Plan Review Notes
Plan Review Notes For Permit 06110152
Permit Number 06110152
Review Stop E
Sequence Number 1
Notes
Date Text
2006-11-28 07:52:39*** UNSAT ***
  
 1) NOTE: PLEASE BE PLANS REFLECT THE FOLLOWING CODES AT
 A MINIMUM.
 2002 NFPA-70, 2003 NFPA-101, 2002 NFPA-72 AND THE
 ELECTRICAL PLANS SHOULD ALSO STATE THE 2004 FBC.
  
 2) NOTE: PLEASE SEE FBC CHAPTER 13. PLEASE SEE
 13-415.1.ABC.1.1, .1.2 AND .1.3.
 PLEASE SEE THERE ARE MANY AREAS WHICH INDICATE SOME
 SORT OF SYMBOL NEXT TO SWITCH, HOWEVER AS THIS SYMBOL
 IS NOT LOCATED ON THE SYMBOL SCHEDULE IT IS UNCLEAR
 WHAT THIS IS FOR REVIEW OF COMPLIANCE WITH ANY LIGHTING
 CONTROL REQUIREMENTS.
 PLEASE SEE MANY OTHER AREAS WHICH A SWITCH IS BEING
 SHOWN AND THE CIRCUIT IS NOT LABELED GOING THROUGH THE
 LIGHTING CONTROL PANEL.
 ** PLEASE KNOW THE LIGHTING CONTROL PANEL WILL BE NOTED
 AS "LCP" IN THE NOTES FORM HERE OUT.
 PLEASE SPECIFY THE SYSTEM WHICH IS BEING INSTALLED OR
 SPECIFIED FOR THE SCOPE OF WORK AND INTENDED
 CONTROL.110.3, 90.7
 PLEASE SEE EACH SPACE SHALL CONTAIN A DEVICE WHICH OVER
 -RIDES A SYSTEM, OR PROVIDES CONTROLS MEANS AS OTHER
 METHODS LISTED IN 13-415.1.ABC.1.1, .1.2.
 PLEASE SEE THERE ARE SEVERAL ROOMS WHICH DO NOT
 INDICATE ANY KIND OF OVER RIDE DEVICE, OCCUPANT SENSOR
 ETC.
 PLEASE SEE THE OVER RIDE TYPE DEVICE IS ALSO REQUIRED
 TO BE LOCATED IN THE AREAS IN WHICH THE OCCUPANT CAN
 SEE THE LIGHTING BEING CONTROLLED.
 PLEASE SEE MISSING AUTO SHUT OFF OF PIT LIGHTS. PLEASE
 BE SURE THE LCP PANEL ONLY CONTROL LIGHTING WHICH
 SHOULD NOT BE TURNED OFF, :IE: PLEASE CIRCUIT WHICH ARE
 SHOWN BEING WIRED TO THE LCP'S , HOWEVER PLEASE SEE
 THERE ARE ALSO EMERGENCY LIGHTING ON THOSE SAME
 CIRCUITS. PLEASE PROVIDE DETAIL ON THE LCP
 RISER/DIAGRAM WHERE ALL EXIT AND EMERGENCY LIGHTING IS
 CIRCUITED AHEAD OF THE LOCAL LIGHTING CONTROL DEVICES.
 PLEASE SEE MISSING PERFORMANCE CALCULATIONS FOR ALL
 AREAS. PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED DO
 NOT INDICATE ANY EXTERIOR LIGHTING; HOWEVER THE PLANS
 INDICATE LIGHTING IN MANY LOCATIONS.
 PLEASE SEE ENERGY CALCULATIONS DO NOT INDICATE THE
 REQUIRED AUTOMATED CONTROLS WHERE LISTING TYPE OF
 CONTROL.
 PLEASE SEE 13-415.1.AB.1, 13-415.2, 13-415.2.ABC.1,
 13-415.2.ABC.1.3.
 PLEASE SEE FBC CHAPTER 13, AS THERE ARE MANY AREAS AND
 ITEMS AS NOTED ABOVE WHICH NEEDS TO BE ADJUSTED.
  
 3) NOTE: PLEASE CORRELATE THE SQ FT ON PERMIT
 APPLICATION WITH THAT OF THE PLANS.
  
