2009-02-13 14:13:04 | ** DENIED REVIEW ** |
| |
| REVISIONS |
| |
| |
| 1) NOTE: PLEASE GO THROUGH AND COORDINATE ALL CHANGES |
| AND REVISIONS. |
| |
| FOR EXAMPLE: SHEET E4.1 NOW HAS EQUIPMENT AND MAINS IN |
| THE MAIN ELECTRICAL ROOM REMOVED HOWEVER THE POWER |
| PLANS STILL SHOW THIS EQUIPMENT AND OTHER EQUIPMENT. IF |
| THIS EQUIPMENT AND OTHERS ARE NO LONGER LOCATED IN THIS |
| ROOM PLEASE SUBMIT PLANS FOR NEW LOCATION(S). |
| 110.26,240.24, 230.71,230.71 ETC |
| |
| FOR EXAMPLE: PLEASE SEE RISER AS MAIN IS STILL NOTED AS |
| MAIN 2 OF 2. THIS WOULD BE MAIN ONE IF THIS IS STILL A |
| SEPARATE BUILDING AS STATED IN PREVIOUS REVIEWS AND |
| REVISIONS. |
| 230.2E |
| |
| FOR EXAMPLE: RISER NOW SHOWS A REVISION WITH THE |
| ADDITION OF A NEW PANEL *L2AB* HOWEVER THE RISER SHOWS |
| THIS PANEL BEING FED FROM *DP2A*. IF YOU GO TO THE |
| PANEL *DP2A* YOU WILL NOT FIND ANY SUCH PANEL. |
| |
| ** PLEASE COORDINATE ALL OF THE ABOVE. |
| 215.5,230,240,220 ETC |
| |
| 2) NOTE: PLEASE REMOVE DESIGNATION OF IT ROOM FROM ALL |
| SHEETS AS THIS DOES NOT MEET 645.4. PLEASE ALSO INCLUDE |
| NOTE WHICH WILL STATE: |
| THIS IS NOT AN IT ROOM WIRING METHODS PER NEC 645 NOT |
| PERMITTED. (OR WORDS TO THAT AFFECT). |
| |
| |
| |
| ** NOT ALL NOTES PROVIDED ON SHEETS SUBMITTED DENOTING |
| CHANGES MATCH WITH PLANS. |
| |
| |
| |
| ** IMPORTANT ** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| INTO TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |
| |