Date |
Text |
2007-04-21 12:53:12 | 2007-04-21 12:53:12 |
| |
| ** UNSAT 2ND REVIEW** |
| |
| ** PLEASE SEE ANY REFERENCES TO THE FBC CHAPTER 1 ARE |
| THE ADMINISTRATIVE SECTION AS ADOPTED BY THE CITY OF |
| WEST PALM BEACH. |
| |
| ** PLEASE SEE THERE ARE MANY ITEMS FROM THE PREVIOUS |
| REVIEW WHICH ARE STILL IN NEED OF ADDRESSING ALONG WITH |
| SOME NEW COMMENTS AS WELL AS COMMENT WHICH COULD NOT BE |
| MADE YET AS THE PLANS SUBMITTED CONTAIN SOME MISSING |
| SHEETS ETC. PLEASE SEE NOTES BELOW WHICH WILL FURTHER |
| EXPLAIN. |
| ** SOME OF THE COMMENTS BELOW ARE NOT RELEVANT TO KAMM |
| CONSULTING. |
| |
| ** PLEASE SEE THAT ONE SET CONTAINS SOME REDLINES FOR |
| AREAS FOR SOME OF THE NOTES. |
| |
| 1) NOTE: PLEASE BE SURE ALL PLANS REFLECT THE FOLLOWING |
| CODES AT A MINIMUM. |
| 2002 NFPA-70, 2003 NFPA-101, 2002 NFPA-72 |
| THIS IS REQUIRED ON THE ARCHITECTURAL SHEETS AS WELL. |
| THE ELECTRICAL SHEETS WERE CORRECTED WITH THE UPDATED |
| CODE INFORMATION.. |
| |
| 2) NOTE: PLEASE SEE THAT COMPLIANCE WITH THE FBC |
| CHAPTER 13 HAS NOT YET BEEN MET. PLEASE SEE THE |
| RESPONSE LETTER ONLY RESPONDED TO THE FIRST SENTENCE OF |
| THE PREVIOUS NOTES AND THE REST OF THE NOTE #2 FROM |
| PREVIOUS REVIEW WAS LEFT. |
| |
| A) PLEASE SEE THAT THE PREVIOUS REVIEW NOTE WILL BE |
| LEFT AS IS AND NEW EXPLANATORY NOTES ARE LISTED AS |
| FOLLOWS. |
| |
| B) PLEASE SEE SOME OF THE CIRCUITING SHOWN ON PLANS |
| WHICH INDICATE CONTROLS THROUGH THE LCPS ARE NOT LISTED |
| ON THE LCPS OR DO NOT CORRELATE. PLEASE SEE THAT |
| CIRCUIT/CONTROL DESIGNATIONS ARE SHOWN AS AB ON ONE AND |
| BA ON ANOTHER. |
| |
| C) PLEASE SEE THERE ARE STILL DEVICES AND SYMBOLS ON |
| PLANS WHICH ARE NOT LISTED ON THE SYMBOL LEGEND FOR |
| OVER RIDE DEVICES ON THE SYMBOL LEGEND FOR ELECTRICAL |
| DEVICES. |
| |
| D) PLEASE SEE THAT THE LEGEND FOR OVER RIDE DEVICES DO |
| NOT INDICATE ANY MAXIMUM TIME FOR PERMITTED OVER RIDES |
| AS REQUIRED. |
| |
| E) PLEASE SEE THAT MANY AREAS LIKE HALLWAYS, BATHROOMS |
| AND OTHER AREAS ETC CONTAIN AN *SO* AND *SW* TYPE |
| DEVICES WHICH WILL NOT PROVIDE COVERAGE FOR LIGHTING |
| CONTROL FOR LIFE SAFETY OR NORMAL OVER RIDE CONTROL. |
| PLEASE SEE SOME HALLS WHICH CONTAIN THIS DEVICE AT ONE |
| END OF THE HALL OR ON ONE SIDE WITH WALLS ETC BLOCKING |
| ANY DETECTION FROM OTHER AREAS FOR OVER RIDE. PLEASE |
