Plan Review Notes For Permit 06110298 |
Permit Number |
06110298 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-11-28 10:39:14 | ************PROVISO************ | | 1. WATER-HAMMER ARRESTORS TO BE INSTALLED PER FBC-2004 | | PLUMBING, SECTION 604.9. | | 2. FULL-OPEN VALVE REQUIRED ON THE WATER SUPPLY PIPE TO | | EVERY WATER HEATER PER FBC 2004 PLUMBING, SECTION | | 606.1. | | 3. THERMAL EXPANSION CONTROL REQUIRED PER FBC-2004 | | PLUMBING, SECTION 607.3. | | 4. ONLY THE FIXTURES WITHIN THE BATHROOM GROUPS SHALL | | CONNECT TO THE WET-VENTED HORIZONTAL BRANCH DRAIN. ANY | | ADDITIONAL FIXTURES SHALL DISCHARGE DOWNSTREAM OF THE | | WET VENT. PER FBC-2004 PLUMBING, SECTION 909.1. |
|