Date |
Text |
2007-05-21 14:38:18 | *****DENIED***** |
| THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE |
| PLAN REVIEW STILL NEED TO BE ADDRESSED: |
| |
| |
| 01.THE ADDRESS OF WHERE THE SCOPE OF WORK WILL BE |
| CONDUCTED SHALL BE IN THE TITLE BLOCK OF EACH SUBMITTED |
| PLAN SHEET. |
| 02.NFPA 101- 2003 EDITION AND THE FLORIDA FIRE |
| PREVENTION CODE - 2004 EDITION SHALL BE REFERENCED. 03. |
| STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. 04. |
| CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT |
| HINDER OR INTERFERE WITH EMERGENCY RESPONSE ACCESS TO |
| THE SAID PROPERTY OR THE VICINITY THEREOF (INCLUDING |
| FIRE LANES). |
| 07. KNOX BOX FOR THE BUILDING WILL BE REQUIRED. CONTACT |
| THE FIRE PREVENTION BUREAU AT (561) 804-4724 FOR |
| APPLICATIONS. |
| 09. ALL FIRE DOORS AND WINDOWS SHALL COMPLY WITH NFPA |
| 80.PANIC HARDWARE OR FIRE EXIT PANIC HARDWARE SHALL |
| REQUIRED ON ALL EXIT DOORS THAT SERVE AND OCCUPANT LOAD |
| OF 100 OR MORE PERSONS. |
| 10. DELAYED-EGRESS LOCKS OR ACCESS-CONTROLLED EGRESS |
| DOORS SHALL COMPLY NFPA 101, CH. 7.2.1.6 |
| 11.EXIT/EGRESS FROM THE BUILDING AND/OR FLOOR SHALL |
| COMPLY WITH APPLICABLE FIRE AND BUILDING CODES (SEE |
| BUILDING PLAN REVIEW COMMENTS). |
| 12.NO EQUIPMENT SHALL BE ALLOWED INSIDE OR PENETRATE |
| EXIT ENCLOSURES UNLESS THE EXCEPTIONS OF NFPA 101, |
| 7.1.3.2.1. (6) ARE MET. |
| 14.INTERIOR WALL AND CEILING FINISH CLASSIFICATION |
| SHALL BE CLASS A OR CLASS B IN GENERAL ASSEMBLY AREAS |
| HAVING AN OCCUPANT LOAD OF MORE THAN 300 AND SHALL BE |
| CLASS A, CLASS B, OR CLASS C IN ASSEMBLY AREAS HAVING |
| OCCUPANTS OF 300 OR FEWER. |
| 15.ELEVATORS TO COMPLY WITH ASME A17.1; WARNING SIGNS |
| WILL BE REQUIRED IN ELEVATOR LOBBY.THE ELEVATORS (OR |
| AT LEAST ONE ELEVATOR) SHOULD BE ACCESSIBLE FOR AN |
| EMERGENCY MEDICAL STRETCHER OR GOURNEY. |
| 17.IF SO EQUIPPED WITH A COOKING HOOD, SEPARATE PLANS |
| AND PERMIT WILL BE REQUIRED. |
| |
| |
| TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| LETTER INDICATING HOW/WHERE (ON THE PLANS) EACH COMMENT |
| WAS ADDRESSED |
| |
| |
| CAPT. MICHAEL A. WILLIAMS |
| FIRE PLAN REVIEW |
| 561-805-6722 |