2006-11-28 07:52:39 | *** UNSAT *** |
| |
| 1) NOTE: PLEASE BE PLANS REFLECT THE FOLLOWING CODES AT |
| A MINIMUM. |
| 2002 NFPA-70, 2003 NFPA-101, 2002 NFPA-72 AND THE |
| ELECTRICAL PLANS SHOULD ALSO STATE THE 2004 FBC. |
| |
| 2) NOTE: PLEASE SEE FBC CHAPTER 13. PLEASE SEE |
| 13-415.1.ABC.1.1, .1.2 AND .1.3. |
| PLEASE SEE THERE ARE MANY AREAS WHICH INDICATE SOME |
| SORT OF SYMBOL NEXT TO SWITCH, HOWEVER AS THIS SYMBOL |
| IS NOT LOCATED ON THE SYMBOL SCHEDULE IT IS UNCLEAR |
| WHAT THIS IS FOR REVIEW OF COMPLIANCE WITH ANY LIGHTING |
| CONTROL REQUIREMENTS. |
| PLEASE SEE MANY OTHER AREAS WHICH A SWITCH IS BEING |
| SHOWN AND THE CIRCUIT IS NOT LABELED GOING THROUGH THE |
| LIGHTING CONTROL PANEL. |
| ** PLEASE KNOW THE LIGHTING CONTROL PANEL WILL BE NOTED |
| AS "LCP" IN THE NOTES FORM HERE OUT. |
| PLEASE SPECIFY THE SYSTEM WHICH IS BEING INSTALLED OR |
| SPECIFIED FOR THE SCOPE OF WORK AND INTENDED |
| CONTROL.110.3, 90.7 |
| PLEASE SEE EACH SPACE SHALL CONTAIN A DEVICE WHICH OVER |
| -RIDES A SYSTEM, OR PROVIDES CONTROLS MEANS AS OTHER |
| METHODS LISTED IN 13-415.1.ABC.1.1, .1.2. |
| PLEASE SEE THERE ARE SEVERAL ROOMS WHICH DO NOT |
| INDICATE ANY KIND OF OVER RIDE DEVICE, OCCUPANT SENSOR |
| ETC. |
| PLEASE SEE THE OVER RIDE TYPE DEVICE IS ALSO REQUIRED |
| TO BE LOCATED IN THE AREAS IN WHICH THE OCCUPANT CAN |
| SEE THE LIGHTING BEING CONTROLLED. |
| PLEASE SEE MISSING AUTO SHUT OFF OF PIT LIGHTS. PLEASE |
| BE SURE THE LCP PANEL ONLY CONTROL LIGHTING WHICH |
| SHOULD NOT BE TURNED OFF, :IE: PLEASE CIRCUIT WHICH ARE |
| SHOWN BEING WIRED TO THE LCP'S , HOWEVER PLEASE SEE |
| THERE ARE ALSO EMERGENCY LIGHTING ON THOSE SAME |
| CIRCUITS. PLEASE PROVIDE DETAIL ON THE LCP |
| RISER/DIAGRAM WHERE ALL EXIT AND EMERGENCY LIGHTING IS |
| CIRCUITED AHEAD OF THE LOCAL LIGHTING CONTROL DEVICES. |
| PLEASE SEE MISSING PERFORMANCE CALCULATIONS FOR ALL |
| AREAS. PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED DO |
| NOT INDICATE ANY EXTERIOR LIGHTING; HOWEVER THE PLANS |
| INDICATE LIGHTING IN MANY LOCATIONS. |
| PLEASE SEE ENERGY CALCULATIONS DO NOT INDICATE THE |
| REQUIRED AUTOMATED CONTROLS WHERE LISTING TYPE OF |
| CONTROL. |
| PLEASE SEE 13-415.1.AB.1, 13-415.2, 13-415.2.ABC.1, |
| 13-415.2.ABC.1.3. |
| PLEASE SEE FBC CHAPTER 13, AS THERE ARE MANY AREAS AND |
| ITEMS AS NOTED ABOVE WHICH NEEDS TO BE ADJUSTED. |
| |
| 3) NOTE: PLEASE CORRELATE THE SQ FT ON PERMIT |
| APPLICATION WITH THAT OF THE PLANS. |
| |
| 4) NOTE: PLEASE SEE MISSING NORMAL AND EMERGENCY |
| PHOTO-METRICS IN ALL EGRESS PATH AREAS. PLEASE SEE |
| MISSING STAIR WAYS. PLEASE SEE NFPA-101 2003, 7.8.1.3, |
| AND 7.9.2.2. |
| A) STAIRS REQUIRE A MINIMUM OF 10FT CANDLES UNDER |
| NORMAL AND 1FT CANDLE UNDER EMERGENCY. |
| B) PLEASE SEE THIS IS FOR ALL EXIT STAIRS TO THE PUBLIC |
| RIGHT OF WAY FOR EGRESS PATHS. |
| |
| 5) NOTE: PLEASE SEE NFPA-101 7.8, 7.9, WHICH REQUIRES |
| LIGHTING AND EMERGENCY LIGHTING TO THE PUBLIC RIGHT OF |
| WAY. PLEASE SEE ALL EXTERIOR STAIRS INCLUDING LARGE AND |
| SMALLER STAIRS AREAS WILL REQUIRE SOME SORT OF BATTERY |
| BACK UP FIXTURES WHICH WILL PROVIDE THE MINIMUM FT |
| CANDLES TO THE PUBLIC RIGHT OF WAY, OUT AND AWAY FROM |
| THE BUILDING. |
| PLEASE SEE THIS INCLUDES RAMP AREAS. |
| |
| 5) NOTE: PLEASE SEE ELEVATOR EQUIPMENT ROOMS WHICH WILL |
| REQUIRE A CHANGE IN FIXTURE TYPE OR AN ADDITIONAL |
| FIXTURE. PLEASE SEE 700.16. |
| |
| 6) NOTE: PLEASE SEE 110.26, 408.7, AND 240.24D WHICH DO |
| NOT PERMIT ELECTRICAL PANELS TO BE LOCATED IN STORAGE |
| ROOMS OR CLOSETS. PLEASE ADJUST LOCATIONS OF EQUIPMENT |
| OR CREATE DEDICATED ELECTRICAL ROOMS/CLOSETS AS DONE IN |
| SOME OTHER LOCATIONS ON PLANS. |
| *** PLEASE SEE ACCESS TO ELECTRICAL EQUIPMENT SHOULD |
| ALSO NOT BE THROUGH STORAGE ROOMS. EQUIPMENT SHOULD BE |
| LOCATED IN A MANNER WHICH READY ACCESS CAN BE GRANTED |
| AND QUITE OFTEN STORAGE ROOMS BECOME A LOCATION WHERE |
| THINGS IMPEDE ACCESS AS NEEDED. |
| |
| 7) NOTE: PLEASE SEE POSSIBLE BUILDING OR FIRE REVIEW |
| COMMENTS WITH RESPECT TO STAIRWAY #4.IT IS UNCLEAR AS |
| THIS SEEMS TO EXIT OCCUPANTS BACK INTO THE BUILDING. |
| THERE ARE SOME INSTANCES WHERE THIS IS PERMITTED; |
| HOWEVER DEPENDING ON POSSIBLE COMMENTS THIS WILL AFFECT |
| THE ELECTRICAL PLANS AND LAYOUT IF ANY CHANGES ARE |
| NEEDED. THIS IS ONLY A NOTE AT THIS TIME. |
| |
| 8) NOTE: PLEASE BE SURE ALL FIXTURES ARE IDENTIFIED BY |
| THEIR FIXTURE DESIGNATIONS. PLEASE SEE SOME FIXTURES |
| ARE MISSING THIS. |
| PLEASE SEE OTHER FIXTURES WHICH ARE INDICATED AS "UT", |
| HOWEVER THIS FIXTURE IS NOT LOCATED ON FIXTURE |
| SCHEDULED AND THE SYMBOL AROUND THE FIXTURE IS NOT |
| SIMILAR AND COULD NOT BE LOCATE ANY OTHER DESIGNATION |
| OR REFERENCE ON PLANS. PLEASE CLARIFY THIS? |
| FBC 106.1.2 ADMIN SECTION. |
| |
| 9) NOTE: PLEASE SEE THERE ARE SEVERAL CIRCUITS ON PLANS |
| WHICH DO NOT SEEM TO BE SHOWN GOING THROUGH ANY OF THE |
| LCP'S? |
| PLEASE PROVIDE A COMPLETE LCP SCHEDULE FOR ALL |
| CIRCUITS. |
| 13-415.1.ABC.1.1, .1.2, AND .1.3. |
| |
| 10) NOTE: PLEASE PROVIDE MORE INFORMATION ON MAIN 1 OF |