 4) NOTE: PLEASE SEE MISSING NORMAL AND EMERGENCY
 PHOTO-METRICS IN ALL EGRESS PATH AREAS. PLEASE SEE
 MISSING STAIR WAYS. PLEASE SEE NFPA-101 2003, 7.8.1.3,
 AND 7.9.2.2.
 A) STAIRS REQUIRE A MINIMUM OF 10FT CANDLES UNDER
 NORMAL AND 1FT CANDLE UNDER EMERGENCY.
 B) PLEASE SEE THIS IS FOR ALL EXIT STAIRS TO THE PUBLIC
 RIGHT OF WAY FOR EGRESS PATHS.
  
 5) NOTE: PLEASE SEE NFPA-101 7.8, 7.9, WHICH REQUIRES
 LIGHTING AND EMERGENCY LIGHTING TO THE PUBLIC RIGHT OF
 WAY. PLEASE SEE ALL EXTERIOR STAIRS INCLUDING LARGE AND
 SMALLER STAIRS AREAS WILL REQUIRE SOME SORT OF BATTERY
 BACK UP FIXTURES WHICH WILL PROVIDE THE MINIMUM FT
 CANDLES TO THE PUBLIC RIGHT OF WAY, OUT AND AWAY FROM
 THE BUILDING.
 PLEASE SEE THIS INCLUDES RAMP AREAS.
  
 5) NOTE: PLEASE SEE ELEVATOR EQUIPMENT ROOMS WHICH WILL
 REQUIRE A CHANGE IN FIXTURE TYPE OR AN ADDITIONAL
 FIXTURE. PLEASE SEE 700.16.
  
 6) NOTE: PLEASE SEE 110.26, 408.7, AND 240.24D WHICH DO
 NOT PERMIT ELECTRICAL PANELS TO BE LOCATED IN STORAGE
 ROOMS OR CLOSETS. PLEASE ADJUST LOCATIONS OF EQUIPMENT
 OR CREATE DEDICATED ELECTRICAL ROOMS/CLOSETS AS DONE IN
 SOME OTHER LOCATIONS ON PLANS.
 *** PLEASE SEE ACCESS TO ELECTRICAL EQUIPMENT SHOULD
 ALSO NOT BE THROUGH STORAGE ROOMS. EQUIPMENT SHOULD BE
 LOCATED IN A MANNER WHICH READY ACCESS CAN BE GRANTED
 AND QUITE OFTEN STORAGE ROOMS BECOME A LOCATION WHERE
 THINGS IMPEDE ACCESS AS NEEDED.
  
 7) NOTE: PLEASE SEE POSSIBLE BUILDING OR FIRE REVIEW
 COMMENTS WITH RESPECT TO STAIRWAY #4.IT IS UNCLEAR AS
 THIS SEEMS TO EXIT OCCUPANTS BACK INTO THE BUILDING.
 THERE ARE SOME INSTANCES WHERE THIS IS PERMITTED;
 HOWEVER DEPENDING ON POSSIBLE COMMENTS THIS WILL AFFECT
 THE ELECTRICAL PLANS AND LAYOUT IF ANY CHANGES ARE
 NEEDED. THIS IS ONLY A NOTE AT THIS TIME.
  
 8) NOTE: PLEASE BE SURE ALL FIXTURES ARE IDENTIFIED BY
 THEIR FIXTURE DESIGNATIONS. PLEASE SEE SOME FIXTURES
 ARE MISSING THIS.
 PLEASE SEE OTHER FIXTURES WHICH ARE INDICATED AS "UT",
 HOWEVER THIS FIXTURE IS NOT LOCATED ON FIXTURE
 SCHEDULED AND THE SYMBOL AROUND THE FIXTURE IS NOT
 SIMILAR AND COULD NOT BE LOCATE ANY OTHER DESIGNATION
 OR REFERENCE ON PLANS. PLEASE CLARIFY THIS?
 FBC 106.1.2 ADMIN SECTION.
  
