2006-12-11 14:40:55BUILDING PLAN REVIEW
 PERMIT: 06110349
 ADD: 5720 PREMIER PARK DR. BLDG# 3
 CONT: "PLAN REVIEW"
 TEL: (954)214-4039 ANDY PRIBY
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3)FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 WHERE THE BEARING CAPACITY OF THE SOIL
 IS NOT DEFINITLY KNOWN OR IS IN QUESTION
 THE BUILDING OFFICIAL MAY REQUIRE EXPLOR
 ATIONS, TEST OR OTHER ADEQUATE PROOF AS
 TO THE PERMISSIBLE SAFE BEARING
 CAPACITY. REQUIRED TEST AND RECOMMENDA-
 TIONS SUBMITTED TO VERIFY BEARING CAPA-
 CITY SHALL BE CERTIFIED BY A GEOTECH-
 NICALREPORT FROM A DESIGN PROFESSIONAL
 PROPERLY LICENSED IN THE STATE OF
 FLORIDA.
  
 4 A) FBC* 105.3RESIDENT INSPECTOR.
 SUBMIT INSPECTOR RESUME' AND LICENSE
 DOCUMENTS TO HAROLD PISKURA, DIRECTOR OF
 THE RESIDENT INSPECTOR PROGRAM.A
 RESIDENT INSPECTOR PROGRAM IS REQUIRED,
 ON THIS PROJECT, DUE TO ONE OR MORE OF
 THE FOLLOWING:
 - BUILDINGS/ADDITIONS OF TYPE I OR II
 CONSTRUCTION
 - ANY MAJOR STRUCTURAL ALTERATIONS
 - STRUCTURES IN WHICH THE CONCRETE
 DESIGN IS BASED ON COMPRESSIVE
 STRENGTH (F'C) IN EXCESS OF 3000 PSI
 - PILE DRIVING
 - BUILDINGS OVER 20,000 SQFT IN AREA
 - BUILDINGS OVER 2 STORIES IN HEIGHT
 - BUILDING/STRUCTURES OF UNUSUAL DESIGN
 OR METHODS OF CONSTRUCTION
  
 4B) SINCE THIS BUILDING WILL REQUIRE A RESIDENT
 INSPECTOR
 (3) SETS OF PLANS, REPORTS, AND OR OTHER REQUIRED
 SUBMITTALS
 WILL BE REQUIRED FOR REVIEW.
  
 5) SHEET A-0 CODE ANALYSIS:
  
 5A) CONSTRUCTION TYPE: PLANS INDICATE A BUILDING TYPE
 IV(UNPROTECTED)
 THIS TERMINOLGY IS FROM THE 2001 FBC PLEASE CORRECT,
 UNDER THE CORRENT
 CODE THIS BUILDING IS TO BE BUILT AS "HEAVY TIMBER"
 CONSTRUCTION.
  
 5B)IT APPEARS THAT THE CODE ANYLSIS IS A COMBINATION
 OF ZONING & BUILDING.
 PLEASE EXPLAIN WHY THE TOTAL BUILDING FOOTPRINT IS
 302,092 WHEREAS
 ON SHEET A-1 BUILDING NUMBER 1 INDICATES THE SQ FT AREA
 TO BE 119,291 SQ FT.
 ALSO FURTHER DOWN THE PAGE BUILDING # 1 INDICATES
 GROUND FLOOR AREA TO BE
 95,391 AND POSSIBLE MEZZANINE LEVEL OF 23,900 SQ. FT.
 FOR THE PURPOSE OF
 BUILDING PLANS EITHER YOU ARE GOING TO BUILD THE
 MEZZANINE LEVEL UNDER THIS PERMIT
 WHICH WILL INCLUDE THIS FIGURE, IF NOTTO BE BUILT
 UNDER THIS PERMIT DO NOT INCLUDE IT.
  
 5C) IN EITHER CASE PLEASE IDENTIFY THE MINIMUM BUILDING
 TYPE AND IF IN TABLE 503
 THE PLANS ARE OVER THE ALLOWABLE SQUARE FOOTAGE,
 INDICATE ANY INCREASES
 TAKEN AND ALSO SHOW CALCULATIONS.
  
 5D) THE PERMIT APPLICATION IS BLANK WHERE THE
 DESCRIPTION OF PROJECT,
 OR WORK TO BE COVERED UNDER THIS PERMIT. FOR THE
 PURPOSES OF THIS REVIEW
 THIS BUILDING WILL BE CONSIDERED A SHELL BUILDING
 PERMIT. TENANT BUILD-OUTS TO BE UNDER
 SEPERATE PERMITS.
  
 5E) IS THIS SITE, ARE THE UNITS TO BE SOLD AS
 CONDOMINIUMS?
  
 5F) THE CODE ANALYSIS ALSO INDICATED THAT THIS IS TO BE
 A FIRE SPRINKLERED
 BUILDING BUT NO FIRE SPRINKLER PLANS , HYDROLICS,FIRE
 PUMP OR FIRE PUMP CONTROLLERE
 WERE SUBMITTED.FOR A BUILDING PERMIT TO BE ISSUED
 FORMINIMUM PLAN REVIEW CRITERIA
 106.3.51.1(4)* FIRE SPRINKLER PLANS ARE REQUIRED.
 903.2.3 GROUP F-1.
 AN AUTOMATIC SPRINKLER SYSTEM SHALL BE PROVIDED
 THROUGHOUT ALL BUILDINGS
 CONTAINING A GROUP F-1 OCCUPANCY WHERE ONE OF THE
 FOLLOWING CONDITIONS EXISTS:
 1.WHERE A GROUP F-1 FIRE AREA EXCEEDS 12,000 SQUARE
 FEET (1115 M 2 ).
  
