2006-12-11 14:40:55 | BUILDING PLAN REVIEW |
| PERMIT: 06110349 |
| ADD: 5720 PREMIER PARK DR. BLDG# 3 |
| CONT: "PLAN REVIEW" |
| TEL: (954)214-4039 ANDY PRIBY |
| |
| |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| * WEST PALM BEACH AMENDMENTS |
| |
| 1STREVIEW |
| ACTION: DENIED |
| |
| 1)--- VERY IMPORTANT STATEMENT --- |
| PLEASE DO NOT IGNORE! |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| 2)FL S S 713.13 |
| NOTICE OF COMMENCEMENT, TO BE FILED |
| WITH THE CLERK OF THE COURT BEFORE A |
| PERMIT WILL BE ISSUED. NOTE: 713.13(2) |
| IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS |
| NOT ACTUALLY COMMENCED |
| WITHIN 90 DAYS AFTER THE RECORDING |
| THEREOF, SUCH NOTICE IS NULL & VOID. |
| |
| 3)FL BLD CODE 1804.2.2 QUESTIONABLE |
| SOILS, WHERE THE BEARING CAPACITY IS |
| NOT DEFINETLY KNOWN OR IS IN QUESTION. |
| WHERE THE BEARING CAPACITY OF THE SOIL |
| IS NOT DEFINITLY KNOWN OR IS IN QUESTION |
| THE BUILDING OFFICIAL MAY REQUIRE EXPLOR |
| ATIONS, TEST OR OTHER ADEQUATE PROOF AS |
| TO THE PERMISSIBLE SAFE BEARING |
| CAPACITY. REQUIRED TEST AND RECOMMENDA- |
| TIONS SUBMITTED TO VERIFY BEARING CAPA- |
| CITY SHALL BE CERTIFIED BY A GEOTECH- |
| NICALREPORT FROM A DESIGN PROFESSIONAL |
| PROPERLY LICENSED IN THE STATE OF |
| FLORIDA. |
| |
| 4 A) FBC* 105.3RESIDENT INSPECTOR. |
| SUBMIT INSPECTOR RESUME' AND LICENSE |
| DOCUMENTS TO HAROLD PISKURA, DIRECTOR OF |
| THE RESIDENT INSPECTOR PROGRAM.A |
| RESIDENT INSPECTOR PROGRAM IS REQUIRED, |
| ON THIS PROJECT, DUE TO ONE OR MORE OF |
| THE FOLLOWING: |
| - BUILDINGS/ADDITIONS OF TYPE I OR II |
| CONSTRUCTION |
| - ANY MAJOR STRUCTURAL ALTERATIONS |
| - STRUCTURES IN WHICH THE CONCRETE |
| DESIGN IS BASED ON COMPRESSIVE |
| STRENGTH (F'C) IN EXCESS OF 3000 PSI |
| - PILE DRIVING |
| - BUILDINGS OVER 20,000 SQFT IN AREA |
| - BUILDINGS OVER 2 STORIES IN HEIGHT |
| - BUILDING/STRUCTURES OF UNUSUAL DESIGN |
| OR METHODS OF CONSTRUCTION |
| |
| 4B) SINCE THIS BUILDING WILL REQUIRE A RESIDENT |
| INSPECTOR |
| (3) SETS OF PLANS, REPORTS, AND OR OTHER REQUIRED |
| SUBMITTALS |
| WILL BE REQUIRED FOR REVIEW. |
| |
| 5) SHEET A-0 CODE ANALYSIS: |
| |
| 5A) CONSTRUCTION TYPE: PLANS INDICATE A BUILDING TYPE |
| IV(UNPROTECTED) |
| THIS TERMINOLGY IS FROM THE 2001 FBC PLEASE CORRECT, |
| UNDER THE CORRENT |
| CODE THIS BUILDING IS TO BE BUILT AS "HEAVY TIMBER" |
| CONSTRUCTION. |
| |
| 5B)IT APPEARS THAT THE CODE ANYLSIS IS A COMBINATION |
| OF ZONING & BUILDING. |
| PLEASE EXPLAIN WHY THE TOTAL BUILDING FOOTPRINT IS |
| 302,092 WHEREAS |
| ON SHEET A-1 BUILDING NUMBER 1 INDICATES THE SQ FT AREA |
| TO BE 119,291 SQ FT. |
| ALSO FURTHER DOWN THE PAGE BUILDING # 1 INDICATES |
| GROUND FLOOR AREA TO BE |
| 95,391 AND POSSIBLE MEZZANINE LEVEL OF 23,900 SQ. FT. |
| FOR THE PURPOSE OF |
| BUILDING PLANS EITHER YOU ARE GOING TO BUILD THE |
| MEZZANINE LEVEL UNDER THIS PERMIT |
| WHICH WILL INCLUDE THIS FIGURE, IF NOTTO BE BUILT |
| UNDER THIS PERMIT DO NOT INCLUDE IT. |
| |
| 5C) IN EITHER CASE PLEASE IDENTIFY THE MINIMUM BUILDING |
| TYPE AND IF IN TABLE 503 |
| THE PLANS ARE OVER THE ALLOWABLE SQUARE FOOTAGE, |
| INDICATE ANY INCREASES |
| TAKEN AND ALSO SHOW CALCULATIONS. |
| |
| 5D) THE PERMIT APPLICATION IS BLANK WHERE THE |
| DESCRIPTION OF PROJECT, |
| OR WORK TO BE COVERED UNDER THIS PERMIT. FOR THE |
| PURPOSES OF THIS REVIEW |
| THIS BUILDING WILL BE CONSIDERED A SHELL BUILDING |
| PERMIT. TENANT BUILD-OUTS TO BE UNDER |
| SEPERATE PERMITS. |
| |
| 5E) IS THIS SITE, ARE THE UNITS TO BE SOLD AS |
| CONDOMINIUMS? |
| |
| 5F) THE CODE ANALYSIS ALSO INDICATED THAT THIS IS TO BE |
| A FIRE SPRINKLERED |
| BUILDING BUT NO FIRE SPRINKLER PLANS , HYDROLICS,FIRE |
| PUMP OR FIRE PUMP CONTROLLERE |
| WERE SUBMITTED.FOR A BUILDING PERMIT TO BE ISSUED |
| FORMINIMUM PLAN REVIEW CRITERIA |
| 106.3.51.1(4)* FIRE SPRINKLER PLANS ARE REQUIRED. |
| 903.2.3 GROUP F-1. |
| AN AUTOMATIC SPRINKLER SYSTEM SHALL BE PROVIDED |
| THROUGHOUT ALL BUILDINGS |
| CONTAINING A GROUP F-1 OCCUPANCY WHERE ONE OF THE |
| FOLLOWING CONDITIONS EXISTS: |
| 1.WHERE A GROUP F-1 FIRE AREA EXCEEDS 12,000 SQUARE |
| FEET (1115 M 2 ). |
| |
| 6)SHEET A-6: |
| |
| 6A) SHEET A-6 , DISCREPANCY, |
| THE ELEVATIONS INDICATES DO NOT INDICATE THE PRESSURE |
| ZONES. |
| |
| 7)FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, |
| PROVIDE 2 COPIES(3 IF THRESH- |
| OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| TESTING REPORTS,MISSING REPORTS ARE AS |
| FOLLOWS: |
| A) STOREFRONT WINDOWS |
| B) MULLIONS |
| C) SKYLIGHTS |
| D) EXTERIOR GLAZED DOORS |
| E) EXTERIOR HOLLOW METAL DOORS |
| F) ROLL UP DOORS |
| G) LOUVERS |
| H) EFIS SYSTEMS |
| I) ROOFING ASSEMBLIES |
| |
| 1609.1.4 PROTECTION OF OPENINGS. |
| IN WIND-BORNE DEBRIS REGIONS, EXTERIOR |
| GLAZING THAT RECEIVES POSITIVE PRESSURE |
| IN THE LOWER 60 FEET (18.3 M) IN |
| BUILDINGS SHALL BE ASSUMED TO BE |
| OPENINGS AND THE BALANCE OF GLAZED |
| OPENINGS IN THE REST OF THE BUILDING |
| SHALL BE ASSUMED TO BE ZERO UNLESS SUCH |
| GLAZING THAT RECEIVES POSITIVE PRESSURE |
| IS IMPACT RESISTANT OR PROTECTED WITH AN |
| IMPACT RESISTANT COVERING MEETING THE |
| REQUIREMENTS OF SSTD 12, ASTM E 1886 AND |
| ASTM E 1996, OR MIAMI-DADE TAS 201, 202 |
| AND 203 REFERENCED THEREIN AS FOLLOWS: |
| 1.GLAZED OPENINGS LOCATED WITHIN 30 |
| FEET (9.1 M) OF GRADE SHALL MEET THE |
| REQUIREMENTS OF THE LARGE MISSILE TEST. |
| 2.GLAZED OPENINGS LOCATED MORE THAN |
| 30 FEET (9.1 M) ABOVE GRADE SHALL MEET |
| THE PROVISIONS OF THE SMALL MISSILE |
| TEST. |
| |
| 8)PRODUCT APPROVALS SUBMITTED WITH |
| PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| PLEASE SEE THE STATE WEBSITE AT |
| WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| STATEWIDE APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A COVER SHEET THAT LISTS |
| THE PRODUCT IDENTITY NUMBER FROM THE |
| STATE. IF THE PRODUCT DOES NOT HAVE |
| STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| SPECIFIC FORM PER RULE 9B-72. SEE |
| ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| |
| 9)WPB ADMIN CODE 106.3* PRODUCT |
| APPROVALS. THOSE PRODUCT WHICH ARE |
| REGULATED BY DCA RULE 9B-72 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| FOR JURISDICTIONAL APPROVAL. |
| |
| 10) THIS SUBMITTAL DOESN'T INCORORATE ANY ROOFING |
| PRODUCT APPROVALS, |
| HERE IS A LIST OF COMMON ISSUES THAT WILL FAIL A |
| ROOFING REPORT SUBMITTAL: |
| THIS ROOF IS MISSING OR NOT INCOMPLIANCE WITH THE |
| FOLLOW ITEMS: |
| |
| ___ CONTRACTOR DID NOT PROVIDE THE MEAN |
| |
| ROOF HEIGHT. |
| |
| ___ CONTRACTOR DID NOT INDICATE THE ROOF |
| PITCH. |
| |
| ___ CONTRACTOR FAILED TO INDICATE WHICH |
| SYSTEM OR SUBSYSTEM WILL BE USED. |
| |
| ___ THE SYSTEM PROVIDED HAS A LOW |
| PRESSURE FOR ZONE ___ . |
| |
| ___ THE SYSTEM PROVIDED STATES |
| LIMITATION# 7, SHOULD THE FASTENER |
| RESISTANCE BE LESS THAN THAT |
| REQUIRED, AS DETERMINED BY THE |
| BUILDING OFFICIAL, A REVISED |
| FASTENER SPACING, PREPARED , SIGNED |
| AND SEALED BY A FLORIDA REGISTERED |
| PROFESSIONAL ENGINEER, REGISTERED |
| ARCHITECT OR REGISTERED ROOF |
| CONSULTANT MAY BE SUBMITTED. |
| |
| ___THE SYSTEM PROVIDED INDICATES |
| LIMITATION# 9, NO ENHANCED |
| FASTENING ALLOWED. |
| |
| |
| 11) SHEET A-8 PRECAST MOULDING DETAIL IS MISSING DETAIL |
| REFRENCE NUMBER. |
| FOUND ON SHEET A-15 DETAIL # 7. PLEASE PROVIDE |
| CALCULATIONS WITH SAFETY |
| FACTOR FOR THE SECURING THIS WEIGHT IN THIS |
| MANNER.106.1.2*ADDITIONAL INFORMATION REQUIRED. |
| |
| 12)SHEET A-11 DETAIL # 3 INDICATES THE FIRE PUMP ROOM |
| TO ALSO BE USED AS ASTORAGE ROOM? |
| |
| 13) SHEET A-11 VARIOUS DETAILS INDICATE THE TRIANGLE |
| AREA CREATED BY THE RISER AND TREAD, |
| 1012.3 LIMITS THIS AREA THA A 6"SPHERE CAN NOT PASS |
| THROUGH. THE WORDING ON THE |
| PLAN IS NOT CLEAR WHAT THE 6" IS FOR. |
| |
| 14)SHEET A-14 DEPENDING ON THE BUILDING TYPE TO BE |
| DECLAIRED, THE PLYOOD IN THE EXTERIOR WALLS MAY BE OF |
| CONCERN. TABLE 601 &602. |
| |
| 15)NOTE WITH THE PRODUCT APPROVALS NOT SUBMITTED THE |
| ROLL UP DOORS MAY OR MAY NOT REQUIRE DOOR BUCKS AND |
| ATTACHMENT. |
| |
| 16)BEFORE A PERMIT TO CONSTRUCT, MAY |
| BE ISSUED, IMPACT FEES MUST BE PAID TO |
| PALM BEACH COUNTY. THE ACTUAL PERMIT |
| SET OF PLANS MUST BE STAMPED BY THAT |
| OFFICE, AND A COPY OF THE PAID RECEIPT |
| ATTACHED TO THE PERMIT APPLICATION. |
| PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| BUILDING PLAN REVIEW |
| JIM WITMER |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |
| E-MAIL: [email protected] |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |