2007-05-21 14:38:18*****DENIED*****
 THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE
 PLAN REVIEW STILL NEED TO BE ADDRESSED:
  
  
 01.THE ADDRESS OF WHERE THE SCOPE OF WORK WILL BE
 CONDUCTED SHALL BE IN THE TITLE BLOCK OF EACH SUBMITTED
 PLAN SHEET.
 02.NFPA 101- 2003 EDITION AND THE FLORIDA FIRE
 PREVENTION CODE - 2004 EDITION SHALL BE REFERENCED. 03.
 STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. 04.
 CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT
 HINDER OR INTERFERE WITH EMERGENCY RESPONSE ACCESS TO
 THE SAID PROPERTY OR THE VICINITY THEREOF (INCLUDING
 FIRE LANES).
 07. KNOX BOX FOR THE BUILDING WILL BE REQUIRED. CONTACT
 THE FIRE PREVENTION BUREAU AT (561) 804-4724 FOR
 APPLICATIONS.
 09. ALL FIRE DOORS AND WINDOWS SHALL COMPLY WITH NFPA
 80.PANIC HARDWARE OR FIRE EXIT PANIC HARDWARE SHALL
 REQUIRED ON ALL EXIT DOORS THAT SERVE AND OCCUPANT LOAD
 OF 100 OR MORE PERSONS.
 10. DELAYED-EGRESS LOCKS OR ACCESS-CONTROLLED EGRESS
 DOORS SHALL COMPLY NFPA 101, CH. 7.2.1.6
 11.EXIT/EGRESS FROM THE BUILDING AND/OR FLOOR SHALL
 COMPLY WITH APPLICABLE FIRE AND BUILDING CODES (SEE
 BUILDING PLAN REVIEW COMMENTS).
 12.NO EQUIPMENT SHALL BE ALLOWED INSIDE OR PENETRATE
 EXIT ENCLOSURES UNLESS THE EXCEPTIONS OF NFPA 101,
 7.1.3.2.1. (6) ARE MET.
 14.INTERIOR WALL AND CEILING FINISH CLASSIFICATION
 SHALL BE CLASS A OR CLASS B IN GENERAL ASSEMBLY AREAS
 HAVING AN OCCUPANT LOAD OF MORE THAN 300 AND SHALL BE
 CLASS A, CLASS B, OR CLASS C IN ASSEMBLY AREAS HAVING
 OCCUPANTS OF 300 OR FEWER.
 15.ELEVATORS TO COMPLY WITH ASME A17.1; WARNING SIGNS
 WILL BE REQUIRED IN ELEVATOR LOBBY.THE ELEVATORS (OR
 AT LEAST ONE ELEVATOR) SHOULD BE ACCESSIBLE FOR AN
 EMERGENCY MEDICAL STRETCHER OR GOURNEY.
 17.IF SO EQUIPPED WITH A COOKING HOOD, SEPARATE PLANS
 AND PERMIT WILL BE REQUIRED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE (ON THE PLANS) EACH COMMENT
 WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722