Plan Review Notes For Permit 06110152 |
Permit Number |
06110152 |
|
Review Stop |
M |
Sequence Number |
6 |
|
Notes |
Date |
Text |
2008-07-09 15:37:50 | REVIEW #: REVISIONS | | ACTION: DENIED | | | | FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS FBC | | CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | 1. M2.1.1: REFRIGERANT SENSORS HAVE BEEN MOVED OUT OF | | THE MACHINERY ROOM. REFRIGERANT DETECTORS IN MACHINERY | | ROOMS SHALL BE PROVIDED AS REQUIRED BY THE FLORIDA FIRE | | PREVENTION CODE IN ACCORDANCE WITH FBCM 1105.3. | | | | 2. M2.3.2: CHANGES ON THIS PAGE ARE NOT IDENTIFIED. | | PLEASE IDENTIFY THE LOCATION AND NATURE OF ALL CHANGES | | RELATED TO THIS REVISION. FBC 106.1.2, FBCB 106.4. | | | | 3. M5.1: SEE COMMENT #1 ABOVE. | | | | NOTE: SOME REVISED PAGES DID NOT HAVE ANY COMMENTS. | | HOWEVER, SINCE ALL THE CHANGES ARE RELATED, ALL PAGES | | AND CALCULATIONS ASSOCIATED WITH THIS REVISION WILL NOT | | BE INCORPORATED INTO THE PERMIT SET OF PLANS UNTIL THE | | ABOVE COMMENTS ARE ADDRESSED. PLEASE CORRECT AND | | RESUBMIT. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J. REGUEIRO | | 561.805.6719 | | [email protected] |
|