Plan Review Notes
Plan Review Notes For Permit 06110152
Permit Number 06110152
Review Stop B
Sequence Number 17
Notes
Date Text
2009-06-15 08:45:46BUILDING PLAN REVIEW
 PERMIT: 06110152
 ADD: 821 N. FLAGLER DR.
 CONT: ANDERSON-MOORE
 TEL: (561)662-1819
  
 JUNE 15, 2009
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS TO THE ADMINISTRATIVE
 CODE
 ORIGINAL REVIEW
 REVISION REVIEW DATED; 10-06-08
  
 ACTION:DENIED
  
 1) SHEET A3.2.1 & A5.2.3
  
 A) REVISION# 4 OF THIS SHEET INDICATES THE CHANGE IN
 FILL MATERIAL FROM EARTHENED FILL TO A GEO FOAM TO
 LESSEN THE LATERAL LOAD OR PRESSURES ON THE STAIR
 WALLS. PLEASE PROVIDE DOCUMENTATION THAT THE FOAM WILL
 MEET THE REQUIREMENTS OF SUPPORTING 3000 PSF FOUNDATION
 NOTES SHEET S-5. SHEET A.5.2.3 DETAIL# 1 INDICATES SEE
 STRUCTURAL DRAWINGS. STRUCTURAL SHEET S-2.1 THE WEST
 END OF THE SECOND FLOOR SLAB HAS A CUT SECTION DETAIL
 3/ S-9. WHEN REVIEWING THIS DETAIL THE PLANS STILL
 INDICATE EARTHENED FILL NOT A GEO FOAM, THE NOTE ON
 THIS SHEET INDICATES CONCRETE STAIRS ON GRADE SEE
 TYPICAL DETAIL. S-6 . S-6 AGAIN INDICATES EARTHENED
 FILL WITH WIRE MESH W.F 6X6 /W1.4XW1.4 NOT A STRUCTURAL
 STEEL REINFORCED SLAB.
  
 B CHAPTER 26 DEALS WITH FOAM PLASTICS WHEN USED IN
 CONSTRUCTION OF STRUCTURES AND BUILDINGS. THERE IS NO
 SECTION THAT INDICATES THE USE OF FOAM AS A FILLER
 BENEATH SLABS BUT TO USE FOAM FOR THIS APPLICATION IT
 WILL NEED TO COMPLY WITH 2603.8. SUCH TESTING SHALL BE
 RELATED TO THE ACTUAL END-USE CONFIGURATION AND BE
 PERFORMED ON THE FINISHED MANUFACTURED FOAM PLASTIC
 ASSEMBLY IN THE MAXIMUM THICKNESS INTENDED FOR USE.
  
 JUNE 15, 2008
 THE SUBMITTAL FOR GEO FOAM HAS NOT MET THE REQUIREMENTS
 OF 2603.8. THE 2004 NOR THE 2007 FBC DOES NOT RECONIZE
 THE ASTM D-6817 STANDARD. ALL CUT SHEETS INDICATE THE
 USE OF GEO FOAM IN GENERAL EARTHWORK APPLICATIONS,
 LEVEES, DIKES, BIRMS... NOT FOR WWITHIN BUILDINGS. THE
 GEO FOAM BROSHURE DOES INDICATE THAT IT IS COMBUSTIBLE!
 SECTION 603.1 DEALS WITH ALLOWED COMBUSTIBLES IN TYPE I
 OR II BUILDINGS, EXCEPTION 3 DEALS WITH PLASTICS (FOAM)
 IN ACCORDANCE WITH CHAPTER 26.
  
 TO ALLOW FOAM PLASTICS IN BUILDINGS THE FOLOWING MUST
 BE MET:
 2603.3 SURFACE-BURNING CHARACTERISTICS. UNLESS
 OTHERWISE INDICATED IN THIS SECTION, FOAM PLASTIC
 INSULATION AND FOAM PLASTIC CORES OF MANUFACTURED
 ASSEMBLIES SHALL HAVE A FLAME SPREAD INDEX OF NOT MORE
 THAN 75 AND A SMOKE-DEVELOPED INDEX OF NOT MORE THAN
 450 WHERE TESTED IN THE MAXIMUM THICKNESS INTENDED FOR
 USE IN ACCORDANCE WITH ASTM E 84.
  
 EXCEPTION #4 IS WHEN FOAM PLASTIC IS USED IN
 INSTALATIONS GREATER THAN 4". FOAM PLASTIC INSULATION
 GREATER THAN 4 INCHES (102 MM) IN THICKNESS SHALL HAVE
 A MAXIMUM FLAME SPREAD INDEX OF 75 AND A
 SMOKE-DEVELOPED INDEX OF 450 WHERE TESTED AT A MINIMUM
 THICKNESS OF 4 INCHES (102 MM), PROVIDED THE END USE IS
 APPROVED IN ACCORDANCE WITH SECTION 2603.8 USING THE
 THICKNESS AND DENSITY INTENDED FOR USE.
  
 2603.8 SPECIAL APPROVAL.
 FOAM PLASTIC SHALL NOT BE REQUIRED TO COMPLY WITH THE
 REQUIREMENTS OF SECTIONS 2603.4 THROUGH 2603.7, WHERE
 SPECIFICALLY APPROVED BASED ON LARGE-SCALE TESTS SUCH
 AS, BUT NOT LIMITED TO, FM 4880, UL 1040, NFPA 286 OR
 UL 1715. SUCH TESTING SHALL BE RELATED TO THE ACTUAL
 END-USE CONFIGURATION AND BE PERFORMED ON THE FINISHED
 MANUFACTURED FOAM PLASTIC ASSEMBLY IN THE MAXIMUM
 THICKNESS INTENDED FOR USE. FOAM PLASTICS THAT ARE USED
 AS INTERIOR FINISH ON THE BASIS OF SPECIAL TESTS SHALL
 ALSO CONFORM TO THE FLAME SPREAD REQUIREMENTS OF
 CHAPTER 8. ASSEMBLIES TESTED SHALL INCLUDE SEAMS,
 JOINTS AND OTHER TYPICAL DETAILS USED IN THE
 INSTALLATION OF THE ASSEMBLY AND SHALL BE TESTED IN THE
 MANNER INTENDED FOR USE.
  
 PLEASE PROVIDE THE FLAME SPREAD AND SMOKE DEVELOPMENT
 IN COMPLIANCE WITH 2603.3 OR THE TESTING FOR
 LARGE-SCALE TEST IN COMPLIANCE WITH 2603.8.