| SEE *SK* DEVICE WHICH IS NOT LISTED FOR CONTROL OR WHAT |
| TYPE OF OPERATION. |
| |
| F) PLEASE SEE ROOMS AND AREAS WHICH DO CONTAIN FLOOR TO |
| CEILING HEIGHT PARTITIONS OR WALLS WHICH THESE ROOMS |
| ARE SEPARATE AND NO OVER RIDE DEVICES ARE SHOWN ON |
| PLANS. |
| |
| G) PLEASE THE COMPLETE REVIEW FOR LIGHTING AS SHOWN ON |
| PLANS AND LIGHTING ON FIXTURE LEGEND AND LIGHTING ON |
| ENERGY CALCULATIONS CAN NOT BE REVIEWED AS THE ENERGY |
| CALCULATIONS DO NOT CORRELATE WITH PLANS FOR LIGHTING |
| OR WITH FIXTURE LEGEND FOR TYPES OF FIXTURES, NUMBER OF |
| FIXTURES, AND WATTAGE ON FIXTURES. |
| |
| H) PLEASE SEE THE TYPE OF CONTROLS FOR LIGHTING DOES |
| NOT CORRELATE. THE ENERGY CALCULATIONS STILL INDICATE |
| *MANUAL ON/OFF8 FOR CONTROL? |
| |
| I) PLEASE SEE SOME CIRCUITS WHICH ARE NOTED AS BEING |
| CONTROLLED THROUGH A LIGHTING DIMMING PANEL WHICH IS |
| NOT INDICATED IN ANY LIGHTING CONTROL PANEL OR ON |
| LIGHTING CONTROL DEVICES. |
| PLEASE PROVIDE MORE DETAILS ON HOW THIS OPERATION WILL |
| TAKE PLACE. NEED TO PROVIDE MORE INFORMATION FOR |
| REVIEW. FBC 106.1.2 |
| |
| ** PLEASE KNOW AS THERE ARE MANY ITEMS WHICH ARE NOT |
| YET CLEAR OR SHOWN, COMPLETE REVIEW FOR SOME ITEMS CAN |
| NOT BE DONE. |
| |
| * PREVIOUS REVIEW NOTE FROM REVIEW #1* |
| PLEASE SEE FBC CHAPTER 13. PLEASE SEE |
| 13-415.1.ABC.1.1, .1.2 AND .1.3. |
| PLEASE SEE THERE ARE MANY AREAS WHICH INDICATE SOME |
| SORT OF SYMBOL NEXT TO SWITCH, HOWEVER AS THIS SYMBOL |
| IS NOT LOCATED ON THE SYMBOL SCHEDULE IT IS UNCLEAR |
| WHAT THIS IS FOR REVIEW OF COMPLIANCE WITH ANY LIGHTING |
| CONTROL REQUIREMENTS. |
| PLEASE SEE MANY OTHER AREAS WHICH A SWITCH IS BEING |
| SHOWN AND THE CIRCUIT IS NOT LABELED GOING THROUGH THE |
| LIGHTING CONTROL PANEL. |
| ** PLEASE KNOW THE LIGHTING CONTROL PANEL WILL BE NOTED |
| AS "LCP" IN THE NOTES FORM HERE OUT. |
| PLEASE SPECIFY THE SYSTEM WHICH IS BEING INSTALLED OR |
| SPECIFIED FOR THE SCOPE OF WORK AND INTENDED |
| CONTROL.110.3, 90.7 |
| PLEASE SEE EACH SPACE SHALL CONTAIN A DEVICE WHICH OVER |
| -RIDES A SYSTEM, OR PROVIDES CONTROLS MEANS AS OTHER |
| METHODS LISTED IN 13-415.1.ABC.1.1, .1.2. |
| PLEASE SEE THERE ARE SEVERAL ROOMS WHICH DO NOT |
| INDICATE ANY KIND OF OVER RIDE DEVICE, OCCUPANT SENSOR |
| ETC. |
| PLEASE SEE THE OVER RIDE TYPE DEVICE IS ALSO REQUIRED |
