Plan Review Notes
Plan Review Notes For Permit 06110337
Permit Number 06110337
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-12-12 09:43:58*****PROVISO*****
  
  
  
 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT
 INTERFERE OR HINDER EMERGENCY ACCESS TO THE SAID
 PROPERTY OF THE VICINITY THEREOF.
  
 3.COMBUSTIBLE WASTE, DUST, AND DEBRIS SHALL BE
 REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR MORE
 FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 4.DEMOLITION PLAN NOTE #7 STATES" FIRE ALARM PANEL
 TO REMAIN " .WILL THE FIRE ALARM SYSTEM BE
 OPERATIONAL DURING DEMOLITION OPERATIONS?IF SO, WHAT
 MEASURE(S) WILL BE UTILIZED TO PREVENT FALSE FIRE
 ALARMS?
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722