BUILDING LOCATION. |
| |
| 1) NOTE: PLEASE KNOW THAT THE PLANS HAVE ONLY BEEN |
| SUBMITTED FOR "PLAN REVIEW" ONLY AND HAVE NOT BEEN |
| SUBMITTED FOR PERMIT AT THIS TIME. PLEASE KNOW AS OF |
| DECEMBER 8TH 2006 THE STATE OF FLORIDA WILL ADOPT THE |
| NEW 2005 NATIONAL ELECTRICAL CODE NFPA-70. PLEASE ALSO |
| KNOW THAT THE NEW 2006 REVISIONS TO THE 2004 FBC WILL |
| ALSO GO INTO AFFECT. |
| PLEASE KNOW THAT AS PERMITS HAVE NOT BEEN APPLIED FOR |
| AT THIS TIME ALL NEW CODES AFTER THIS DATE WILL BE |
| REQUIRED TO BE MET. |
| |
| 2) NOTE: PLEASE BE SURE ALL THE FOLLOWING RELEVANT |
| CODES ARE REFLECTED ON PLANS. |
| 2002 NFPA-70 ONLY IF A PERMIT IS APPLIED FOR BY THE 8TH |
| OF DEC. PLEASE REFLECT THE 2005 NFPA-70, 2002 NFPA-72, |
| 2003 NFPA-101, 2003 NFPA-20 AND THE 2004 FBC. |
| |
| 3) NOTE: PLEASE SEE FBC 2004 CHAPTER 13. |
| PLEASE SEE ENERGY CALCULATIONS WHICH INDICATE "MANUAL" |
| FOR THE MEANS OF CONTROL FOR LIGHTING. PLEASE SEE |
| ENERGY CALCULATIONS WHICH MENTIONS "NONE ENTERED" FOR |
| EXTERIOR LIGHTING, HOWEVER PLANS DO INDICATE THIS. |
| PLEASE SEE 13-415.1.ABC.1.1, .1.2, AND .1.3. PLEASE SEE |
| 13-415.1.AB.1, 13-415.2.ABC.1. |
| PLEASE SEE SOME OF THE INTERIOR LIGHTS ARE BEING SHOWN |
| CIRCUITED THROUGH THE LIGHTING CONTROL PANELS AND NOTED |
| AS EXTERIOR LIGHTS WHEN THESE ARE INTERIOR FIXTURES. |
| PLEASE SEE ALL AREAS WHICH CONTAIN FLOOR TO CEILING |
| HEIGHT PARTITIONS SHALL ALSO CONTAIN LIGHTING CONTROL |
| BY ONE OF THE MEANS AS STATED IN THE CODE. THIS OFFICE |
| DOES NOT REQUIRE ONE DESIGN OVER ANOTHER. |
| PLEASE SEE MORE THAN OPTION IS AVAILABLE. PLEASE BE |
| SURE TO CORRELATE CIRCUITING AS AN EXAMPLE OF CIRCUIT |
| "3HP-5". ON THE LIGHTING CONTROL PANEL IS SHOWS THIS |
| CIRCUIT AS FEEDING EXTERIOR LIGHTS, YET ON PLANS THIS |
| IS THE CIRCUIT WHICH FEEDS THE INTERIOR LIGHTS. PLEASE |
| ALSO SEE THAT ALL EMERGENCY AND EXIT LIGHTS SHALL BE |
| SHOWN IN DETAIL WIRED ON THE LINE SIDE OF ANY LIGHTING |
| CONTROL PANEL. (700.12E). |
| |
| |
| 4) NOTE: PLEASE SEE NFPA-101 7.8 AND 7.9, WHICH MAY |
| ALSO BE PART OF THE FIRE REVIEWER COMMENTS WITH RESPECT |
| TO A MINIMUM OF LIGHTING REQUIRED IN SPACE UNTIL SUCH |
| TIME FOR TENANT BUILD OUT. PLEASE SEE THAT MINIMUM |
| BATTERY BACK UP LIGHTS OF SOME KIND WILL BE REQUIRED |
| FOR EGRESS AREAS WHICH INCLUDE EXTERIOR STAIRS TO THE |
| PUBLIC RIGHT OF WAY. PLEASE SEE MINIMUM FOOT CANDLES |
| UNDER NORMAL POWER AND MINIMUM FOOT CANDLES REQUIRED |
| UNDER EMERGENCY POWER. 7.8.1.3, 7.9.2.2. PLEASE KNOW |
| THESE LIGHTING LEVELS SHOWN ON PHOTO-METRICS WILL BE |
| REQUIRED ON ELECTRICAL PLANS FOR REVIEW WHETHER OR NOT |
| THESE COMMENTS ARE MADE BY FIRE REVIEW. |
| |
| 5) NOTE: PLEASE SEE 230.2E WHICH SPEAKS OF SIGNAGE |
| REQUIRED FOR ALL SERVICE FEEDING ONE BUILDING. PLEASE |
| SEE THAT RISER ONLY INDICATES 2-MAINS FOR THIS |
| BUILDING, WHEN IN FACT THE MAIN FOR THE FIRE PUMP |
