Plan Review Notes For Permit 06110152
Permit Number 06110152
Review Stop P
Sequence Number 9
Notes
Date Text
2009-04-14 10:45:58DENIED
 REFERENCE:
 FBC-2004 PLUMBING
  
 1. SHT P2.2.2 SUBMIT CALCULATIONS FOR THE EXISTING ROOF
 DRAINS THAT HAVE THE ADDED VERTICAL CONTRIBUTION FROM
 THE NEW ADDIITION PLEASE INDICATE TOTAL SQUARE FOOTAGE
 BEING DRAINED BY THE DRAINS ADJACENT TO THE NEW
 ADDITION. SHOW EXISTING SF AND 1/2 AREA OF NEW VERTICAL
 WALL ADDED TO SF. INDICATE THE SIZE OF THE EXISTING
 ROOF DRAINS AND THE SIZE OF THE EXISTING ROOF LEADERS.
 SECTIONS 1106 & 1107 WITH ALL SUBSECTIONS. SHOW ALL
 SECONDARY ROOF DRAINS/SCUPPERS AND INDICATE THE SIZE OF
 THE SECONDARY ROOF DRAINS/SCUPPERS AND THE SIZE OF THE
 LEADERS OF THE SECONDARY ROOF DRAINS. THE REASON FOR
 THIS COMMENT IS BECAUSE OF THE FACT THAT THE ROOF
 DRAINS BEING DELETED WERE SHOWN ON THE PLANS TO ADDRESS
 THE VERTICAL CONTRIBUTION FROM THE NEW BUILDING.
 ****RESPONSE INDICATES THAT THE EXISTING ROOF HAS
 GUTTERS & DOWNSPOUTS. WITH THE NEW VERTICAL
 CONTRIBUTION THE CALCULATIONS WILL STILL BE REQUIRED
 FOR SIZING THE GUTTERS AND DOWNSPOUTS. PLEAS SUBMIT THE
 CALCULATIONS AS WELL AS THE GUTTER SIZE, DOWNSPOUT
 SIZE, LOCATION OF DOWNSPOUTS, AND INDICATE THE SLOPE OF
 THE GUTTERS INDICATING THE HIGH POINT OF THE GUTTERS
 AND DIRECTION OF FLOW TO THE DOWNSPOUTS. TABLES 1106.3
 & 1106.6.
  
 **********NEW COMMENT**********
  
 1B. SHT P6.1 THE RISER DIAGRAM DOES NOT REFLECT THE
 FLOOR PLAN BY THE DRINKING FOUNTAIN. THE RISER DIAGRAM
 SHOWS A NEW CONNECTION LOCATION FOR THE HOT & COLD
 WATER TO THE 2 INCH WATER MAIN, DOES NOT SHOW THE LINES
 TO THE ROOF AS SHOWN ON THE FLOOR PLAN, AND DOES NOT
 SHOW THE OLD CONNECTION TO THE WATER MAINS AS SHOWN ON
 THE FLOOR PLAN. PLEASE CORRELATE THE RISER WITH THE
 FLOOR PLAN. SECTIONS 106.1.1 & 601.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  