| TO BE LOCATED IN THE AREAS IN WHICH THE OCCUPANT CAN |
| SEE THE LIGHTING BEING CONTROLLED. |
| PLEASE SEE MISSING AUTO SHUT OFF OF PIT LIGHTS. PLEASE |
| BE SURE THE LCP PANEL ONLY CONTROL LIGHTING WHICH |
| SHOULD NOT BE TURNED OFF, :IE: PLEASE CIRCUIT WHICH ARE |
| SHOWN BEING WIRED TO THE LCP'S , HOWEVER PLEASE SEE |
| THERE ARE ALSO EMERGENCY LIGHTING ON THOSE SAME |
| CIRCUITS. PLEASE PROVIDE DETAIL ON THE LCP |
| RISER/DIAGRAM WHERE ALL EXIT AND EMERGENCY LIGHTING IS |
| CIRCUITED AHEAD OF THE LOCAL LIGHTING CONTROL DEVICES. |
| PLEASE SEE MISSING PERFORMANCE CALCULATIONS FOR ALL |
| AREAS. PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED DO |
| NOT INDICATE ANY EXTERIOR LIGHTING; HOWEVER THE PLANS |
| INDICATE LIGHTING IN MANY LOCATIONS. |
| PLEASE SEE ENERGY CALCULATIONS DO NOT INDICATE THE |
| REQUIRED AUTOMATED CONTROLS WHERE LISTING TYPE OF |
| CONTROL. |
| PLEASE SEE 13-415.1.AB.1, 13-415.2, 13-415.2.ABC.1, |
| 13-415.2.ABC.1.3. |
| PLEASE SEE FBC CHAPTER 13, AS THERE ARE MANY AREAS AND |
| ITEMS AS NOTED ABOVE WHICH NEEDS TO BE ADJUSTED. |
| |
| 3) NOTE: PLEASE CORRELATE ALL SQ FT ON ALL DOCUMENTS. |
| THIS NOTE REMAINS AS THE SQ FT ON PERMIT APPLICATION IS |
| ONE, THE SQ FT ON PLANS ARE ANOTHER AND THE SQ FT ON |
| ENERGY CALCULATIONS ARE YET ANOTHER. PLEASE COORDINATE |
| ALL OF THESE. |
| PLEASE BE SURE TO COORDINATE WITH ALL SHEETS ELECTRICAL |
| AND OTHER WISE. |
| |
| 4) NOTE: PLEASE SEE MISSING NORMAL AND EMERGENCY |
| PHOTO-METRICS IN ALL EGRESS PATH AREAS. PLEASE SEE |
| MISSING STAIR WAYS. PLEASE SEE NFPA-101 2003, 7.8.1.3, |
| AND 7.9.2.2. |
| A) STAIRS REQUIRE A MINIMUM OF 10FT CANDLES UNDER |
| NORMAL AND 1FT CANDLE UNDER EMERGENCY. |
| B) PLEASE SEE THIS IS FOR ALL EXIT STAIRS TO THE PUBLIC |
| RIGHT OF WAY FOR EGRESS PATHS. |
| |
| PLEASE SEE PREVIOUS NOTES WHICH REQUESTED ALL MINIMUM |
| LIGHTING LEVELS AS REQUIRED PER THE LIFE SAFETY CODE TO |
| BE SHOWN. |
| PLEASE SEE NO NORMAL LIGHTING LEVELS FOR EGRESS AREAS |
| WERE SUBMITTED FOR REVIEW? |
| PLEASE SEE THERE ARE DISCREPANCIES IN THE PLANS. PLEASE |
| SEE THE LIGHTINGPLANS AND PHOTO-METRICS ETC AS THE |
| SOME OF THE FIXTURES ARE MISSING FROM PHOTO-METRICS, |
| SOME OF THE FIXTURES SHOWN ON PHOTO-METRICS ARE NOT THE |
| SAME NUMBER OF FIXTURES ON PLANS ETC. |
| PLEASE SEE SOME AREAS WHICH SHOW LIGHTING FOR EGRESS OR |
| THE NUMBER AND TYPE OF FIXTURES DO NOT CORRELATE. |
| PLEASE SEE SOME OF THE AREAS WHICH ARE NOTED FOR |
| EXAMPLE WHICH ARE NOT ALL LOCATIONS WHICH COORDINATION |
| IS NEEDED. |
| PLEASE SEE: STAIRS 3, STAIR 4, EGRESS AREAS FROM SECOND |
| FLOOR ON WEST SIDE OF GYM, AREAS ON WEST SIDE, AREAS ON |
| NORTH SIDE, ETC |
| PLEASE GO THROUGH ALL FIXTURES ON PLANS AND COORDINATE |
| WITH THE FIXTURES ON PHOTO-METRICS AND ENERGY |
| CALCULATIONS. |
| PLEASE SEE SOME FIXTURES WHICH SEEM TO BE SHADED FOR A |
| TYPICAL EM FIXTURE YET THE DESIGNATION IS THAT OF A |
| NORMAL FIXTURE W/OUT BATTERY BACK UP. |
| PLEASE SEE NFPA-101 7.8, 7.9, 7.8.1.3, 7.9.2.2 WHICH |
| REQUIRES LIGHTING AND EMERGENCY LIGHTING TO THE PUBLIC |
| RIGHT OF WAY. PLEASE SEE ALL EXTERIOR STAIRS INCLUDING |
| LARGE AND SMALLER STAIRS AREAS WILL REQUIRE SOME SORT |
| OF BATTERY BACK UP FIXTURES WHICH WILL PROVIDE THE |
| MINIMUM FT CANDLES TO THE PUBLIC RIGHT OF WAY, OUT AND |
| AWAY FROM THE BUILDING. |
| PLEASE SEE THIS INCLUDES RAMP AREAS. |
| |
| 5) NOTE: PLEASE SEE ELEVATOR EQUIPMENT ROOMS WHICH WILL |
| REQUIRE A CHANGE IN FIXTURE TYPE OR AN ADDITIONAL |
| FIXTURE. PLEASE SEE 700.16. THIS IS THE SAME COMMENT AS |
| THESE ROOMS STILL ONLY INDICATE ONE FIXTURE. PLEASE |
| PROVIDE A FIXTURE WHICH CONTAINS MORE THAN A SINGLE |
| BALLAST CONTROLLING EACH BULB, OR ADJUST THE NUMBER OF |
| FIXTURES OR ADJUST BY SOME OTHER MEANS. PLEASE SEE |
| 620.23 WHICH REQUIRE DEDICATED BRANCH CIRCUITS FOR |
| THESE CIRCUITS FOR LIGHTING AND RECEPTACLES. PLEASE SEE |
| THE POWER PLANS WHICH INDICATE A NOTE #3 WHICH STATES |
| THE GFI WILL BE FED FROM THE VFD.(VARIABLE FREQUENCY |
| DRIVE) WHICH CAN NOT BE DONE OR IS PERMITTED. |
| PLEASE SEE ONLY ONE OF THE TWO ELEVATOR EQUIPMENT ROOMS |
| CONTAINS A DEDICATED LIGHTING CIRCUIT. PLEASE SEE THE |
| CIRCUIT FOR ROOM #1 LIGHTING IS LISTED ON PANEL |
| SCHEDULE *L1AA* AS A CIRCUIT WHICH FEEDS A *REFG* |
| PANEL? |
| PLEASE ADJUST ALL CIRCUITING FOR ELEVATOR ROOMS AND |
| LIGHTING. |
| |
| 6) NOTE: PLEASE SEE 110.26, 408.7, AND 240.24D WHICH DO |
| NOT PERMIT ELECTRICAL PANELS TO BE LOCATED IN STORAGE |
| ROOMS OR CLOSETS. PLEASE ADJUST LOCATIONS OF EQUIPMENT |
| OR CREATE DEDICATED ELECTRICAL ROOMS/CLOSETS AS DONE IN |
| SOME OTHER LOCATIONS ON PLANS. |
| PLEASE KNOW THAT THIS NOTE REMAINS AS NOT ONLY ARE MANY |
