2007-09-14 18:58:24*****DENIED*****
 THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE
 PLAN REVIEW STILL NEED TO BE ADDRESSED:
 .
 09. ALL FIRE DOORS AND WINDOWS SHALL COMPLY WITH NFPA
 80.PANIC HARDWARE OR FIRE EXIT PANIC HARDWARE SHALL
 REQUIRED ON ALL EXIT DOORS THAT SERVE AND OCCUPANT LOAD
 OF 100 OR MORE PERSONS.ADD COMMENT TO AN APPROPIATE
 PLAN SHEET
  
  
 14.INTERIOR WALL AND CEILING FINISH CLASSIFICATION
 SHALL BE CLASS A OR CLASS B IN GENERAL ASSEMBLY AREAS
 HAVING AN OCCUPANT LOAD OF MORE THAN 300 AND SHALL BE
 CLASS A, CLASS B, OR CLASS C IN ASSEMBLY AREAS HAVING
 OCCUPANTS OF 300 OR FEWER.SPECIFY
  
 15.ELEVATORS TO COMPLY WITH ASME A17.1; WARNING SIGNS
 WILL BE REQUIRED IN ELEVATOR LOBBY.THE ELEVATORS (OR
 AT LEAST ONE ELEVATOR) SHOULD BE ACCESSIBLE FOR AN
 EMERGENCY MEDICAL STRETCHER OR GOURNEY.ADD COMMENT TO
 AN APPROPIATE PLAN SHEET
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE (ON THE PLANS) EACH COMMENT
 WAS ADDRESSED
  
  