Plan Review Notes
Plan Review Notes For Permit 06110152
Permit Number 06110152
Review Stop P
Sequence Number 7
Notes
Date Text
2009-02-24 09:54:01DENIED
 REFERENCE:
 FBC-2004 PLUMBING
  
 1. SHTS P2.2.2 & P5.2 SUBMIT CALCULATIONS FOR THE
 EXISTING ROOF DRAINS THAT HAVE THE ADDED VERTICAL
 CONTRIBUTION FROM THE NEW ADDIITION PLEASE INDICATE
 TOTAL SQUARE FOOTAGE BEING DRAINED BY THE DRAINS
 ADJACENT TO THE NEW ADDITION. SHOW EXISTING SF AND 1/2
 AREA OF NEW VERTICAL WALL ADDED TO SF. INDICATE THE
 SIZE OF THE EXISTING ROOF DRAINS AND THE SIZE OF THE
 EXISTING ROOF LEADERS. SECTIONS 1106 & 1107 WITH ALL
 SUBSECTIONS. SHOW ALL SECONDARY ROOF DRAINS/SCUPPERS
 AND INDICATE THE SIZE OF THE SECONDARY ROOF
 DRAINS/SCUPPERS AND THE SIZE OF THE LEADERS OF THE
 SECONDARY ROOF DRAINS. THE REASON FOR THIS COMMENT IS
 BECAUSE OF THE FACT THAT THE ROOF DRAINS BEING DELETED
 WERE SHOWN ON THE PLANS TO ADDRESS THE VERTICAL
 CONTRIBUTION FROM THE NEW BUILDING.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  