Plan Review Notes
Plan Review Notes For Permit 06110337
Permit Number 06110337
Review Stop P
Sequence Number 1
Notes
Date Text
2006-12-11 09:38:27DENIED;
 1.PRINTED NAME AND LICENSE NUMBER REQUIRED. SEE
 ELECTRICAL PLAN REVIEWER'S NOTE.
 2. NO DEAD ENDS PERMITED IN THE DRAINAGE SYSTEM. ALL
 SANITARYAND VENT PIPING THAT WILL NOT BE RE-USED IN
 THE SAME LOCATION SHALL BE REMOVED TO WITHIN 2' OF THE
 BUILDING DRAIN. FBC-2004 PLUMBING SECTION 704.5.
 3. A PLUMBING PERMIT IS REQUIRED BY A LICENSED PLUMBING
 CONTRACTOR TO DO THE PLUMBING DEMO. PLUMBING
 INSPECTIONS REQUIRED
 PLEASE ADD NOTES ON PLANS TO COVER NOTE 2 AND 3
 .
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695