Plan Review Notes
Plan Review Notes For Permit 06110349
Permit Number 06110349
Review Stop E
Sequence Number 1
Notes
Date Text
2006-12-04 13:03:12**** UNSAT ****
  
 PERMIT # 06110349
 BUILDING # 3
 PLEASE KNOW THAT THE ADDRESS SHALL BE PLACE ON THE
 PLANS TITLE BLOCK AS IT HAS NOW BEEN DESIGNATED TO THIS
 BUILDING LOCATION.
  
 1) NOTE: PLEASE KNOW THAT THE PLANS HAVE ONLY BEEN
 SUBMITTED FOR "PLAN REVIEW" ONLY AND HAVE NOT BEEN
 SUBMITTED FOR PERMIT AT THIS TIME. PLEASE KNOW AS OF
 DECEMBER 8TH 2006 THE STATE OF FLORIDA WILL ADOPT THE
 NEW 2005 NATIONAL ELECTRICAL CODE NFPA-70. PLEASE ALSO
 KNOW THAT THE NEW 2006 REVISIONS TO THE 2004 FBC WILL
 ALSO GO INTO AFFECT.
 PLEASE KNOW THAT AS PERMITS HAVE NOT BEEN APPLIED FOR
 AT THIS TIME ALL NEW CODES AFTER THIS DATE WILL BE
 REQUIRED TO BE MET.
  
 2) NOTE: PLEASE BE SURE ALL THE FOLLOWING RELEVANT
 CODES ARE REFLECTED ON PLANS.
 2002 NFPA-70 ONLY IF A PERMIT IS APPLIED FOR BY THE 8TH
 OF DEC. PLEASE REFLECT THE 2005 NFPA-70, 2002 NFPA-72,
 2003 NFPA-101, 2003 NFPA-20 AND THE 2004 FBC.
  
 3) NOTE: PLEASE SEE FBC 2004 CHAPTER 13.
 PLEASE SEE ENERGY CALCULATIONS WHICH INDICATE "MANUAL"
 FOR THE MEANS OF CONTROL FOR LIGHTING. PLEASE SEE
 ENERGY CALCULATIONS WHICH MENTIONS "NONE ENTERED" FOR
 EXTERIOR LIGHTING, HOWEVER PLANS DO INDICATE THIS.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2, AND .1.3. PLEASE SEE
 13-415.1.AB.1, 13-415.2.ABC.1.
 PLEASE SEE SOME OF THE INTERIOR LIGHTS ARE BEING SHOWN
 CIRCUITED THROUGH THE LIGHTING CONTROL PANELS AND NOTED
 AS EXTERIOR LIGHTS WHEN THESE ARE INTERIOR FIXTURES.
 PLEASE SEE ALL AREAS WHICH CONTAIN FLOOR TO CEILING
 HEIGHT PARTITIONS SHALL ALSO CONTAIN LIGHTING CONTROL
 BY ONE OF THE MEANS AS STATED IN THE CODE. THIS OFFICE
 DOES NOT REQUIRE ONE DESIGN OVER ANOTHER.
 PLEASE SEE MORE THAN OPTION IS AVAILABLE. PLEASE BE
 SURE TO CORRELATE CIRCUITING AS AN EXAMPLE OF CIRCUIT
 "3HP-5". ON THE LIGHTING CONTROL PANEL IS SHOWS THIS
 CIRCUIT AS FEEDING EXTERIOR LIGHTS, YET ON PLANS THIS
 IS THE CIRCUIT WHICH FEEDS THE INTERIOR LIGHTS. PLEASE
 ALSO SEE THAT ALL EMERGENCY AND EXIT LIGHTS SHALL BE
 SHOWN IN DETAIL WIRED ON THE LINE SIDE OF ANY LIGHTING
 CONTROL PANEL. (700.12E).
  
  
 4) NOTE: PLEASE SEE NFPA-101 7.8 AND 7.9, WHICH MAY
 ALSO BE PART OF THE FIRE REVIEWER COMMENTS WITH RESPECT
 TO A MINIMUM OF LIGHTING REQUIRED IN SPACE UNTIL SUCH
 TIME FOR TENANT BUILD OUT. PLEASE SEE THAT MINIMUM
 BATTERY BACK UP LIGHTS OF SOME KIND WILL BE REQUIRED
 FOR EGRESS AREAS WHICH INCLUDE EXTERIOR STAIRS TO THE
 PUBLIC RIGHT OF WAY. PLEASE SEE MINIMUM FOOT CANDLES
 UNDER NORMAL POWER AND MINIMUM FOOT CANDLES REQUIRED
 UNDER EMERGENCY POWER. 7.8.1.3, 7.9.2.2. PLEASE KNOW
 THESE LIGHTING LEVELS SHOWN ON PHOTO-METRICS WILL BE
 REQUIRED ON ELECTRICAL PLANS FOR REVIEW WHETHER OR NOT
 THESE COMMENTS ARE MADE BY FIRE REVIEW.
  
