Date |
Text |
2007-01-25 13:04:38 | *** UNSAT 2ND REVIEW** |
| |
| 1) NOTE:PLEASE SEE NOTES FROM PREVIOUS REVIEW. PLANS |
| AND SHEETS FOR EQUIPMENT, LIGHTING FEEDS ETC DO NOT |
| CORRELATE. PLEASE SEE THERE ARE SEVERAL DIFFERENCES. |
| NO GFI PROTECTION, ETC. |
| |
| ** PLEASE CORRELATE ALL SHEETS; PLEASE COMPLETE PLANS |
| FOR 2002 NEC, 215.5, 680, 240.4, 310.16 ETC FOR CODE |
| COMPLIANCE. |
| |
| 2) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| REPEAT COMMENTS FOR CODE COMPLIANCE. ONE SET OF ELEC IS |
| BEING RETAINED SHEETS 4 AND 5. |
| |
| 3) NOTE:PLEASE KNOW THAT THE PLANS FOR THE ELECTRICAL |
| DETAIL SHALL BE SPECIFIC TO THE SCOPE OF WORK ON THE |
| JOB APPLIED FOR. PLEASE CORRELATE EQUIPMENT WITH NEW |
| PROPOSED PANEL SCHEDULE AS SOME EQUIPMENT SHOWN IS NOT |
| ON SCHEDULE? |
| PLEASE SEE THE PANELS AS SHOWN ON PLANS DO NOT |
| CORRELATE. |
| 408.4, 310.16, |
| FBC 106.1.2 |
| FBC 106.3.5.1.2,106.3.5.5 ADMIN SECTION. |
| |
| 4) NOTE: PLEASE LIST THE FEEDER TO THE NEW VAK-PAK |
| PANEL. |
| 215.5, 215.3. |
| |
| 5) NOTE: PLEASE COMPLETE THE LOAD CALCULATIONS FOR ALL |
| AND INDICATE THE CONTINUOUS LOADS AT 125%. |
| 215.3, 230.42 ETC. |
| ** PLEASE BE SURE TO KEEP ANY SHEETS WHICH CONTAIN |
| PLUMBING STAMPS. |
| |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |