Plan Review Notes
Plan Review Notes For Permit 06110152
Permit Number 06110152
Review Stop E
Sequence Number 2
Notes
Date Text
2007-04-21 12:53:122007-04-21 12:53:12
  
 ** UNSAT 2ND REVIEW**
  
 ** PLEASE SEE ANY REFERENCES TO THE FBC CHAPTER 1 ARE
 THE ADMINISTRATIVE SECTION AS ADOPTED BY THE CITY OF
 WEST PALM BEACH.
  
 ** PLEASE SEE THERE ARE MANY ITEMS FROM THE PREVIOUS
 REVIEW WHICH ARE STILL IN NEED OF ADDRESSING ALONG WITH
 SOME NEW COMMENTS AS WELL AS COMMENT WHICH COULD NOT BE
 MADE YET AS THE PLANS SUBMITTED CONTAIN SOME MISSING
 SHEETS ETC. PLEASE SEE NOTES BELOW WHICH WILL FURTHER
 EXPLAIN.
 ** SOME OF THE COMMENTS BELOW ARE NOT RELEVANT TO KAMM
 CONSULTING.
  
 ** PLEASE SEE THAT ONE SET CONTAINS SOME REDLINES FOR
 AREAS FOR SOME OF THE NOTES.
  
 1) NOTE: PLEASE BE SURE ALL PLANS REFLECT THE FOLLOWING
 CODES AT A MINIMUM.
 2002 NFPA-70, 2003 NFPA-101, 2002 NFPA-72
 THIS IS REQUIRED ON THE ARCHITECTURAL SHEETS AS WELL.
 THE ELECTRICAL SHEETS WERE CORRECTED WITH THE UPDATED
 CODE INFORMATION..
  
 2) NOTE: PLEASE SEE THAT COMPLIANCE WITH THE FBC
 CHAPTER 13 HAS NOT YET BEEN MET. PLEASE SEE THE
 RESPONSE LETTER ONLY RESPONDED TO THE FIRST SENTENCE OF
 THE PREVIOUS NOTES AND THE REST OF THE NOTE #2 FROM
 PREVIOUS REVIEW WAS LEFT.
  
 A) PLEASE SEE THAT THE PREVIOUS REVIEW NOTE WILL BE
 LEFT AS IS AND NEW EXPLANATORY NOTES ARE LISTED AS
 FOLLOWS.
  
 B) PLEASE SEE SOME OF THE CIRCUITING SHOWN ON PLANS
 WHICH INDICATE CONTROLS THROUGH THE LCPS ARE NOT LISTED
 ON THE LCPS OR DO NOT CORRELATE. PLEASE SEE THAT
 CIRCUIT/CONTROL DESIGNATIONS ARE SHOWN AS AB ON ONE AND
 BA ON ANOTHER.
  
 C) PLEASE SEE THERE ARE STILL DEVICES AND SYMBOLS ON
 PLANS WHICH ARE NOT LISTED ON THE SYMBOL LEGEND FOR
 OVER RIDE DEVICES ON THE SYMBOL LEGEND FOR ELECTRICAL
 DEVICES.
  
 D) PLEASE SEE THAT THE LEGEND FOR OVER RIDE DEVICES DO
 NOT INDICATE ANY MAXIMUM TIME FOR PERMITTED OVER RIDES
 AS REQUIRED.
  
 E) PLEASE SEE THAT MANY AREAS LIKE HALLWAYS, BATHROOMS
 AND OTHER AREAS ETC CONTAIN AN *SO* AND *SW* TYPE
 DEVICES WHICH WILL NOT PROVIDE COVERAGE FOR LIGHTING
 CONTROL FOR LIFE SAFETY OR NORMAL OVER RIDE CONTROL.
 PLEASE SEE SOME HALLS WHICH CONTAIN THIS DEVICE AT ONE
 END OF THE HALL OR ON ONE SIDE WITH WALLS ETC BLOCKING
 ANY DETECTION FROM OTHER AREAS FOR OVER RIDE. PLEASE
 SEE *SK* DEVICE WHICH IS NOT LISTED FOR CONTROL OR WHAT
 TYPE OF OPERATION.
  
 F) PLEASE SEE ROOMS AND AREAS WHICH DO CONTAIN FLOOR TO
 CEILING HEIGHT PARTITIONS OR WALLS WHICH THESE ROOMS
 ARE SEPARATE AND NO OVER RIDE DEVICES ARE SHOWN ON
 PLANS.
  
 G) PLEASE THE COMPLETE REVIEW FOR LIGHTING AS SHOWN ON
 PLANS AND LIGHTING ON FIXTURE LEGEND AND LIGHTING ON
 ENERGY CALCULATIONS CAN NOT BE REVIEWED AS THE ENERGY
 CALCULATIONS DO NOT CORRELATE WITH PLANS FOR LIGHTING
 OR WITH FIXTURE LEGEND FOR TYPES OF FIXTURES, NUMBER OF
 FIXTURES, AND WATTAGE ON FIXTURES.
  
 H) PLEASE SEE THE TYPE OF CONTROLS FOR LIGHTING DOES
 NOT CORRELATE. THE ENERGY CALCULATIONS STILL INDICATE
 *MANUAL ON/OFF8 FOR CONTROL?
  
 I) PLEASE SEE SOME CIRCUITS WHICH ARE NOTED AS BEING
 CONTROLLED THROUGH A LIGHTING DIMMING PANEL WHICH IS
 NOT INDICATED IN ANY LIGHTING CONTROL PANEL OR ON
 LIGHTING CONTROL DEVICES.
 PLEASE PROVIDE MORE DETAILS ON HOW THIS OPERATION WILL
 TAKE PLACE. NEED TO PROVIDE MORE INFORMATION FOR
 REVIEW. FBC 106.1.2
  
 ** PLEASE KNOW AS THERE ARE MANY ITEMS WHICH ARE NOT
 YET CLEAR OR SHOWN, COMPLETE REVIEW FOR SOME ITEMS CAN
 NOT BE DONE.
  
 * PREVIOUS REVIEW NOTE FROM REVIEW #1*
 PLEASE SEE FBC CHAPTER 13. PLEASE SEE
 13-415.1.ABC.1.1, .1.2 AND .1.3.
 PLEASE SEE THERE ARE MANY AREAS WHICH INDICATE SOME
 SORT OF SYMBOL NEXT TO SWITCH, HOWEVER AS THIS SYMBOL
 IS NOT LOCATED ON THE SYMBOL SCHEDULE IT IS UNCLEAR
 WHAT THIS IS FOR REVIEW OF COMPLIANCE WITH ANY LIGHTING
 CONTROL REQUIREMENTS.
 PLEASE SEE MANY OTHER AREAS WHICH A SWITCH IS BEING
 SHOWN AND THE CIRCUIT IS NOT LABELED GOING THROUGH THE
 LIGHTING CONTROL PANEL.
 ** PLEASE KNOW THE LIGHTING CONTROL PANEL WILL BE NOTED
 AS "LCP" IN THE NOTES FORM HERE OUT.
 PLEASE SPECIFY THE SYSTEM WHICH IS BEING INSTALLED OR
 SPECIFIED FOR THE SCOPE OF WORK AND INTENDED
 CONTROL.110.3, 90.7
 PLEASE SEE EACH SPACE SHALL CONTAIN A DEVICE WHICH OVER
 -RIDES A SYSTEM, OR PROVIDES CONTROLS MEANS AS OTHER
 METHODS LISTED IN 13-415.1.ABC.1.1, .1.2.
 PLEASE SEE THERE ARE SEVERAL ROOMS WHICH DO NOT
 INDICATE ANY KIND OF OVER RIDE DEVICE, OCCUPANT SENSOR
 ETC.
 PLEASE SEE THE OVER RIDE TYPE DEVICE IS ALSO REQUIRED
 TO BE LOCATED IN THE AREAS IN WHICH THE OCCUPANT CAN
 SEE THE LIGHTING BEING CONTROLLED.
 PLEASE SEE MISSING AUTO SHUT OFF OF PIT LIGHTS. PLEASE
 BE SURE THE LCP PANEL ONLY CONTROL LIGHTING WHICH
 SHOULD NOT BE TURNED OFF, :IE: PLEASE CIRCUIT WHICH ARE
 SHOWN BEING WIRED TO THE LCP'S , HOWEVER PLEASE SEE
 THERE ARE ALSO EMERGENCY LIGHTING ON THOSE SAME
 CIRCUITS. PLEASE PROVIDE DETAIL ON THE LCP
 RISER/DIAGRAM WHERE ALL EXIT AND EMERGENCY LIGHTING IS
 CIRCUITED AHEAD OF THE LOCAL LIGHTING CONTROL DEVICES.
 PLEASE SEE MISSING PERFORMANCE CALCULATIONS FOR ALL
 AREAS. PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED DO
 NOT INDICATE ANY EXTERIOR LIGHTING; HOWEVER THE PLANS
 INDICATE LIGHTING IN MANY LOCATIONS.
 PLEASE SEE ENERGY CALCULATIONS DO NOT INDICATE THE
 REQUIRED AUTOMATED CONTROLS WHERE LISTING TYPE OF
 CONTROL.
 PLEASE SEE 13-415.1.AB.1, 13-415.2, 13-415.2.ABC.1,
 13-415.2.ABC.1.3.
 PLEASE SEE FBC CHAPTER 13, AS THERE ARE MANY AREAS AND
 ITEMS AS NOTED ABOVE WHICH NEEDS TO BE ADJUSTED.
  
 3) NOTE: PLEASE CORRELATE ALL SQ FT ON ALL DOCUMENTS.
 THIS NOTE REMAINS AS THE SQ FT ON PERMIT APPLICATION IS
 ONE, THE SQ FT ON PLANS ARE ANOTHER AND THE SQ FT ON
 ENERGY CALCULATIONS ARE YET ANOTHER. PLEASE COORDINATE
 ALL OF THESE.
 PLEASE BE SURE TO COORDINATE WITH ALL SHEETS ELECTRICAL
 AND OTHER WISE.
  
 4) NOTE: PLEASE SEE MISSING NORMAL AND EMERGENCY
 PHOTO-METRICS IN ALL EGRESS PATH AREAS. PLEASE SEE
 MISSING STAIR WAYS. PLEASE SEE NFPA-101 2003, 7.8.1.3,
 AND 7.9.2.2.
 A) STAIRS REQUIRE A MINIMUM OF 10FT CANDLES UNDER
 NORMAL AND 1FT CANDLE UNDER EMERGENCY.
 B) PLEASE SEE THIS IS FOR ALL EXIT STAIRS TO THE PUBLIC
 RIGHT OF WAY FOR EGRESS PATHS.
  
 PLEASE SEE PREVIOUS NOTES WHICH REQUESTED ALL MINIMUM
 LIGHTING LEVELS AS REQUIRED PER THE LIFE SAFETY CODE TO
 BE SHOWN.
 PLEASE SEE NO NORMAL LIGHTING LEVELS FOR EGRESS AREAS
 WERE SUBMITTED FOR REVIEW?
 PLEASE SEE THERE ARE DISCREPANCIES IN THE PLANS. PLEASE
 SEE THE LIGHTINGPLANS AND PHOTO-METRICS ETC AS THE
 SOME OF THE FIXTURES ARE MISSING FROM PHOTO-METRICS,
 SOME OF THE FIXTURES SHOWN ON PHOTO-METRICS ARE NOT THE
 SAME NUMBER OF FIXTURES ON PLANS ETC.
 PLEASE SEE SOME AREAS WHICH SHOW LIGHTING FOR EGRESS OR
 THE NUMBER AND TYPE OF FIXTURES DO NOT CORRELATE.
 PLEASE SEE SOME OF THE AREAS WHICH ARE NOTED FOR
 EXAMPLE WHICH ARE NOT ALL LOCATIONS WHICH COORDINATION
 IS NEEDED.
 PLEASE SEE: STAIRS 3, STAIR 4, EGRESS AREAS FROM SECOND
 FLOOR ON WEST SIDE OF GYM, AREAS ON WEST SIDE, AREAS ON
 NORTH SIDE, ETC
 PLEASE GO THROUGH ALL FIXTURES ON PLANS AND COORDINATE
 WITH THE FIXTURES ON PHOTO-METRICS AND ENERGY
 CALCULATIONS.
 PLEASE SEE SOME FIXTURES WHICH SEEM TO BE SHADED FOR A
 TYPICAL EM FIXTURE YET THE DESIGNATION IS THAT OF A
 NORMAL FIXTURE W/OUT BATTERY BACK UP.
 PLEASE SEE NFPA-101 7.8, 7.9, 7.8.1.3, 7.9.2.2 WHICH
 REQUIRES LIGHTING AND EMERGENCY LIGHTING TO THE PUBLIC
 RIGHT OF WAY. PLEASE SEE ALL EXTERIOR STAIRS INCLUDING
 LARGE AND SMALLER STAIRS AREAS WILL REQUIRE SOME SORT
 OF BATTERY BACK UP FIXTURES WHICH WILL PROVIDE THE
 MINIMUM FT CANDLES TO THE PUBLIC RIGHT OF WAY, OUT AND
 AWAY FROM THE BUILDING.
 PLEASE SEE THIS INCLUDES RAMP AREAS.
  
 5) NOTE: PLEASE SEE ELEVATOR EQUIPMENT ROOMS WHICH WILL
 REQUIRE A CHANGE IN FIXTURE TYPE OR AN ADDITIONAL
 FIXTURE. PLEASE SEE 700.16. THIS IS THE SAME COMMENT AS
 THESE ROOMS STILL ONLY INDICATE ONE FIXTURE. PLEASE
 PROVIDE A FIXTURE WHICH CONTAINS MORE THAN A SINGLE
 BALLAST CONTROLLING EACH BULB, OR ADJUST THE NUMBER OF
 FIXTURES OR ADJUST BY SOME OTHER MEANS. PLEASE SEE
 620.23 WHICH REQUIRE DEDICATED BRANCH CIRCUITS FOR
 THESE CIRCUITS FOR LIGHTING AND RECEPTACLES. PLEASE SEE
 THE POWER PLANS WHICH INDICATE A NOTE #3 WHICH STATES
 THE GFI WILL BE FED FROM THE VFD.(VARIABLE FREQUENCY
 DRIVE) WHICH CAN NOT BE DONE OR IS PERMITTED.
 PLEASE SEE ONLY ONE OF THE TWO ELEVATOR EQUIPMENT ROOMS
 CONTAINS A DEDICATED LIGHTING CIRCUIT. PLEASE SEE THE
 CIRCUIT FOR ROOM #1 LIGHTING IS LISTED ON PANEL
 SCHEDULE *L1AA* AS A CIRCUIT WHICH FEEDS A *REFG*
 PANEL?
 PLEASE ADJUST ALL CIRCUITING FOR ELEVATOR ROOMS AND
 LIGHTING.
  
 6) NOTE: PLEASE SEE 110.26, 408.7, AND 240.24D WHICH DO
 NOT PERMIT ELECTRICAL PANELS TO BE LOCATED IN STORAGE
 ROOMS OR CLOSETS. PLEASE ADJUST LOCATIONS OF EQUIPMENT
 OR CREATE DEDICATED ELECTRICAL ROOMS/CLOSETS AS DONE IN
 SOME OTHER LOCATIONS ON PLANS.
 PLEASE KNOW THAT THIS NOTE REMAINS AS NOT ONLY ARE MANY
 LOCATIONS ON PLANS FOR THESE SAME LOCATIONS STILL
 IDENTIFIED AS *STORAGE ROOMS* BUT AS TO THE LOCATIONS,
 SIZE ETC THE FOLLOWING CONSIDERATION IS TO BE MADE FOR
 ROOM 113 ADJACENT TO THE *MULTI-PURPOSE ROOM*. THIS
 ROOM WHICH CONTAINS THESE ELECTRICAL PANELS IS THE ONLY
 ROOM WHICH IS ADJACENT TO THIS MULTI-PURPOSE ROOM WHICH
 CONTAINS NO OTHER ADJACENT STORAGE ROOMS OR CLOSETS.
 THUS, THIS ROOM DUE TO IS SIZE, PROXIMITY AND THE LACK
 OF ANY OTHER STORAGE AREAS WILL MOST CERTAINLY BE
 UTILIZED AS A STORAGE ROOM OF SORTS. THE NEC AND LIFE
 SAFETY CODE REQUIRE THAT NOT ONLY ARE ITEMS NOT
 PERMITTED TO BE STORED IN THESE ROOMS THEY ALSO
 PROHIBIT THE STORING OF COMBUSTIBLES AND EASILY
 IGNITABLE MATERIALS ABOUT ELECTRICAL EQUIPMENT
 CONTAINING OVER CURRENT PROTECTION. IN THE INTEREST OF
 NOT ONLY THE FIRE HAZARD TO PROPERTY, THE LIFE SAFETY
 TO OCCUPANTS SHOULD BE CONSIDERED TO CHANGE THIS
 AREA/WALLS/LAYOUT TO PERHAPS PROVIDE A SEPARATE STORAGE
 AREA FOR THIS MULTI-PURPOSE ROOM AND THE MECHANICAL AND
 ELECTRICAL ROOMS TO CONTAIN NOT ONLY LOCKED DOORS, BUT
 TO ALLEVIATE THE STORAGE POTENTIAL. THIS WILL BE GONE
 OVER IN DETAIL WITH THE FIRE MARSHAL AND FIRE PLAN
 REVIEWER. PLEASE CONSULT WITH THIS OFFICE AND FIRE
 DEPARTMENT FOR ANY OTHER LOCATIONS/PROPOSED CHANGES. **
 ACCESS TO ELECTRICAL ROOMS SHALL BE FOR *QUALIFIED
 PERSONNEL* AS DEFINED IN THE NEC.
 *** PLEASE SEE ACCESS TO ELECTRICAL EQUIPMENT SHOULD
 ALSO NOT BE THROUGH STORAGE ROOMS. EQUIPMENT SHOULD BE
 LOCATED IN A MANNER WHICH READY ACCESS CAN BE GRANTED
 AND QUITE OFTEN STORAGE ROOMS BECOME A LOCATION WHERE
 THINGS IMPEDE ACCESS AS NEEDED.
  
 7) NOTE: PLEASE SEE THE CIVIL SHEETS ARE MISSING
 REQUIRED INFORMATION ON TITLE BLOCKS AS REQUIRED PER
 FAC 61G15-23.002 AND FS 471.023. NOT A COMMENT FOR KAMM
 CONSULTING.
 MISSING PRINTED NAME, PRINTED LICENSE NUMBER ALONG WITH
 MISSING CERTIFICATE OF AUTHORIZATION NUMBER. THIS IS
 REQUIRED WHETHER OR NOT COMMENT IS MADE BY ANY OTHER
 TRADE.
  
 8) NOTE:PLEASE COORDINATE ALL FIXTURES ON PLANS AND
 IDENTIFY ALL FIXTURES. PLEASE SEE PLANS STILL CONTAIN
 SEVERAL FIXTURES WHICH ARE NOT IDENTIFIED OR COORDINATE
 WITH FIXTURE LEGEND, LIGHTING PLANS AND PHOTO-METRIC
 PLANS AS NOTED ABOVE IN NOTE #2.
 FBC 106.1.2 ADMIN SECTION.
  
 9) NOTE: SAME NOTE AS ON PREVIOUS REVIEW WHICH WILL
 REMAIN AS COORDINATION OF CIRCUITS, CONTROLS ETC AS
 NOTED IN NOTE #2 ABOVE NEEDS TO BE DONE.
 PLEASE SEE THERE ARE SEVERAL CIRCUITS ON PLANS WHICH
 DO NOT SEEM TO BE SHOWN GOING THROUGH ANY OF THE
 LCP'S?
 PLEASE PROVIDE A COMPLETE LCP SCHEDULE FOR ALL
 CIRCUITS.
 13-415.1.ABC.1.1, .1.2, AND .1.3.
  
 10) NOTE: PLEASE PROVIDE MORE INFORMATION ON MAIN 1 OF
 2. PLEASE INDICATE SIZE, VOLTAGE ETC.
 THIS NOTE REMAINS AS ONLY INFORMATION ON THE EXISTING
 PANEL/MAIN IN THE AMPHITHEATRE WAS NOTED.
 THE SIZE, VOLTAGE, OVER CURRENT PROTECTION CAN NOT BE
 ASSUMED. THE RESPONSE LETTER MENTIONS TO SEE REVISED
 E5.1, YET NO CHANGES OR INFORMATION COULD BE FOUND.
 PLEASE SEE THE RISER SHOWS *DASHED LINES* FOR MAIN 1
 AND MAIN 2, WHICH AS NOTED ON THE RIGHT OF RISER, THE
 *DASHED LINES* REPRESENT THESE AS *EXISTING*, HOW IS
 THIS POSSIBLE WHEN THE BUILDING IS BEING BUILT AND THIS
 EQUIPMENT IS NOT INSTALLED AT THIS TIME?
 PLEASEADJUST DESIGNATIONS.
 230, 240, 110.3, 90.7
 FBC 106.1.2
  
 11) NOTE: PLEASE ADJUST NOTED #12 FOR RISER AS THE NOTE
 TENDS TO LEND TO THE DISCONNECTING OF THE EXISTING
 GROUNDING ELECTRODE SYSTEM.
 PLEASE ADJUST NOTE WITH WORDS WHICH REQUIRES THE
 *SEPARATION* OF THE EXISTING NEUTRAL AND GROUNDING
 ELECTRODE SYSTEM BOND, SO THAT THE NEW EQUIPMENT
 GROUNDING CONDUCTOR FROM THE NEW MAIN IS CONNECTED TO
 THE EXISTING GROUNDING ELECTRODE SYSTEM. (WORDS TO THE
 SAME AFFECT TO BE CHOSEN BY DESIGNER) (PLEASE CONTACT
 THIS OFFICE FOR ANY QUESTIONS OR TO GO OVER IF NEED
 BE)
 250.6, 250.50, 250.24, 250.110 ETC.
  
 12) NOTE: PLEASE SEE LIGHTING ON PLANS WHICH DO NOT
 CONTAIN SOME CIRCUITING DESIGNATIONS.
 PLEASE ALSO SEE SOME EM LTS, WHICH DO NOT INDICATE
 CIRCUITING.(GYM)
 PLEASE SEE FBC 106.3.5.1.2, 106.1.2 FOR COORDINATION
 AND SEE 700.12E FOR CIRCUITING OF EMERGENCY AND EXIT
 LIGHTS TO LOCAL LIGHTING CIRCUITS AS SHOWN ON MOST OF
 THE PLANS.
  
 13) NOTE: PLEASE SEE NO LOAD CALCULATIONS OR LOAD
 SUMMARY COULD BE LOCATED.
 220.3, 220.10, 220.11, 220.13, 215.3 AND 230.42 ETC.
 FBC ADMIN SECTION 106.3.5.1.2
  
 14) NOTE: PLEASE SEE SETS OF PLANS SUBMITTED ARE NOT
 COMPLETE AT THIS TIME FOR REVIEW. PLEASE SEE PLANS ARE
 MISSING THE FIRST FLOOR WEST SIDE POWER PLANS.SETS
 FOR POWER PLANS AND SHEETS START AT E3.1.2. PLEASE SEE
 THE PREVIOUS PLANS SUBMITTED DID CONTAIN A E3.1.1. FBC
 106.3.5.1.2, 106.1.2
  
 15) NOTE: PLEASE BE SURE THAT ALL SHEETS IN ALL SETS
 ARE SIGNED, DATED AND SEAL BY THE DESIGN PROFESSIONALS
 AS REQUIRED UNDER FAC 61G15-23.002 AND FS 471.025.
 PLEASE SEE THAT MULTIPLE SHEETS IN SOME SETS ARE NOT
 SIGNED, DATED OR SEALED AT ALL FOR M, E, P AND FA
 SHEETS. THIS SEEMS TO BE THE NEW REVISED SHEETS ONLY.
 THIS REVIEWER CHECKED AT LEAST ONE OTHER SET SUBMITTED
 AND THIS WAS DONE HOWEVER NOT ALL SETS WERE DONE.
 PLEASE BE SURE TO DO THIS FOR ALL SHEETS, ALL SETS AND
 ALL DOCUMENTS.
  
 16) NOTE: PLEASE SEE INDICATE ANY FIRE SPRINKLER WATER
 LINE AS PART OF THE GROUNDING ELECTRODE SYSTEM.
 250.106
 PLEASE SEE RESPONSE MENTIONS TO *CONNECT TO THE
 EXISTING FS LINE* THIS IS OR AT LEAST SHOULD BE PART OF
 THE EXISTING FIRE SPRINKLER SYSTEM AT THE EXISTING
 SERVICE LOCATION, HOVER NOTE SHOULD INDICATE NOT ONLY
 THE METALLIC COLD WATER LINE , BUT ALSO THE FIRE
 SPRINKLER LINE.
  
 17) NOTE: PLEASE SEE FBC 2004 11-4.28.2 AND
 11-4.28.3(4) FOR ALL AUDIBLE AND VISUAL DEVICES. PLEASE
 SEE 11-4.28.1 FOR LOCATION REQUIREMENTS. PLEASE BE SURE
 FA PLANS INDICATE ALL THE MINIMUM LEVELS PER ADA AND
 PLACES NOTES ALSO FOR FBC SECTIONS AS GIVEN. PLEASE SEE
 THIS IS THE SAME NOTE AND THE RESPONSE LETTER ACTUALLY
 DOES NOT CONTAIN ANY WRITTEN RESPONSE TO THIS? PLEASE
 SEE THAT THE ONLY REVISED SHEET INSERTED IN THE FA
 SHEETS IS THAT OF SHEET FA0.1.
 PLEASE SEE SECTION 11-4.28.1 OF THE FBC 2004 FOR
 LOCATIONS WHICH INCLUDE ALL COMMON AND ACCESSIBLE AREAS
 FOR THESE TYPES OF DEVICES. THE MINIMUM LEVELS FOR ADA
 COMPLIANCE ARE 75CD, MANY SHOWN AS 15CD.
 PLEASE ADJUST FA SHEETS FOR THESE LOCATIONS.
  
 18) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENT FOR CODE COMPLIANCE AS THIS IS ONLY
 GIVEN AS A NOTICE AT THIS TIME.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 **PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
2007-04-19 16:35:021-ROLL IN ELEC FOR REVIEW