| LOCATIONS ON PLANS FOR THESE SAME LOCATIONS STILL |
| IDENTIFIED AS *STORAGE ROOMS* BUT AS TO THE LOCATIONS, |
| SIZE ETC THE FOLLOWING CONSIDERATION IS TO BE MADE FOR |
| ROOM 113 ADJACENT TO THE *MULTI-PURPOSE ROOM*. THIS |
| ROOM WHICH CONTAINS THESE ELECTRICAL PANELS IS THE ONLY |
| ROOM WHICH IS ADJACENT TO THIS MULTI-PURPOSE ROOM WHICH |
| CONTAINS NO OTHER ADJACENT STORAGE ROOMS OR CLOSETS. |
| THUS, THIS ROOM DUE TO IS SIZE, PROXIMITY AND THE LACK |
| OF ANY OTHER STORAGE AREAS WILL MOST CERTAINLY BE |
| UTILIZED AS A STORAGE ROOM OF SORTS. THE NEC AND LIFE |
| SAFETY CODE REQUIRE THAT NOT ONLY ARE ITEMS NOT |
| PERMITTED TO BE STORED IN THESE ROOMS THEY ALSO |
| PROHIBIT THE STORING OF COMBUSTIBLES AND EASILY |
| IGNITABLE MATERIALS ABOUT ELECTRICAL EQUIPMENT |
| CONTAINING OVER CURRENT PROTECTION. IN THE INTEREST OF |
| NOT ONLY THE FIRE HAZARD TO PROPERTY, THE LIFE SAFETY |
| TO OCCUPANTS SHOULD BE CONSIDERED TO CHANGE THIS |
| AREA/WALLS/LAYOUT TO PERHAPS PROVIDE A SEPARATE STORAGE |
| AREA FOR THIS MULTI-PURPOSE ROOM AND THE MECHANICAL AND |
| ELECTRICAL ROOMS TO CONTAIN NOT ONLY LOCKED DOORS, BUT |
| TO ALLEVIATE THE STORAGE POTENTIAL. THIS WILL BE GONE |
| OVER IN DETAIL WITH THE FIRE MARSHAL AND FIRE PLAN |
| REVIEWER. PLEASE CONSULT WITH THIS OFFICE AND FIRE |
| DEPARTMENT FOR ANY OTHER LOCATIONS/PROPOSED CHANGES. ** |
| ACCESS TO ELECTRICAL ROOMS SHALL BE FOR *QUALIFIED |
| PERSONNEL* AS DEFINED IN THE NEC. |
| *** PLEASE SEE ACCESS TO ELECTRICAL EQUIPMENT SHOULD |
| ALSO NOT BE THROUGH STORAGE ROOMS. EQUIPMENT SHOULD BE |
| LOCATED IN A MANNER WHICH READY ACCESS CAN BE GRANTED |
| AND QUITE OFTEN STORAGE ROOMS BECOME A LOCATION WHERE |
| THINGS IMPEDE ACCESS AS NEEDED. |
| |
| 7) NOTE: PLEASE SEE THE CIVIL SHEETS ARE MISSING |
| REQUIRED INFORMATION ON TITLE BLOCKS AS REQUIRED PER |
| FAC 61G15-23.002 AND FS 471.023. NOT A COMMENT FOR KAMM |
| CONSULTING. |
| MISSING PRINTED NAME, PRINTED LICENSE NUMBER ALONG WITH |
| MISSING CERTIFICATE OF AUTHORIZATION NUMBER. THIS IS |
| REQUIRED WHETHER OR NOT COMMENT IS MADE BY ANY OTHER |
| TRADE. |
| |
| 8) NOTE:PLEASE COORDINATE ALL FIXTURES ON PLANS AND |
| IDENTIFY ALL FIXTURES. PLEASE SEE PLANS STILL CONTAIN |
| SEVERAL FIXTURES WHICH ARE NOT IDENTIFIED OR COORDINATE |
| WITH FIXTURE LEGEND, LIGHTING PLANS AND PHOTO-METRIC |
| PLANS AS NOTED ABOVE IN NOTE #2. |
| FBC 106.1.2 ADMIN SECTION. |
| |
| 9) NOTE: SAME NOTE AS ON PREVIOUS REVIEW WHICH WILL |
| REMAIN AS COORDINATION OF CIRCUITS, CONTROLS ETC AS |
| NOTED IN NOTE #2 ABOVE NEEDS TO BE DONE. |
| PLEASE SEE THERE ARE SEVERAL CIRCUITS ON PLANS WHICH |
| DO NOT SEEM TO BE SHOWN GOING THROUGH ANY OF THE |
| LCP'S? |
| PLEASE PROVIDE A COMPLETE LCP SCHEDULE FOR ALL |
| CIRCUITS. |
| 13-415.1.ABC.1.1, .1.2, AND .1.3. |
| |
| 10) NOTE: PLEASE PROVIDE MORE INFORMATION ON MAIN 1 OF |
| 2. PLEASE INDICATE SIZE, VOLTAGE ETC. |
| THIS NOTE REMAINS AS ONLY INFORMATION ON THE EXISTING |
| PANEL/MAIN IN THE AMPHITHEATRE WAS NOTED. |
| THE SIZE, VOLTAGE, OVER CURRENT PROTECTION CAN NOT BE |
| ASSUMED. THE RESPONSE LETTER MENTIONS TO SEE REVISED |
| E5.1, YET NO CHANGES OR INFORMATION COULD BE FOUND. |
| PLEASE SEE THE RISER SHOWS *DASHED LINES* FOR MAIN 1 |
| AND MAIN 2, WHICH AS NOTED ON THE RIGHT OF RISER, THE |
| *DASHED LINES* REPRESENT THESE AS *EXISTING*, HOW IS |
| THIS POSSIBLE WHEN THE BUILDING IS BEING BUILT AND THIS |
| EQUIPMENT IS NOT INSTALLED AT THIS TIME? |
| PLEASEADJUST DESIGNATIONS. |
| 230, 240, 110.3, 90.7 |
| FBC 106.1.2 |
| |
| 11) NOTE: PLEASE ADJUST NOTED #12 FOR RISER AS THE NOTE |
| TENDS TO LEND TO THE DISCONNECTING OF THE EXISTING |
| GROUNDING ELECTRODE SYSTEM. |
| PLEASE ADJUST NOTE WITH WORDS WHICH REQUIRES THE |
| *SEPARATION* OF THE EXISTING NEUTRAL AND GROUNDING |
| ELECTRODE SYSTEM BOND, SO THAT THE NEW EQUIPMENT |
| GROUNDING CONDUCTOR FROM THE NEW MAIN IS CONNECTED TO |
| THE EXISTING GROUNDING ELECTRODE SYSTEM. (WORDS TO THE |
| SAME AFFECT TO BE CHOSEN BY DESIGNER) (PLEASE CONTACT |
| THIS OFFICE FOR ANY QUESTIONS OR TO GO OVER IF NEED |
| BE) |
| 250.6, 250.50, 250.24, 250.110 ETC. |
| |
| 12) NOTE: PLEASE SEE LIGHTING ON PLANS WHICH DO NOT |
| CONTAIN SOME CIRCUITING DESIGNATIONS. |
| PLEASE ALSO SEE SOME EM LTS, WHICH DO NOT INDICATE |
| CIRCUITING.(GYM) |
| PLEASE SEE FBC 106.3.5.1.2, 106.1.2 FOR COORDINATION |
| AND SEE 700.12E FOR CIRCUITING OF EMERGENCY AND EXIT |
| LIGHTS TO LOCAL LIGHTING CIRCUITS AS SHOWN ON MOST OF |
| THE PLANS. |
| |
| 13) NOTE: PLEASE SEE NO LOAD CALCULATIONS OR LOAD |
| SUMMARY COULD BE LOCATED. |
| 220.3, 220.10, 220.11, 220.13, 215.3 AND 230.42 ETC. |
| FBC ADMIN SECTION 106.3.5.1.2 |
| |
