2007-09-14 18:58:24 | *****DENIED***** | | THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE | | PLAN REVIEW STILL NEED TO BE ADDRESSED: | | . | | 09. ALL FIRE DOORS AND WINDOWS SHALL COMPLY WITH NFPA | | 80.PANIC HARDWARE OR FIRE EXIT PANIC HARDWARE SHALL | | REQUIRED ON ALL EXIT DOORS THAT SERVE AND OCCUPANT LOAD | | OF 100 OR MORE PERSONS.ADD COMMENT TO AN APPROPIATE | | PLAN SHEET | | | | | | 14.INTERIOR WALL AND CEILING FINISH CLASSIFICATION | | SHALL BE CLASS A OR CLASS B IN GENERAL ASSEMBLY AREAS | | HAVING AN OCCUPANT LOAD OF MORE THAN 300 AND SHALL BE | | CLASS A, CLASS B, OR CLASS C IN ASSEMBLY AREAS HAVING | | OCCUPANTS OF 300 OR FEWER.SPECIFY | | | | 15.ELEVATORS TO COMPLY WITH ASME A17.1; WARNING SIGNS | | WILL BE REQUIRED IN ELEVATOR LOBBY.THE ELEVATORS (OR | | AT LEAST ONE ELEVATOR) SHOULD BE ACCESSIBLE FOR AN | | EMERGENCY MEDICAL STRETCHER OR GOURNEY.ADD COMMENT TO | | AN APPROPIATE PLAN SHEET | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING HOW/WHERE (ON THE PLANS) EACH COMMENT | | WAS ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|