2007-04-30 16:39:36 | ---------------DENIED------------------ |
| |
| THE FIRST SET OF COMMENTS ARE NUMBERED TO CORRESPOND |
| WITH PREVIOUS REVIEW COMMENTS FOR CONTINUITY: |
| |
| 1.OK |
| |
| 2. MACHINERY ROOM EXHAUST TERMINATES 11'6" FROM |
| PROPERTY LINE AND IS ADJASCENT TO AN OPENING INTO THE |
| PARKING GARAGE. THE REQUIREMENTS OF FBC,M 1105.6.1 HAVE |
| NOT BEEN MET. |
| |
| 3. OK |
| |
| 4. WHAT PROVISIONS AHVE BEEN MADE FOR REQUIRED MINIMUM |
| VENTILATION UNDER NON-EMERGENCY CONDITIONS PER FBC,M |
| 1105.6 AND IN QUANTITIES DETERMINED BY FBC,M 1105.6.3? |
| NOTES INDICATE FAN IS ONLY ENERGIZED AND MAKE-UP AIR |
| DAMPERS ARE ONLY OPEN UNDER EMERGENCY CONDITIONS. |
| |
| 5. OK |
| |
| NEW COMMENTS: |
| |
| A. M2.3.1 AND M2.3.2: BALCONY (ROOM 316) COULD NOT BE |
| FOUND ON ARCHITECTURAL FLOOR PLANS. ALSO, SEVERAL FIRE |
| DAMPERS ARE SHOWN IN WALLS WHICH ARE NOT SHOWN TO BE |
| RATED ON ARCHITECTURAL PLANS OR LIFE SAFETY PLANS. |
| PLEASE COORDINATE DRAWINGS SHOWING LOCATION OF RATED |
| BARRIERS/PARTITIONS (IF NEEDED) WHICH CORRESPONDS WITH |
| DUCT PENETRATION OPEN ING PROTECTIVES (IF NEEDED). |
| |
| B. M2.1.1: A TWO-HOUR RATED WALL IS SHOWN BETWEEN ROOM |
| 100 AND 101/101A ON PAGE LS2.1.0. THERE ARE THREE |
| MECHANICAL PENETRATIONS IN THIS WALL FROM AHU 1-2 |
| REQUIRING OPENING PROTECTIVES PER FBC,M 607.5. ALSO, |
| PLEASE SHOW SIZE AND TYPE OF DIFFUSERS (IF ANY) TO BE |
| USED AT THESE WALL TERMINATIONS. |
| |
| C. AHU 1-1: WHAT IS THE SIZE OF RETURN OPENING IN |
| MACHINERY ROOM 103? ALSO, AIR FROM AHU 1-1 SHALL NOT BE |
| RECIRCULATED PER FBC,M 403.2.1 AND FBC,M 1105.6.2. |
| |
| D. M2.1.2: AHU 1-3 CALLS FOR 6000 CFM ON SCHEDULE BUT |
| SHOWS 6275 ON FLOOR PLAN. WHICH IS CORRECT? |
| |
| E. M2.1.2 ROOM 113: GRILL DESIGNATION SAYS "TYPICAL OF |
| 7" BUT PLAN SHOWS 8 GRILLS IN ROOM. PLEASE CLARIFY. |
| |
| F. M2.2.1 BOYS/GIRLS LOCKER ROOMS: BOTH AREAS SHOW |
| RETURN AIR FROM LOCKER ROOMS. RECIRCULATION OF AIR FROM |
| LOCKER ROOMS/RESTROOMS IS PROHIBITED PER FBC,M TABLE |
| 403.3 NOTE (B). |
| |
| G. M2.2.1: PLAN SHOWS A FIRE DAMPER ON TWO 1 1/4" WATER |
| LINES AT VESTIBULE 201. PLEASE CLARIFY. |
| |
| H. AHU 2-4: PLAN SHOWS 800 CFM SUPPLY WITH 500 CFM R/A |
| AND 80 CFM O.A.HOW IS THIS SYSTEM TO BE BALANCED? |
| |
| I. M2.2.2: R/A FROM ROOMS 229/230 DO NOT MEET THE |
| EXCEPTIONS FOR BALANCED RETURN UNDER FBC,M 601.4. |
| UNLESS THE TRANSFER DUCT IS DESIGNED TO 1 1/2 TIMES THE |
| SQUARE INCHES OF SUPPLY, A FIELD TEST IS REQUIRED TO |
| SHOW THE PRESSURE DIFFERENTIAL TO BE 0.01" WC OR LESS |
| PER FBC,M 601.4. THIS APPLIES TO ANY AREAS UTILIZING |
| TRANSFER DUCTS/GRILLS FOR BALANCED RETURN. |
| |
| J. M2.2.2 AHU 2-9: PLEASE SHOW SIZES OF BRANCH DUCTS AT |
| TEE ON SUPPLY DUCT SYSTEM. FBC 106.1.1 |
| |
| K. AHU SYSTEMS: MOST SYSTEMS APPEAR TO BE DESIGNED WITH |
| EQUAL AMOUNTS OF SUPPLY AND RETURN AIR. EXAMPLE: AHU |
| 2-6 SHOWS 1600 CFM SUPPLY, 1600 CFM RETURN AMD 330 CFM |
| O.A. HOW WILL O/A BE INTRODUCED OF 100% OF SUPPLY IS |
| BEING RETURNED? PLEASE CHECK ALL A/C SYSTEMS FOR PROPER |
| BALANCE IN ACCORDANCE WITH FBC,M 403.1. |
| |
| L. ALL EXIT ENCLOSURES: EQUIPMENT AND DUCTWORK FOR EXIT |
| ENCLOSURE VENTILATION SHALL COMPLY WITH THE |
| REQUIREMENTS FBC,M 401.4. SOME ASPECTS OF THE A/C |
| SYSTEMS MAY NEED TO BE MODIFIED TO MEET THIS |
| REQUIREMENT. A REVIEW OF CHANGES WITH POSSIBLE NEW |
| COMMENTS WILL BE DONE AT TIME OF RESUBMITTAL. |
| |