| 14) NOTE: PLEASE SEE SETS OF PLANS SUBMITTED ARE NOT |
| COMPLETE AT THIS TIME FOR REVIEW. PLEASE SEE PLANS ARE |
| MISSING THE FIRST FLOOR WEST SIDE POWER PLANS.SETS |
| FOR POWER PLANS AND SHEETS START AT E3.1.2. PLEASE SEE |
| THE PREVIOUS PLANS SUBMITTED DID CONTAIN A E3.1.1. FBC |
| 106.3.5.1.2, 106.1.2 |
| |
| 15) NOTE: PLEASE BE SURE THAT ALL SHEETS IN ALL SETS |
| ARE SIGNED, DATED AND SEAL BY THE DESIGN PROFESSIONALS |
| AS REQUIRED UNDER FAC 61G15-23.002 AND FS 471.025. |
| PLEASE SEE THAT MULTIPLE SHEETS IN SOME SETS ARE NOT |
| SIGNED, DATED OR SEALED AT ALL FOR M, E, P AND FA |
| SHEETS. THIS SEEMS TO BE THE NEW REVISED SHEETS ONLY. |
| THIS REVIEWER CHECKED AT LEAST ONE OTHER SET SUBMITTED |
| AND THIS WAS DONE HOWEVER NOT ALL SETS WERE DONE. |
| PLEASE BE SURE TO DO THIS FOR ALL SHEETS, ALL SETS AND |
| ALL DOCUMENTS. |
| |
| 16) NOTE: PLEASE SEE INDICATE ANY FIRE SPRINKLER WATER |
| LINE AS PART OF THE GROUNDING ELECTRODE SYSTEM. |
| 250.106 |
| PLEASE SEE RESPONSE MENTIONS TO *CONNECT TO THE |
| EXISTING FS LINE* THIS IS OR AT LEAST SHOULD BE PART OF |
| THE EXISTING FIRE SPRINKLER SYSTEM AT THE EXISTING |
| SERVICE LOCATION, HOVER NOTE SHOULD INDICATE NOT ONLY |
| THE METALLIC COLD WATER LINE , BUT ALSO THE FIRE |
| SPRINKLER LINE. |
| |
| 17) NOTE: PLEASE SEE FBC 2004 11-4.28.2 AND |
| 11-4.28.3(4) FOR ALL AUDIBLE AND VISUAL DEVICES. PLEASE |
| SEE 11-4.28.1 FOR LOCATION REQUIREMENTS. PLEASE BE SURE |
| FA PLANS INDICATE ALL THE MINIMUM LEVELS PER ADA AND |
| PLACES NOTES ALSO FOR FBC SECTIONS AS GIVEN. PLEASE SEE |
| THIS IS THE SAME NOTE AND THE RESPONSE LETTER ACTUALLY |
| DOES NOT CONTAIN ANY WRITTEN RESPONSE TO THIS? PLEASE |
| SEE THAT THE ONLY REVISED SHEET INSERTED IN THE FA |
| SHEETS IS THAT OF SHEET FA0.1. |
| PLEASE SEE SECTION 11-4.28.1 OF THE FBC 2004 FOR |
| LOCATIONS WHICH INCLUDE ALL COMMON AND ACCESSIBLE AREAS |
| FOR THESE TYPES OF DEVICES. THE MINIMUM LEVELS FOR ADA |
| COMPLIANCE ARE 75CD, MANY SHOWN AS 15CD. |
| PLEASE ADJUST FA SHEETS FOR THESE LOCATIONS. |
| |
| 18) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| REPEAT COMMENT FOR CODE COMPLIANCE AS THIS IS ONLY |
| GIVEN AS A NOTICE AT THIS TIME. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| **PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
| |
2007-04-19 16:35:02 | 1-ROLL IN ELEC FOR REVIEW |