Plan Review Notes
Plan Review Notes For Permit 06110152
Permit Number 06110152
Review Stop M
Sequence Number 6
Notes
Date Text
2008-07-09 15:37:50REVIEW #: REVISIONS
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS FBC
 CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. M2.1.1: REFRIGERANT SENSORS HAVE BEEN MOVED OUT OF
 THE MACHINERY ROOM. REFRIGERANT DETECTORS IN MACHINERY
 ROOMS SHALL BE PROVIDED AS REQUIRED BY THE FLORIDA FIRE
 PREVENTION CODE IN ACCORDANCE WITH FBCM 1105.3.
  
 2. M2.3.2: CHANGES ON THIS PAGE ARE NOT IDENTIFIED.
 PLEASE IDENTIFY THE LOCATION AND NATURE OF ALL CHANGES
 RELATED TO THIS REVISION. FBC 106.1.2, FBCB 106.4.
  
 3. M5.1: SEE COMMENT #1 ABOVE.
  
 NOTE: SOME REVISED PAGES DID NOT HAVE ANY COMMENTS.
 HOWEVER, SINCE ALL THE CHANGES ARE RELATED, ALL PAGES
 AND CALCULATIONS ASSOCIATED WITH THIS REVISION WILL NOT
 BE INCORPORATED INTO THE PERMIT SET OF PLANS UNTIL THE
 ABOVE COMMENTS ARE ADDRESSED. PLEASE CORRECT AND
 RESUBMIT.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]