Plan Review Notes
Plan Review Notes For Permit 06110152
Permit Number 06110152
Review Stop P
Sequence Number 2
Notes
Date Text
2007-06-13 14:53:14DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. SHT A0.0.1 INDICATES ASSEMBLY OCCUPANCY FOR THE 1ST
 & 2ND FLOORS. PER SECTION 403.1.1, POTTY PARITY,
 RESTROOMS WHICH ARE OPEN TO THE PUBLIC, MUST HAVE A
 RATIO OF 3:2 WATER CLOSETS PROVIDED FOR WOMEN AS THE
 COMBINED TOTAL OF WATER CLOSETS & URINALS PROVIDED FOR
 MEN. POTTY PARITY DOES NOT SEEM TO BE COMPLIED WITH.
 PLEASE SHOW COMPLIANCE WITH SECTION 403.1.1.
 ****RESPONSE NOTED, BUT ACCORDING TO TABLE 403.1, FIRST
 FLOOR ASSEMBLY OF 271 FOR WOMEN @ 1/65 COMES OUT TO
 4.169 AND ALL FRACTIONS SHALL BE ROUNDED UP. SO THE
 TOTAL WOMENS W/C'S REQUIRED IS 18, NOT 17 AS SHOWN.
  
 2. SHT A2.4.1 SUBMIT CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS PER SECTIONS 1106 & 1107 WITH ALL
 SUBSECTIONS & TABLES. SHOW THE SQUARE FOOTAGE OF EACH
 AREA TO BE DRAINED, AND 1/2 AREA OF ALL VERTICAL WALLS
 INCLUDING PARAPETS AS WELL AS ANY ROOF AREA FROM ABOVE
 THAT DRAINS ON TO THE LOWER ROOFS IN THE CALCULATIONS.
 SECTIONS 106.3.5.1.3(7)(13) & TABLES 1106.2, 1106.3 &
 1106.6. INDICATE THE SIZE OF THE GUTTERS AND SHOW SLOPE
 WITH THE HIGH POINTS OF THE GUTTER INDICATED.
 ****RESPONSE NOTED, BUT NO CALCULATIONS WERE FOUND. THE
 1/2 AREA OF ALL VERTICAL WALLS WAS NOT INDICATED AND NO
 SQUARE FOOTAGE IS INDICATED FOR THE ROOF DRAINS SHOWN
 ON SHT P2.3.1 & ASSOCIATED DRAINS ON THE STORM RISER
 DIAGRAM SHT P5.2. UPON FURTHER REVIEW, NO CALCULATIONS
 WERE FOUND FOR THE EXISTING ROOF DRAINS THAT HAVE THE
 ADDED VERTICAL CONTRIBUTION FROM THE NEW ADDIITION
 PLEASE INDICATE TOTAL SQUARE FOOTAGE BEING DRAINED BY
 THE DRAINS ADJACENT TO THE NEW ADDITION. SHOW EXISTING
 SF AND 1/2 AREA OF NEW VERTICAL WALL ADDED TO SF.
 INDICATE THE SIZE OF THE EXISTING ROOF DRAINS AND THE
 SIZE OF THE EXISTING ROOF LEADERS.
  
 3. SHTS A4.1.1 & A4.1.2 SHOW THE CLEAR FLOOR SPACE FOR
 THE URINAL, ACCESSIBLE SHOWERS AND DRINKING FOUNTAINS
 PER SECTIONS 11-4.18..3, 11-4.21.2, & 11-4.15.5. ****NO
 RESPONSE, NOT ADDRESSED.
  
 4. SHT A7.1.1 FINISH SCHEDULE. BOY'S RESTROOM 107 &
 GIRL'S RESTROOM 109 INDICATE PAINTED GWB FOR THE WALL
 FINISH. SECTION 1210.2 REQUIRES A "SMOOTH, HARD,
 NONABSORBENT" SURFACE. PAINTED GWB IS NOT CONSIDERED A
 "HARD" SURFACE. PLEASE INDICATE HOW THIS REQUIREMENT
 WILL BE COMPLIED WITH. ALSO SEE BOY'S RESTROOM 302 AND
 GIRL'S RESTROOM 304. NO FINISH IS INDICATED. PLEASE
 INDICATE WALL FINISH TO COMPLY WITH SECTION 1210.2.
 ****NO RESPONSE, NOT ADDRESSED.
  
 5. SHT A8.1.3 SHOW THE FOLLOWING REQUIREMENTS:
 A. 11-4.16.6 DISPENSERS (FIG 29(B)
 B. 11-4.18.4 FLUSH CONTROLS
 C. 11-4.19.5 FAUCETS
 D. 11-4.21.2 SIZE & CLEARANCES
 E. 11-4.21.3 SEAT
 F. 11-4.21.4 GRAB BARS (FIG 11-37)
 G. 11-4.21.5 CONTROLS
 H. 11-4.21.6 SHOWER UNIT
 ****NO RESPONSE, NOT ADDRESSED.
  
 6. SUBMIT A DETAIL FOR THE ACCESSIBLE DRINKING
 FOUNTAINS. SHOW COMPLIANCE WITH SECTION 11-4.15 AND ALL
 SUBSECTIONS INCLUDING ALSO SECTION 11-4.1.3(10)(A)
 PROVISIONS FOR THOSE WHO HAVE DIFFICULTY BENDING AND
 STOOPING.
 ****NO RESPONSE, NOT ADDRESSED.
  
 7. SHT P0.1 WATER HEATER DETAIL. SUBMIT CALCULATION FOR
 THE EXPANSION TANK FOR THE 1230 GAL W/H. SUBMIT THE
 MANUF. SPECIFICATION SHEETS AND INDICATE THE MODEL
 NUMBER SHOWING TANK SIZE. SECTION 607.3.2. ****RESPONSE
 NOTED, BUT THE CALCULATIONS WERE NOT SUBMITTED. (SEE
 EXAMPLES OF TWO DIFFERENT MANUF. CALCULATIONS FOR
 EXPANSION TANKS).
  
 8. SHT P3-1.1 RPZV BACKFLOWS ARE REQUIRED ON EACH WATER
 SUPPLY LINE INTO THE BUILDING. SECTION 608.13.2. SHOW
 ON THE PLANS.
 ****RESPONSE NOTED, BUT THE CIVIL SHEET WERE NOT
 SUBMITTED WITH THESE PLANS. PLEASE INDICATE ON THE
 PLANS LOCATION OF REQUIRED BACKFLOWS.
  
 9. SHT P5.1 VENT SHOWN UPSTREAM OF THE SANITARY STACK
 AND PRIOR TO THE FIRST WATER CLOSETS IS NOT SHOWN ON
 THE FLOOR PLAN. (TOILET ROOMS 221 & 223). PLEASE
 CORRELATE INFORMATION BETWEEN THE FLOOR PLAN AND THE
 RISER DIAGRAM. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. ROOMS
 221 & 223 ARE ONLY SHOWN ON SHT P2.2 AND NO CHANGE TO
 FLOOR PLAN SHOWN.
  
 10. SHT P5.1 SANITARY RISER DIAGRAM. SHOW THE DFU'S AS
 THEY ACCUMULATE IN THE SYSTEM TO VERIFY THE PIPE SIZES.
 SECTION 106.1.1 AND TABLES 709.1, 710.1(1) & 710.1(2).
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED.
  
 11. OK
  
 12. SHT P6.1 DOMESTIC WATER ISOMETRIC. SHOW THE
 REQUIRED RPZV BACKFLOWS ON THE WATER SERVICES, AND SHOW
 AN RPZV ON THE SUPPLY LINE FOR THE 2" MAKE UP WATER TO
 THE ROOF. SECTION 608.13.2.
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. - NOT
 SHOWN ON ISOMETRIC AS INDICATED.
  
 13. SHT P6.1 WATER HAMMER ARRESTORS SHALL BE LOCATED
 NEAR THE FIXTURES IN AN "EFFECTIVE RANGE" NOT IN THE
 CEILING AS SHOWN. PDI-WH 201 AND MANUF. INSTALLATION
 INSTRUCTIONS.
 ****RESPONSE NOTED, COMMENT NOT ADDRESSED.
  
 14. SHT P6.1 SHUT OFF VALVES ARE REQUIRED ON BOTH SIDES
 OF THE CIRCULATION PUMP FOR THE WATER HEATERS. ALSO
 SHOW THE VALVES ON THE WATER HEATER DETAIL SHT P0.1.
 SECTION 606.2(3).
 ****RESPONSE NOTED, COMMENT NOT ADDRESSED FOR SHUT OFF
 VALVES FOR THE CIRCULATION PUMP.
  
 15. SUBMIT A STORM RISER ISOMETRIC RISER DIAGRAM. SHOW
 ALL PIPE SIZES, OFFSETS, AND SQUARE FOOTAGE AS IT
 ACCUMULATES IN THE SYSTEM. SECTION 106.3.5.1.3.
 ****RESPONSE NOTED, BUT THE SQUARE FOOTAGE AS IT
 ACCUMULATES IN THE SYSTEM IS NOT SHOWN ON THE RISER.
 THE RISER DIAGRAM DOES NOT REFLECT THE FLOOR PLAN FOR
 THE 6" @3535SF.
  
 16. OK
  
 **********NEW COMMENTS**********
  
 1B. ALL SHEETS FOR PME SHALL BE SIGNED, SEALED & DATED
 ON THE DATE THE SEAL & SIGNATURE ARE AFFIXED TO SAID
 PLANS. SECTION 106.1.
  
 2B. SEE THE ATTACHED SHEET CONCERNING FS 553.80(2)(B)
 AND THE DESIGN PROFESSIONAL. THIS IS GIVEN AS A NOTICE
 AT THIS TIME.
  
 REVIEW BY KEN STEVENS