 5) NOTE: PLEASE SEE 230.2E WHICH SPEAKS OF SIGNAGE
 REQUIRED FOR ALL SERVICE FEEDING ONE BUILDING. PLEASE
 SEE THAT RISER ONLY INDICATES 2-MAINS FOR THIS
 BUILDING, WHEN IN FACT THE MAIN FOR THE FIRE PUMP
 SHOULD ALSO BE NOTED AND LABELED. PLEASE ALSO PLACE
 NOTES ON RISER FOR SIGNAGE WHICH WILL BE REQUIRED FOR
 ALL MAINS AND SERVICE LOCATIONS. PLEASE SEE AS THE
 JOCKEY PUMP IS BEING FED FROM THE NORMAL HOUSE PANEL,
 THIS SHALL ALSO BE LABELED ACCORDINGLY. 695.4(B)3
  
 6) NOTE: PLEASE SUBMIT THE MANUFACTURE SPEC/CUT SHEETS
 FOR THE FIRE PUMP AND FIRE PUMP CONTROLLER.THIS IS
 REQUIRED UNDER THE BASE BUILDING PLANS FOR REVIEW OF
 CODE COMPLIANCE FOR THE BUILDINGS ELECTRICAL SYSTEM AND
 FEEDS TO THIS PUMP. PLEASE KNOW EVEN THOUGH THE FIRE
 SPRINKLER SYSTEM IS UNDER A SEPARATE PERMIT. PLEASE SEE
 NFPA-20 2003, PLEASE SEE 9.3, 9.3.2.2 ALL SECTIONS
 FOLLOWING. PLEASE SEE WHERE LOCKED ROTOR CURRENT SHALL
 BE MARKED, DISCONNECTING MEANS, ISOLATING SWITCHES ETC
 SHALL BE SHOWN WITH PLANS AND SPECS SHEETS SUBMITTED.
 PLEASE ALSO SEE NEC 695.4(B)(1). PLEASE SEE CHAPTER 10
 OF NFPA-20 10.3.6, 10.4.2, 10.4.2.2 ETC.
 PLEASE KNOW THIS OFFICE IS UNABLE TO REVIEW FOR MANY
 CODE COMPLIANCE ITEMS AT THIS TIME AS THE ABOVE
 INFORMATION WAS NOT SUBMITTED.
 PLEASE SEE 110.3, AND 90.7.
 PLEASE SEE FBC ADMIN SECTION 106.1.2, 106.3.5.1.1PARA
 5
  
 7) NOTE: PLEASE SEE NFPA-72 AS THE BREAKER WHICH FEEDS
 THE FIRE ALARM CONTROL PANEL (FACP) SHALL BE A BREAKER
 WHICH CONTAINS A "LOCK-ON" DEVICE WHICH IS AN INTEGRAL
 PART OF THE BREAKER. PLEASE KNOW THAT A "SNAP ON" TYPE
 DEVICE WILL NOT BE ACCEPTABLE TO THE AHJ. NFPA-72.
 4.4.1.4.2.1THE DEDICATED BRANCH CIRCUIT(S) AND
 CONNECTIONS SHALL BE MECHANICALLY PROTECTED.
 4.4.1.4.2.2CIRCUIT DISCONNECTING MEANS SHALL HAVE A
 RED MARKING, SHALL BE ACCESSIBLE ONLY TO AUTHORIZED
 PERSONNEL, AND SHALL BE IDENTIFIED AS "FIRE ALARM
 CIRCUIT"
 4.4.1.4.2.3THE LOCATION OF THE CIRCUIT DISCONNECTING
 MEANS SHALL BE PERMANENTLY IDENTIFIED AT THE FIRE ALARM
 CONTROL UNIT.
 PLEASE ALSO SEE 90.7, 110.3 AND 90.4.
 THIS CAN BE ADDRESSED WITH IDENTIFICATION ON THE PANEL
 SCHEDULE AND A NOTE ON PANEL FOR TYPE OF BREAKER TO BE
 USED FOR THIS CIRCUIT.
  
 8) NOTE: PLEASE COMPLETE RISER FOR FIRE PUMP AS NOTED
 ABOVE FOR FEEDERS ETC.
 240.4, 310.16, 695, NFPA-20 CHAPTER 9
  
 9) NOTE: PLEASE INDICATE "FLOATING NEUTRAL" ON THE
 METERS ON THE SECONDARY SIDE OF THE PRIMARY MAIN.
 250.6, 250.24B.
  
 10) NOTE: PLEASE SUBMIT OR INDICATE REQUIREMENTS FOR
 WIND LOAD CALCULATIONS FOR BUILDING REVIEW FOR FBC 2004
 140MPH.
  
 11) NOTE: PLEASE CLARIFY THE NOTIFICATION APPLIANCE
 CIRCUITS CALCULATIONS WHICH INDICATE A DATE OF
 9/25/01?
  
 PLEASE SEE FBC 2004 CHAPTER 11. , MORE SPECIFICALLY
 11-4.28, .1.2, AND .3(4). PLEASE ALSO SEE NFPA-72
 2002.
 THIS MAY OR MAY NOT CHANGE ACTUAL SHOWN UNITS. AS FOR
 MINIMUM CANDELA LEVELS SEE ABOVE AS NOTED.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  
  
  