Date |
Text |
2006-11-21 16:08:51 | *** UNSAT*** |
| |
| ** PLEASE KNOW PERMIT PACKAGE CONTAIN ONE PLAN FOR |
| COMMERCIAL POOL AND ONE FOR FOUNTAIN. LOCATED THE OTHER |
| SET OF PLANS AND PLACED ALL SETS IN TO EACH OF THEIR |
| RESPECTIVE PACKAGES. |
| |
| 1) NOTE:PLEASE KNOW THAT THE PLANS FOR THE ELECTRICAL |
| DETAIL SHALL BE SPECIFIC TO THE SCOPE OF WORK ON THE |
| JOB APPLIED FOR. PLEASE CORRELATE EQUIPMENT WITH NEW |
| PROPOSED PANEL SCHEDULE AS SOME EQUIPMENT SHOWN IS NOT |
| ON SCHEDULE? |
| 408.4, 310.16, |
| FBC 106.1.2 |
| FBC 106.3.5.1.2,106.3.5.5 ADMIN SECTION. |
| |
| 2) NOTE: PLEASE KNOW AS THIS IS A THRESHOLD/ON-SITE |
| INSPECTOR JOB, THREE SETS OF ALL PLANS MUST BE |
| SUBMITTED. |
| 109.3.6, 106.1.2 ADMIN SECTION. |
| |
| 3) NOTE: PLEASE KNOW THAT NO WHITE OUT OR HAND WRITTEN |
| CHANGES MAY BE DONE TO PLANS WHICH ARE SIGNED, DATED OR |
| SEALED BY AN ENGINEER. |
| PLEASE ALSO SEE THAT ATTACHED SHEETS CHANGING OR |
| MODIFYING PLANS IN ANY WAY IS ALSO NOT PERMITTED UNLESS |
| DONE BY THE ENGINEER OF RECORD, SIGNED, DATED, SEALED |
| ALONG WITH TITLE BLOCKS AS REQUIRED PER FAC |
| 61G15-23.002, FS 471.025 |
| |
| 4) NOTE: PLEASE LIST THE FEEDER TO THE NEW VAK-PAK |
| PANEL. |
| 215.5, 215.3. |
| |
| 5) NOTE: PLEASE COMPLETE THE LOAD CALCULATIONS FOR ALL |
| AND INDICATE THE CONTINUOUS LOADS AT 125%. |
| 215.3, 230.42 ETC. |
| |
| |
| ** PLEASE KNOW AS INFORMATION NEEDED WAS NOT SUBMITTED |
| AT THIS TIME THEIR MAY BE COMMENTS ON THE FOLLOWING |
| REVIEW |
| |
| ** ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| **PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. |
| |
| **IF THERE ARE ANY QUESTIONS, COMMENTSOR IF ANY OF |
| THE NOTES TYPEDWHICH ARE UNCLEAR IN ANY WAY, PLEASE |
| DO NOT HESITATEIN CONTACTING THIS REVIEWER. |
| |
| |
| |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |