2007-09-04 14:42:58 | BUILDING PLAN REVIEW |
| PERMIT: 06110152 |
| ADD: 807 N. FLAGLER DR. |
| CONT: ANDERSON-MOORE |
| TEL: (561)662-1819 |
| |
| |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| * WEST PALM BEACH AMENDMENTS TO THE ADMINISTRATIVE |
| CODE |
| |
| 3RDREVIEW |
| ACTION: DENIED |
| |
| 1)--- VERY IMPORTANT STATEMENT --- |
| PLEASE DO NOT IGNORE! |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| YOUR ANTICIPATED COOPERATION. |
| |
| 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED |
| WITH THE CLERK OF THE COURT BEFORE A PERMIT WILL BE |
| ISSUED. NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE |
| NOTICE OFCOMMENCEMENT IS NOT ACTUALLY COMMENCED |
| WITHIN 90 DAYS AFTER THE RECORDING THEREOF, SUCH NOTICE |
| IS NULL & VOID. |
| |
| 3) BUILDING PROVISO: 109.3.10 IMPACT OF CONSTRUCTION. |
| |
| 4) BUILDING PROVISO: 109.3.10.1 HURRICANE PROTECTION. |
| |
| 5) COMPLIED, SPECIAL INSPECTOR AGREEMENT, THANK YOU. |
| |
| 6) COMPLIED, 3-SOILS REPORTS. |
| |
| 7)SECOND REQUEST,FLOOD ELEVATION CERTIFICATE WILL |
| BE REQUIRED BEFORE THE ISSUANCE OF THE CERTIFICATE OF |
| OCCUPANCY. THE ISSUE WITH THE FLOOD ELEVATION |
| CERTIFICATE IS IT WILL BE REQUIRED FOR THE "WHOLE |
| BUILDING" BEING THAT THE PROPOSED, THE ADDITION IS OVER |
| 50% WORTH OF THE EXISTING BUILDING "SUBSTANTIAL |
| IMPROVEMENTS" NEED TO BE MET UNDER W. P. B. CODE OF |
| ORDNANCES |
| CITY CODEARTICLE XVII FLOOD PREVENTION & CONTROL SEE |
| ATTACHED DOCUMENT FOR COMPLIANCE. NOTE UNDER SECTION |
| 94-546(B)(2) NONRESIDENTIAL CONSTRUCTION COMPLIANCE |
| THROUGH |
| FLOOD PROOFING.SEE THE EXISTING MARGARET TIGHE |
| MACHLIN THEATER FINISH FLOOR IS 5.13'N A VD 88. SEE |
| CIVIL PLAN C-1. |
| CITY CODE OF ORDNANCES |
| 94-546 (B)(2)NONRESIDENTIAL CONSTRUCTION.ALL NEW |
| CONSTRUCTION |
| OR SUBSTANTIAL IMPROVEMENT OF ANY COMMERCIAL, |
| INDUSTRIAL OR OTHER NONRESIDENTIAL STRUCTURE SHALL |
| EITHER HAVE THE LOWEST FLOOR, BASE FLOOD ELEVATION OR, |
| TOGETHER WITH ATTENDANT UTILITY AND SANITARY |
| FACILITIES, BE FLOOD PROOFED SO THAT BELOW SIX INCHES |
| ABOVE THE FLOOD BASE LEVEL THE STRUCTURE IS WATERTIGHT, |
| WITH WALLS SUBSTANTIALLY IMPERMEABLE TO THE PASSAGE OF |
| WATER AND WITH STRUCTURAL COMPONENTS HAVING THE |
| CAPABILITY OF RESISTING HYDROSTATIC AND HYDRODYNAMIC |
| LOADS AND EFFECTS OF BUOYANCY. A REGISTERED |
| PROFESSIONAL ENGINEER OR ARCHITECT SHALL CERTIFY THAT |
| THE STANDARDS OF THIS SUBSECTION ARE SATISFIED. SUCH |
| CERTIFICATION SHALL BE PROVIDED TO THE CITY ENGINEER. |
| |
| 8-12 COMPLIED. |
| |
| 13) COMPLIED, NOTED THE EXISTING DROP OFF ZONE FOR THE |
| ROSARIAN ACADEMY IS AT THE MARY ALICE FORTIN BUILDING. |
| |
| 14-28)COMPLIED. |
| |
| 29) 2ND REQUEST,1609.1.4 PROTECTION OF OPENINGS. IN |
| WIND-BORNE DEBRIS REGIONS, EXTERIOR |
| GLAZING THAT RECEIVES POSITIVE PRESSURE IN THE LOWER 60 |
| FEET (18.3 M) IN BUILDINGS SHALL BE ASSUMED TO BE |
| OPENINGS AND THE BALANCE OF GLAZED OPENINGS IN THE REST |
| OF THE BUILDING |
| SHALL BE ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT |
| RECEIVES POSITIVE PRESSURE IS IMPACT RESISTANT OR |
| PROTECTED WITH AN IMPACT RESISTANT COVERING MEETING THE |
| REQUIREMENTS OF SSTD 12, ASTM E 1886 AND ASTM E 1996, |
| OR MIAMI-DADE TAS 201, 202 AND 203 REFERENCED THEREIN |
| AS FOLLOWS: 1.GLAZED OPENINGS LOCATED WITHIN 30 FEET |
| (9.1 M) OF GRADE SHALL MEET THE REQUIREMENTS OF THE |
| LARGE MISSILE TEST. 2.GLAZED OPENINGS LOCATED MORE |
| THAN 30 FEET (9.1 M) ABOVE GRADE SHALL MEET THE |
| PROVISIONS OF THE SMALL MISSILE TEST. |
| |
| 30)2ND REQUEST, PRODUCT APPROVALS SUBMITTED WITH |
| PERMIT APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED |
| TO COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR |
| INFORMATION |
| PLEASE SEE THE STATE WEBSITE AT |
| WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE |
| APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER |
| SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE |
| STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL, |
| SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR |
| SITE SPECIFIC FORM PER RULE 9B-72. |
| |
| 31)2ND REQUEST,FL BLD CODE 1609.1.4: COMPONENTS & |
| CLADDING, PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT |
| INSPECTOR) OF PRODUCT |
| TESTING REPORTS,MISSING REPORTS ARE AS FOLLOWS:A) |
| EXTERIOR GLAZED SWING DOORS, SINGLE AND PAIRS ?OK |
| |
| B) EXTERIOR HOLLOW METAL FRAME DOORS, SINGLE AND PAIRS |
| FL 6224- OK |
| |
| C) ROOF HATCHES: THIS WILL BE A PROVISO, IF AT TIME OF |
| CERTIFICATE OF COMPLETION THE MANUFACTURER HAS NOT |
| RECEIVED EITHER STATE APPROVAL OR A MIAMI-DADE NOAA |
| LOCAL PRODUCT APPROVAL WILL NEED TO BE ACHIEVED BEFORE |
| C/O. |
| |
| D) FIXED WINDOWS-OK |
| |
| E) OPERABLE WINDOWS-OK |
| |
| F) SPANDREL GLASS-OK |
| |
| G) MULLIONS VERTICAL AND HORIZONTAL PART OF NOA. |
| |
| H) WALL LOUVERS- OK |
| |
| I) STRUCTURAL ANCHORS TRUSS ANCHORS-NO APPROVALS |
| SUBMITTED |
| |
| J) ROOFING ASSEMBLIES, ROOFING INSULATION, FLAT ROOFS |
| MODIFIED |
| ROOF TILE AND ASSEMBLIES. NOA 06-0606.06 ENTEGRA |
| TILE PLEASE HIGHLIGHT THE METHOD OF ATTACHMENT FOUND ON |
| PAGES 4 & 5. |
| |
| MODIFIED, THIS INFORMATION WILL BE NEEDED FOR A REVIEW |
| OF ROOFING PRODUCTS: |
| THIS FLAT ROOF (MODIFIED) IS MISSING OR NOT IN |
| COMPLIANCE WITH THE FOLLOW ITEMS: |
| |
| _XX__NOTE ROOF IS OVER 4 FEET FROM GRADE, THE ROOF |
| TABLE 1609.6.2.1(4) SEE HEIGHT |
| ADJUSTMENT FACTOR 1.12. |
| ___ CONTRACTOR DID NOT INDICATE THE ROOF PITCH. _XX__ |
| CONTRACTOR FAILED TO INDICATE WHICH SUB-SYSTEM TO BE |
| USED. |
| PAGES 9-26, PLEASE HIGHLIGHT WHICH SYSTEM WILL |
| BE INSTALLED. |
| _XX__ THE SYSTEM PROVIDED HAS A LOW PRESSURE FOR ZONE |
| 2& 3__ . |
| _XX__ THE SYSTEM PROVIDED STATESLIMITATION# 7, SHOULD |
| THE FASTENER RESISTANCE BE LESS THAN THATREQUIRED, AS |
| DETERMINED BY THE BUILDING OFFICIAL, A REVISED FASTENER |
| SPACING, PREPARED , SIGNED AND SEALED BY A FLORIDA |
| REGISTERED PROFESSIONAL ENGINEER, REGISTERED |
| ARCHITECT OR REGISTERED ROOFCONSULTANT MAY BE |
| SUBMITTED. |
| ___THE SYSTEM PROVIDED INDICATES LIMITATION# 9, NO |
| ENHANCED FASTENING ALLOWED. |
| |
| 32) 2ND REQUEST, W P B ADMINISTRATIVE CODE 106.3.3* |
| PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED |
| BY DCA RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN |
| WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| FOR JURISDICTIONAL APPROVAL. |
| |
| 33-35) COMPLIED. |
| |
| 36) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, |
| IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE |
| ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT |
| OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE |
| PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS |
| OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF |
| CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST |
| RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT |
| BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC |
| REQUIREMENT, THE SPECIFIC |
| REQUIREMENT SHALL BE APPLICABLE. |
| |
| BUILDING PLAN REVIEW |
| JIM WITMER C. B. O. |
| BUILDING PLAN REVIEW II |
| |
| |
| |
| |
| |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |
| E-MAIL: [email protected] |
| |
| |