| SHOULD ALSO BE NOTED AND LABELED. PLEASE ALSO PLACE |
| NOTES ON RISER FOR SIGNAGE WHICH WILL BE REQUIRED FOR |
| ALL MAINS AND SERVICE LOCATIONS. PLEASE SEE AS THE |
| JOCKEY PUMP IS BEING FED FROM THE NORMAL HOUSE PANEL, |
| THIS SHALL ALSO BE LABELED ACCORDINGLY. 695.4(B)3 |
| |
| 6) NOTE: PLEASE SUBMIT THE MANUFACTURE SPEC/CUT SHEETS |
| FOR THE FIRE PUMP AND FIRE PUMP CONTROLLER.THIS IS |
| REQUIRED UNDER THE BASE BUILDING PLANS FOR REVIEW OF |
| CODE COMPLIANCE FOR THE BUILDINGS ELECTRICAL SYSTEM AND |
| FEEDS TO THIS PUMP. PLEASE KNOW EVEN THOUGH THE FIRE |
| SPRINKLER SYSTEM IS UNDER A SEPARATE PERMIT. PLEASE SEE |
| NFPA-20 2003, PLEASE SEE 9.3, 9.3.2.2 ALL SECTIONS |
| FOLLOWING. PLEASE SEE WHERE LOCKED ROTOR CURRENT SHALL |
| BE MARKED, DISCONNECTING MEANS, ISOLATING SWITCHES ETC |
| SHALL BE SHOWN WITH PLANS AND SPECS SHEETS SUBMITTED. |
| PLEASE ALSO SEE NEC 695.4(B)(1). PLEASE SEE CHAPTER 10 |
| OF NFPA-20 10.3.6, 10.4.2, 10.4.2.2 ETC. |
| PLEASE KNOW THIS OFFICE IS UNABLE TO REVIEW FOR MANY |
| CODE COMPLIANCE ITEMS AT THIS TIME AS THE ABOVE |
| INFORMATION WAS NOT SUBMITTED. |
| PLEASE SEE 110.3, AND 90.7. |
| PLEASE SEE FBC ADMIN SECTION 106.1.2, 106.3.5.1.1PARA |
| 5 |
| |
| 7) NOTE: PLEASE SEE NFPA-72 AS THE BREAKER WHICH FEEDS |
| THE FIRE ALARM CONTROL PANEL (FACP) SHALL BE A BREAKER |
| WHICH CONTAINS A "LOCK-ON" DEVICE WHICH IS AN INTEGRAL |
| PART OF THE BREAKER. PLEASE KNOW THAT A "SNAP ON" TYPE |
| DEVICE WILL NOT BE ACCEPTABLE TO THE AHJ. NFPA-72. |
| 4.4.1.4.2.1THE DEDICATED BRANCH CIRCUIT(S) AND |
| CONNECTIONS SHALL BE MECHANICALLY PROTECTED. |
| 4.4.1.4.2.2CIRCUIT DISCONNECTING MEANS SHALL HAVE A |
| RED MARKING, SHALL BE ACCESSIBLE ONLY TO AUTHORIZED |
| PERSONNEL, AND SHALL BE IDENTIFIED AS "FIRE ALARM |
| CIRCUIT" |
| 4.4.1.4.2.3THE LOCATION OF THE CIRCUIT DISCONNECTING |
| MEANS SHALL BE PERMANENTLY IDENTIFIED AT THE FIRE ALARM |
| CONTROL UNIT. |
| PLEASE ALSO SEE 90.7, 110.3 AND 90.4. |
| THIS CAN BE ADDRESSED WITH IDENTIFICATION ON THE PANEL |
| SCHEDULE AND A NOTE ON PANEL FOR TYPE OF BREAKER TO BE |
| USED FOR THIS CIRCUIT. |
| |
| 8) NOTE: PLEASE COMPLETE RISER FOR FIRE PUMP AS NOTED |
| ABOVE FOR FEEDERS ETC. |
| 240.4, 310.16, 695, NFPA-20 CHAPTER 9 |
| |
| 9) NOTE: PLEASE INDICATE "FLOATING NEUTRAL" ON THE |
| METERS ON THE SECONDARY SIDE OF THE PRIMARY MAIN. |
| 250.6, 250.24B. |
| |
| 10) NOTE: PLEASE SUBMIT OR INDICATE REQUIREMENTS FOR |
| WIND LOAD CALCULATIONS FOR BUILDING REVIEW FOR FBC 2004 |
| 140MPH. |
| |
| 11) NOTE: PLEASE CLARIFY THE NOTIFICATION APPLIANCE |
| CIRCUITS CALCULATIONS WHICH INDICATE A DATE OF |
| 9/25/01? |
| |
| PLEASE SEE FBC 2004 CHAPTER 11. , MORE SPECIFICALLY |
| 11-4.28, .1.2, AND .3(4). PLEASE ALSO SEE NFPA-72 |
| 2002. |
| THIS MAY OR MAY NOT CHANGE ACTUAL SHOWN UNITS. AS FOR |
| MINIMUM CANDELA LEVELS SEE ABOVE AS NOTED. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| |