Plan Review Notes For Permit 06110152 |
Permit Number |
06110152 |
|
Review Stop |
M |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2007-08-13 10:58:24 | ***********PROVISO************** | | PROVIDE MIN. 290 CFM MECHANICAL EXHAUST FOR MACHINERY | | ROOM 103 WHEN NOT IN EMERGENCY CONDITIONS IN ACCORDANCE | | WITH FBC,M 1105.6. REVISE PGAES M2.1.1, M6.1 AND ANY | | OTHER EFFECTED PAGES, SHOWING COMPLIANCE, PRIOR TO | | ROUGH INSPECTION. | | | | RONALD J REGUEIRO | | 561.805.6719 | | [email protected] |
|