2007-01-06 17:09:55 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 CHAPTER 1 |
| FBC-2004 CHAPTER 11 |
| |
| 1. SHT A0.0.1 INDICATES ASSEMBLY OCCUPANCY FOR THE 1ST |
| & 2ND FLOORS. PER SECTION 403.1.1, POTTY PARITY, |
| RESTROOMS WHICH ARE OPEN TO THE PUBLIC, MUST HAVE A |
| RATIO OF 3:2 WATER CLOSETS PROVIDED FOR WOMEN AS THE |
| COMBINED TOTAL OF WATER CLOSETS & URINALS PROVIDED FOR |
| MEN. POTTY PARITY DOES NOT SEEM TO BE COMPLIED WITH. |
| PLEASE SHOW COMPLIANCE WITH SECTION 403.1.1. |
| |
| 2. SHT A2.4.1 SUBMIT CALCULATIONS FOR PRIMARY AND |
| SECONDARY ROOF DRAINS PER SECTIONS 1106 & 1107 WITH ALL |
| SUBSECTIONS & TABLES. SHOW THE SQUARE FOOTAGE OF EACH |
| AREA TO BE DRAINED, AND 1/2AREA OF ALL VERTICAL WALLS |
| INCLUDING PARAPETS AS WELL AS ANY ROOF AREA FROM ABOVE |
| THAT DRAINS ON TO THE LOWER ROOFS IN THE CALCULATIONS. |
| SECTIONS 106.3.5.1.3(7)(13) & TABLES 1106.2, 1106.3 & |
| 1106.6. INDICATE THE SIZE OF THE GUTTERS AND SHOW SLOPE |
| WITH THE HIGH POINTS OF THE GUTTER INDICATED. |
| |
| 3. SHTS A4.1.1 & A4.1.2 SHOW THE CLEAR FLOOR SPACE FOR |
| THE URINAL, ACCESSIBLE SHOWERS AND DRINKING FOUNTAINS |
| PER SECTIONS 11-4.18..3, 11-4.21.2, & 11-4.15.5. |
| |
| 4. SHT A7.1.1 FINISH SCHEDULE. BOY'S RESTROOM 107 & |
| GIRL'S RESTROOM 109 INDICATE PAINTED GWB FOR THE WALL |
| FINISH. SECTION 1210.2 REQUIRES A "SMOOTH, HARD, |
| NONABSORBENT" SURFACE. PAINTED GWB IS NOT CONSIDERED A |
| "HARD" SURFACE. PLEASE INDICATE HOW THIS REQUIREMENT |
| WILL BE COMPLIED WITH. ALSO SEE BOY'S RESTROOM 302 AND |
| GIRL'S RESTROOM 304. NO FINISH IS INDICATED. PLEASE |
| INDICATE WALL FINISH TO COMPLY WITH SECTION 1210.2. |
| |
| 5. SHT A8.1.3 SHOW THE FOLLOWING REQUIREMENTS: |
| A. 11-4.16.6 DISPENSERS (FIG 29(B) |
| B. 11-4.18.4 FLUSH CONTROLS |
| C. 11-4.19.5 FAUCETS |
| D. 11-4.21.2 SIZE & CLEARANCES |
| E. 11-4.21.3 SEAT |
| F. 11-4.21.4 GRAB BARS (FIG 11-37) |
| G. 11-4.21.5 CONTROLS |
| H. 11-4.21.6 SHOWER UNIT |
| |
| 6. SUBMIT A DETAIL FOR THE ACCESSIBLE DRINKING |
| FOUNTAINS. SHOW COMPLIANCE WITH SECTION 11-4.15 AND ALL |
| SUBSECTIONS INCLUDING ALSO SECTION 11-4.1.3(10)(A) |
| PROVISIONS FOR THOSE WHO HAVE DIFFICULTY BENDING AND |
| STOOPING. |
| |
| 7. SHT P0.1 WATER HEATER DETAIL. SUBMIT CALCULATION FOR |
| THE EXPANSION TANK FOR THE 1230 GAL W/H. SUBMIT THE |
| MANUF. SPECIFICATION SHEETS AND INDICATE THE MODEL |
| NUMBER SHOWING TANK SIZE. SECTION 607.3.2. |
| |
| 8. SHT P3-1.1 RPZV BACKFLOWS ARE REQUIRED ON EACH WATER |
| SUPPLY LINE INTO THE BUILDING. SECTION 608.13.2. SHOW |
| ON THE PLANS. |
| |
| 9. SHT P5.1 VENT SHOWN UPSTREAM OF THE SANITARY STACK |
| AND PRIOR TO THE FIRST WATER CLOSETS IS NOT SHOWN ON |
| THE FLOOR PLAN. (TOILET ROOMS 221 & 223). PLEASE |
| CORRELATE INFORMATION BETWEEN THE FLOOR PLAN AND THE |
| RISER DIAGRAM. SECTION 106.1.1. |
| |
| 10. SHT P5.1 SANITARY RISER DIAGRAM. SHOW THE DFU'S AS |
| THEY ACCUMULATE IN THE SYSTEM TO VERIFY THE PIPE SIZES. |
| SECTION 106.1.1 AND TABLES 709.1, 710.1(1) & 710.1(2). |
| |
| 11. SHTS P2.3.1, P2.4.1, AND P2.4.2 SHOW THE VENTS THRU |
| THE ROOF ON THE ROOF PLANS TO REFLECT THE RISER |
| DIAGRAM. SECTION 106.1.1. |
| |
| 12. SHT P6.1 DOMESTIC WATER ISOMETRIC. SHOW THE |
| REQUIRED RPZV BACKFLOWS ON THE WATER SERVICES, AND SHOW |
| AN RPZV ON THE SUPPLY LINE FOR THE 2" MAKE UP WATER TO |
| THE ROOF. SECTION 608.13.2. |
| |
| 13. SHT P6.1 WATER HAMMER ARRESTORS SHALL BE LOCATED |
| NEAR THE FIXTURES IN AN "EFFECTIVE RANGE" NOT IN THE |
| CEILING AS SHOWN. PDI-WH 201 AND MANUF. INSTALLATION |
| INSTRUCTIONS. |
| |
| 14. SHT P6.1 SHUT OFF VALVES ARE REQUIRED ON BOTH SIDES |
| OF THE CIRCULATION PUMP FOR THE WATER HEATERS. ALSO |
| SHOW THE VALVES ON THE WATER HEATER DETAIL SHT P0.1. |
| SECTION 606.2(3). |
| |
| 15. SUBMIT A STORM RISER ISOMETRIC RISER DIAGRAM. SHOW |
| ALL PIPE SIZES, OFFSETS, AND SQUARE FOOTAGE AS IT |
| ACCUMULATES IN THE SYSTEM. SECTION 106.3.5.1.3. |
| |
| 16. SUBMIT A CONDENSATE RISER ISOMETRIC RISER DIAGRAM. |
| SHOW ALL PIPE SIZES. SECTION 106.3.5.1.3. |
| |
| REVIEW BY KEN STEVENS |