| 2. PLEASE INDICATE SIZE, VOLTAGEETC. |
| 230, 240, 110.3, 90.7 |
| FBC 106.1.2 |
| |
| 11) NOTE: PLEASE SEE MISSING AN EQUIPMENT GROUNDING |
| CONDUCTOR FROM THIS MAIN 1 OF 2 TO THE EXISTING MDP |
| PANEL. |
| IT IS NOTED THAT THE SYSTEM SHALL SEPARATE ALL NEUTRAL |
| AND GROUND CONNECTIONS AT THE EXISTING MDP. 250.24B, |
| 250.110, 250.122 |
| FBC 106.1.2 ADMIN SECTION. |
| |
| 12) NOTE: PLEASE SEE AN "EQUIPMENT GROUNDING CONDUCTOR" |
| IS BEING SHOWN FROM THE FPL TRANSFORMER TO THE NEW MAIN |
| 2 OF 2? PLEASE SEE 250.6, AND 250.24 AS EQUIPMENT |
| GROUNDING CONDUCTORS ARE ONLY INSTALLED AFTER THE FIRST |
| MEANS OF DISCONNECT. |
| |
| 13) NOTE: PLEASE INDICATE ALL CONTINUOUS LOADS AND THE |
| LARGEST MOTOR LOADS ON EACH PANEL AND SERVICE AT 125%. |
| PLEASE SEE NO LOAD CALCULATIONS OR LOAD SUMMARY COULD |
| BE LOCATED. |
| 220.3, 220.10, 220.11, 220.13, 215.3 AND 230.42 ETC. |
| FBC ADMIN SECTION 106.3.5.1.2 |
| |
| 14) NOTE: PLEASE SEE PANEL "L2 AA" IS BEING SHOWN FED |
| FROM MULTIPLE PANELS. PLEASE SEE THIS PANEL IS SHOWN |
| FED FROM BOTH "DP2A" AND "DP2B". PLEASE CORRELATE AND |
| ADJUST. |
| PLEASE SEE RISER AS THE RISER SHOWS THIS PANEL ONLY |
| BEING FED FROM DP2A. |
| FBC 106.1.2. |
| |
| 15) NOTE: PLEASE SEE PANEL "DP1B" WHICH INDICATES A |
| FEED TO A PANEL "L1BB" , YET NO PANEL SCHEDULE COULD BE |
| LOCATED ON THE PLANS SUBMITTED. |
| FBC 106.1.2 |
| |
| 16) NOTE: PLEASE SEE A PANEL SCHEDULE FOR "L3AB" WAS |
| SUBMITTED ON PANEL SCHEDULES, HOWEVER COULD NOT LOCATED |
| ON ANY OTHER OF THE PANEL SCHEDULE WHERE THIS IS FED |
| FROM OR COULD NOT LOCATED THIS ON THE ELECTRICAL RISER |
| DIAGRAM EITHER.PLEASE CLARIFY. |
| FBC 106.1.2, 106.3.5.1.2 |
| |
| 17) NOTE: PLEASE BE SURE TO GO THROUGH PLANS AND |
| CORRELATE ALL PANELS SHOWN ON PLANS WITH THE RISER |
| DIAGRAM AND PANEL SCHEDULES SUBMITTED. |
| FBC 106.1.2, 106.3.5.1.2 |
| |
| 18) NOTE: PLEASE SEE INDICATE ANY FIRE SPRINKLER WATER |
| LINE AS PART OF THE GROUNDING ELECTRODE SYSTEM. |
| 250.106 |
| |
| 19) NOTE: PLEASE SEE FBC 2004 11-4.28.2 AND |
| 11-4.28.3(4) FOR ALL AUDIBLE AND VISUAL DEVICES. PLEASE |
| SEE 11-4.28.1 FOR LOCATION REQUIREMENTS. PLEASE BE SURE |
| FA PLANS INDICATE ALL THE MINIMUM LEVELS PER ADA AND |
| PLACES NOTES ALSO FOR FBC SECTIONS AS GIVEN. |
| |
| ** PLEASE KNOW AS THERE ARE MANY ITEMS NOT SHOWN OR |
| MISSING, THERE MAY BE COMMENTS ON THE FOLLOWING |
| REVIEW. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| **PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |