2007-09-04 14:42:58BUILDING PLAN REVIEW
 PERMIT: 06110152
 ADD: 807 N. FLAGLER DR.
 CONT: ANDERSON-MOORE
 TEL: (561)662-1819
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS TO THE ADMINISTRATIVE
 CODE
  
 3RDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A PERMIT WILL BE
 ISSUED. NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE
 NOTICE OFCOMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING THEREOF, SUCH NOTICE
 IS NULL & VOID.
  
 3) BUILDING PROVISO: 109.3.10 IMPACT OF CONSTRUCTION.
  
 4) BUILDING PROVISO: 109.3.10.1 HURRICANE PROTECTION.
  
 5) COMPLIED, SPECIAL INSPECTOR AGREEMENT, THANK YOU.
  
 6) COMPLIED, 3-SOILS REPORTS.
  
 7)SECOND REQUEST,FLOOD ELEVATION CERTIFICATE WILL
 BE REQUIRED BEFORE THE ISSUANCE OF THE CERTIFICATE OF
 OCCUPANCY. THE ISSUE WITH THE FLOOD ELEVATION
 CERTIFICATE IS IT WILL BE REQUIRED FOR THE "WHOLE
 BUILDING" BEING THAT THE PROPOSED, THE ADDITION IS OVER
 50% WORTH OF THE EXISTING BUILDING "SUBSTANTIAL
 IMPROVEMENTS" NEED TO BE MET UNDER W. P. B. CODE OF
 ORDNANCES
 CITY CODEARTICLE XVII FLOOD PREVENTION & CONTROL SEE
 ATTACHED DOCUMENT FOR COMPLIANCE. NOTE UNDER SECTION
 94-546(B)(2) NONRESIDENTIAL CONSTRUCTION COMPLIANCE
 THROUGH
 FLOOD PROOFING.SEE THE EXISTING MARGARET TIGHE
 MACHLIN THEATER FINISH FLOOR IS 5.13'N A VD 88. SEE
 CIVIL PLAN C-1.
 CITY CODE OF ORDNANCES
 94-546 (B)(2)NONRESIDENTIAL CONSTRUCTION.ALL NEW
 CONSTRUCTION
 OR SUBSTANTIAL IMPROVEMENT OF ANY COMMERCIAL,
 INDUSTRIAL OR OTHER NONRESIDENTIAL STRUCTURE SHALL
 EITHER HAVE THE LOWEST FLOOR, BASE FLOOD ELEVATION OR,
 TOGETHER WITH ATTENDANT UTILITY AND SANITARY
 FACILITIES, BE FLOOD PROOFED SO THAT BELOW SIX INCHES
 ABOVE THE FLOOD BASE LEVEL THE STRUCTURE IS WATERTIGHT,
 WITH WALLS SUBSTANTIALLY IMPERMEABLE TO THE PASSAGE OF
 WATER AND WITH STRUCTURAL COMPONENTS HAVING THE
 CAPABILITY OF RESISTING HYDROSTATIC AND HYDRODYNAMIC
 LOADS AND EFFECTS OF BUOYANCY. A REGISTERED
 PROFESSIONAL ENGINEER OR ARCHITECT SHALL CERTIFY THAT
 THE STANDARDS OF THIS SUBSECTION ARE SATISFIED. SUCH
 CERTIFICATION SHALL BE PROVIDED TO THE CITY ENGINEER.
  
 8-12 COMPLIED.
  
 13) COMPLIED, NOTED THE EXISTING DROP OFF ZONE FOR THE
 ROSARIAN ACADEMY IS AT THE MARY ALICE FORTIN BUILDING.
  
 14-28)COMPLIED.
  
 29) 2ND REQUEST,1609.1.4 PROTECTION OF OPENINGS. IN
 WIND-BORNE DEBRIS REGIONS, EXTERIOR
 GLAZING THAT RECEIVES POSITIVE PRESSURE IN THE LOWER 60
 FEET (18.3 M) IN BUILDINGS SHALL BE ASSUMED TO BE
 OPENINGS AND THE BALANCE OF GLAZED OPENINGS IN THE REST
 OF THE BUILDING
 SHALL BE ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT
 RECEIVES POSITIVE PRESSURE IS IMPACT RESISTANT OR
 PROTECTED WITH AN IMPACT RESISTANT COVERING MEETING THE
 REQUIREMENTS OF SSTD 12, ASTM E 1886 AND ASTM E 1996,
 OR MIAMI-DADE TAS 201, 202 AND 203 REFERENCED THEREIN
 AS FOLLOWS: 1.GLAZED OPENINGS LOCATED WITHIN 30 FEET
 (9.1 M) OF GRADE SHALL MEET THE REQUIREMENTS OF THE
 LARGE MISSILE TEST. 2.GLAZED OPENINGS LOCATED MORE
 THAN 30 FEET (9.1 M) ABOVE GRADE SHALL MEET THE
 PROVISIONS OF THE SMALL MISSILE TEST.
  
 30)2ND REQUEST, PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED
 TO COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL,
 SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR
 SITE SPECIFIC FORM PER RULE 9B-72.
  
 31)2ND REQUEST,FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT
 INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS FOLLOWS:A)
 EXTERIOR GLAZED SWING DOORS, SINGLE AND PAIRS ?OK
  
 B) EXTERIOR HOLLOW METAL FRAME DOORS, SINGLE AND PAIRS
 FL 6224- OK
  
 C) ROOF HATCHES: THIS WILL BE A PROVISO, IF AT TIME OF
 CERTIFICATE OF COMPLETION THE MANUFACTURER HAS NOT
 RECEIVED EITHER STATE APPROVAL OR A MIAMI-DADE NOAA
 LOCAL PRODUCT APPROVAL WILL NEED TO BE ACHIEVED BEFORE
 C/O.
  
 D) FIXED WINDOWS-OK
  
 E) OPERABLE WINDOWS-OK
  
 F) SPANDREL GLASS-OK
  
 G) MULLIONS VERTICAL AND HORIZONTAL PART OF NOA.
  
 H) WALL LOUVERS- OK
  
 I) STRUCTURAL ANCHORS TRUSS ANCHORS-NO APPROVALS
 SUBMITTED
  
 J) ROOFING ASSEMBLIES, ROOFING INSULATION, FLAT ROOFS
 MODIFIED
 ROOF TILE AND ASSEMBLIES. NOA 06-0606.06 ENTEGRA
 TILE PLEASE HIGHLIGHT THE METHOD OF ATTACHMENT FOUND ON
 PAGES 4 & 5.
  
 MODIFIED, THIS INFORMATION WILL BE NEEDED FOR A REVIEW
 OF ROOFING PRODUCTS:
 THIS FLAT ROOF (MODIFIED) IS MISSING OR NOT IN
 COMPLIANCE WITH THE FOLLOW ITEMS:
  
 _XX__NOTE ROOF IS OVER 4 FEET FROM GRADE, THE ROOF
 TABLE 1609.6.2.1(4) SEE HEIGHT
 ADJUSTMENT FACTOR 1.12.
 ___ CONTRACTOR DID NOT INDICATE THE ROOF PITCH. _XX__
 CONTRACTOR FAILED TO INDICATE WHICH SUB-SYSTEM TO BE
 USED.
 PAGES 9-26, PLEASE HIGHLIGHT WHICH SYSTEM WILL
 BE INSTALLED.
 _XX__ THE SYSTEM PROVIDED HAS A LOW PRESSURE FOR ZONE
 2& 3__ .
 _XX__ THE SYSTEM PROVIDED STATESLIMITATION# 7, SHOULD
 THE FASTENER RESISTANCE BE LESS THAN THATREQUIRED, AS
 DETERMINED BY THE BUILDING OFFICIAL, A REVISED FASTENER
 SPACING, PREPARED , SIGNED AND SEALED BY A FLORIDA
 REGISTERED PROFESSIONAL ENGINEER, REGISTERED
 ARCHITECT OR REGISTERED ROOFCONSULTANT MAY BE
 SUBMITTED.
 ___THE SYSTEM PROVIDED INDICATES LIMITATION# 9, NO
 ENHANCED FASTENING ALLOWED.
  
 32) 2ND REQUEST, W P B ADMINISTRATIVE CODE 106.3.3*
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED
 BY DCA RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 33-35) COMPLIED.
  
 36) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED,
 IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE
 ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
 BUILDING PLAN REVIEW