Plan Review Notes For Permit 06110152 |
Permit Number |
06110152 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-01-09 08:04:43 | DENIED: | | 1.PLAN SHEET M2.1.1 & DETAIL ON SHEET M7.3, DOES NOT | | INDICATE TERMINATION OF THE REFRIGERANT RELIEF VENT. | | PLEASE SHOW COMPLIANCE WITH 2004 FMC 1105.7,PRESSURE | | RELIEF DEVICES, PURGE SYSTEMS, FUSIBLE PLUGS LOCATED | | WITHIN THE MACHINERY ROOM SHALL TERMINATE OUTSIDE OF | | THE BUILDING NOT LESS THAN 15 FT ABOVE THE ADJOINING | | GRADE AND NOT LESS THAN 20 FT FROM ANY WINDOW, | | VENTILATION OPENING OR EXIT. | | | | 2.PLAN SHEET M2.1.1, CHILLER ROOM EXHAUST TERMINATION | | SHALL BE DISCHARGED NOT LESS THAN 20 FT FROM A PROPERTY | | LINE OR OPENINGS INTO BUILDINGS PER 2004 FMC 1105.6. | | | | 3.PLAN SHEET M2.1.1 KEY NOTE 5 INDICATES REFRIGERANT | | MONITORING PANEL.PLEASE INDICATE LOCATATION AND | | NUMBER OF DETECTORS TIED INTO THE PANEL. | | | | 4.PLAN SHEET M6.1 INDICATES EXHAUST AIR CALCULATION | | AS REQUIRED IN ASHRAE 15.PLEASE PROVIDE THE NORMAL | | VENTILATION REQUIREMENTS PER 2004 FMC 1105.6. | | | | 5.PLEASE NOTE, THE MECHANICAL PORTION OF THE SPEC | | BOOK REFER TO THE MECHANICAL DRAWINGS FOR | | SPECIFICATIONS.PLEASE PROVIDE INFORMATION ON PIPE | | MATERIAL PER 2004 FMC CHAPTER 12. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS | | AT (561)805-6719 OR E-MAIL [email protected]. |
|