 6)SHEET A-6:
  
 6A) SHEET A-6 , DISCREPANCY,
 THE ELEVATIONS INDICATES DO NOT INDICATE THE PRESSURE
 ZONES.
  
 7)FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) STOREFRONT WINDOWS
 B) MULLIONS
 C) SKYLIGHTS
 D) EXTERIOR GLAZED DOORS
 E) EXTERIOR HOLLOW METAL DOORS
 F) ROLL UP DOORS
 G) LOUVERS
 H) EFIS SYSTEMS
 I) ROOFING ASSEMBLIES
  
 1609.1.4 PROTECTION OF OPENINGS.
 IN WIND-BORNE DEBRIS REGIONS, EXTERIOR
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IN THE LOWER 60 FEET (18.3 M) IN
 BUILDINGS SHALL BE ASSUMED TO BE
 OPENINGS AND THE BALANCE OF GLAZED
 OPENINGS IN THE REST OF THE BUILDING
 SHALL BE ASSUMED TO BE ZERO UNLESS SUCH
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IS IMPACT RESISTANT OR PROTECTED WITH AN
 IMPACT RESISTANT COVERING MEETING THE
 REQUIREMENTS OF SSTD 12, ASTM E 1886 AND
 ASTM E 1996, OR MIAMI-DADE TAS 201, 202
 AND 203 REFERENCED THEREIN AS FOLLOWS:
 1.GLAZED OPENINGS LOCATED WITHIN 30
 FEET (9.1 M) OF GRADE SHALL MEET THE
 REQUIREMENTS OF THE LARGE MISSILE TEST.
 2.GLAZED OPENINGS LOCATED MORE THAN
 30 FEET (9.1 M) ABOVE GRADE SHALL MEET
 THE PROVISIONS OF THE SMALL MISSILE
 TEST.
  
 8)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 9)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 10) THIS SUBMITTAL DOESN'T INCORORATE ANY ROOFING
 PRODUCT APPROVALS,
 HERE IS A LIST OF COMMON ISSUES THAT WILL FAIL A
 ROOFING REPORT SUBMITTAL:
 THIS ROOF IS MISSING OR NOT INCOMPLIANCE WITH THE
 FOLLOW ITEMS:
  
 ___ CONTRACTOR DID NOT PROVIDE THE MEAN
  
 ROOF HEIGHT.
  
 ___ CONTRACTOR DID NOT INDICATE THE ROOF
 PITCH.
  
 ___ CONTRACTOR FAILED TO INDICATE WHICH
 SYSTEM OR SUBSYSTEM WILL BE USED.
  
 ___ THE SYSTEM PROVIDED HAS A LOW
 PRESSURE FOR ZONE ___ .
  
 ___ THE SYSTEM PROVIDED STATES
 LIMITATION# 7, SHOULD THE FASTENER
 RESISTANCE BE LESS THAN THAT
 REQUIRED, AS DETERMINED BY THE
 BUILDING OFFICIAL, A REVISED
 FASTENER SPACING, PREPARED , SIGNED
 AND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER, REGISTERED
 ARCHITECT OR REGISTERED ROOF
 CONSULTANT MAY BE SUBMITTED.
  
 ___THE SYSTEM PROVIDED INDICATES
 LIMITATION# 9, NO ENHANCED
 FASTENING ALLOWED.
  
  
 11) SHEET A-8 PRECAST MOULDING DETAIL IS MISSING DETAIL
 REFRENCE NUMBER.
 FOUND ON SHEET A-15 DETAIL # 7. PLEASE PROVIDE
 CALCULATIONS WITH SAFETY
 FACTOR FOR THE SECURING THIS WEIGHT IN THIS
 MANNER.106.1.2*ADDITIONAL INFORMATION REQUIRED.
  
 12)SHEET A-11 DETAIL # 3 INDICATES THE FIRE PUMP ROOM
 TO ALSO BE USED AS ASTORAGE ROOM?
  
 13) SHEET A-11 VARIOUS DETAILS INDICATE THE TRIANGLE
 AREA CREATED BY THE RISER AND TREAD,
 1012.3 LIMITS THIS AREA THA A 6"SPHERE CAN NOT PASS
 THROUGH. THE WORDING ON THE
 PLAN IS NOT CLEAR WHAT THE 6" IS FOR.
  
 14)SHEET A-14 DEPENDING ON THE BUILDING TYPE TO BE
 DECLAIRED, THE PLYOOD IN THE EXTERIOR WALLS MAY BE OF
 CONCERN. TABLE 601 &602.
  
 15)NOTE WITH THE PRODUCT APPROVALS NOT SUBMITTED THE
 ROLL UP DOORS MAY OR MAY NOT REQUIRE DOOR BUCKS AND
 ATTACHMENT.
  
 16)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  