Plan Review Notes
Plan Review Notes For Permit 06110152
Permit Number 06110152
Review Stop P
Sequence Number 3
Notes
Date Text
2007-09-08 05:59:32DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 ****FROM PREVIOUS REVIEW:
 ******FROM PREVIOUS REVIEWS:
  
 1. OK
 2. OK
 3. OK
 4. OK
 5. OK
 6. OK
 7. OK
  
 8. SHT P3-1.1 RPZV BACKFLOWS ARE REQUIRED ON EACH WATER
 SUPPLY LINE INTO THE BUILDING. SECTION 608.13.2. SHOW
 ON THE PLANS.
 ****RESPONSE NOTED, BUT THE CIVIL SHEET WERE NOT
 SUBMITTED WITH THESE PLANS. PLEASE INDICATE ON THE
 PLANS LOCATION OF REQUIRED BACKFLOWS.
 ******RESPONSE NOTED, BUT THE RPZV BACKFLOWS ARE NOT
 INDICATED ON THE CIVIL PLANS AS REQUIRED FOR EACH
 BUILDING.
  
 9. SHT P5.1 VENT SHOWN UPSTREAM OF THE SANITARY STACK
 AND PRIOR TO THE FIRST WATER CLOSETS IS NOT SHOWN ON
 THE FLOOR PLAN. (TOILET ROOMS 221 & 223). PLEASE
 CORRELATE INFORMATION BETWEEN THE FLOOR PLAN AND THE
 RISER DIAGRAM. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. ROOMS
 221 & 223 ARE ONLY SHOWN ON SHT P2.2 AND NO CHANGE TO
 FLOOR PLAN SHOWN.
 ******RESPONSE NOTED, BUT THE VENT IS STILL NOT SHOWN
 ON THE FLOOR PLAN TO REFLECT THE RISER DIAGRAM.
  
 10. OK
 11. OK
  
 12. SHT P6.1 DOMESTIC WATER ISOMETRIC. SHOW THE
 REQUIRED RPZV BACKFLOWS ON THE WATER SERVICES, AND SHOW
 AN RPZV ON THE SUPPLY LINE FOR THE 2" MAKE UP WATER TO
 THE ROOF. SECTION 608.13.2.
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. - NOT
 SHOWN ON ISOMETRIC AS INDICATED.
 ******RESPONSE NOTED, BUT THE RPZV BACKFLOWS ARE NOT
 SHOWN ON THE WATER SERVICE TO EACH BUILDING.
  
 13. OK
 14. OK
 15. OK
 16. OK
  
 **********NEW COMMENTS**********
  
 1B. ALL SHEETS FOR PME SHALL BE SIGNED, SEALED & DATED
 ON THE DATE THE SEAL & SIGNATURE ARE AFFIXED TO SAID
 PLANS. SECTION 106.1.
 ******RESPONSE NOTED, BUT ONE ELECTRICAL SHEET DOES NOT
 HAVE A SIGNATURE ON ONE SET.
  
 2B. OK
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]