 9) NOTE: PLEASE SEE THERE ARE SEVERAL CIRCUITS ON PLANS
 WHICH DO NOT SEEM TO BE SHOWN GOING THROUGH ANY OF THE
 LCP'S?
 PLEASE PROVIDE A COMPLETE LCP SCHEDULE FOR ALL
 CIRCUITS.
 13-415.1.ABC.1.1, .1.2, AND .1.3.
  
 10) NOTE: PLEASE PROVIDE MORE INFORMATION ON MAIN 1 OF
 2. PLEASE INDICATE SIZE, VOLTAGEETC.
 230, 240, 110.3, 90.7
 FBC 106.1.2
  
 11) NOTE: PLEASE SEE MISSING AN EQUIPMENT GROUNDING
 CONDUCTOR FROM THIS MAIN 1 OF 2 TO THE EXISTING MDP
 PANEL.
 IT IS NOTED THAT THE SYSTEM SHALL SEPARATE ALL NEUTRAL
 AND GROUND CONNECTIONS AT THE EXISTING MDP. 250.24B,
 250.110, 250.122
 FBC 106.1.2 ADMIN SECTION.
  
 12) NOTE: PLEASE SEE AN "EQUIPMENT GROUNDING CONDUCTOR"
 IS BEING SHOWN FROM THE FPL TRANSFORMER TO THE NEW MAIN
 2 OF 2? PLEASE SEE 250.6, AND 250.24 AS EQUIPMENT
 GROUNDING CONDUCTORS ARE ONLY INSTALLED AFTER THE FIRST
 MEANS OF DISCONNECT.
  
 13) NOTE: PLEASE INDICATE ALL CONTINUOUS LOADS AND THE
 LARGEST MOTOR LOADS ON EACH PANEL AND SERVICE AT 125%.
 PLEASE SEE NO LOAD CALCULATIONS OR LOAD SUMMARY COULD
 BE LOCATED.
 220.3, 220.10, 220.11, 220.13, 215.3 AND 230.42 ETC.
 FBC ADMIN SECTION 106.3.5.1.2
  
 14) NOTE: PLEASE SEE PANEL "L2 AA" IS BEING SHOWN FED
 FROM MULTIPLE PANELS. PLEASE SEE THIS PANEL IS SHOWN
 FED FROM BOTH "DP2A" AND "DP2B". PLEASE CORRELATE AND
 ADJUST.
 PLEASE SEE RISER AS THE RISER SHOWS THIS PANEL ONLY
 BEING FED FROM DP2A.
 FBC 106.1.2.
  
 15) NOTE: PLEASE SEE PANEL "DP1B" WHICH INDICATES A
 FEED TO A PANEL "L1BB" , YET NO PANEL SCHEDULE COULD BE
 LOCATED ON THE PLANS SUBMITTED.
 FBC 106.1.2
  
 16) NOTE: PLEASE SEE A PANEL SCHEDULE FOR "L3AB" WAS
 SUBMITTED ON PANEL SCHEDULES, HOWEVER COULD NOT LOCATED
 ON ANY OTHER OF THE PANEL SCHEDULE WHERE THIS IS FED
 FROM OR COULD NOT LOCATED THIS ON THE ELECTRICAL RISER
 DIAGRAM EITHER.PLEASE CLARIFY.
 FBC 106.1.2, 106.3.5.1.2
  
 17) NOTE: PLEASE BE SURE TO GO THROUGH PLANS AND
 CORRELATE ALL PANELS SHOWN ON PLANS WITH THE RISER
 DIAGRAM AND PANEL SCHEDULES SUBMITTED.
 FBC 106.1.2, 106.3.5.1.2
  
 18) NOTE: PLEASE SEE INDICATE ANY FIRE SPRINKLER WATER
 LINE AS PART OF THE GROUNDING ELECTRODE SYSTEM.
 250.106
  
 19) NOTE: PLEASE SEE FBC 2004 11-4.28.2 AND
 11-4.28.3(4) FOR ALL AUDIBLE AND VISUAL DEVICES. PLEASE
 SEE 11-4.28.1 FOR LOCATION REQUIREMENTS. PLEASE BE SURE
 FA PLANS INDICATE ALL THE MINIMUM LEVELS PER ADA AND
 PLACES NOTES ALSO FOR FBC SECTIONS AS GIVEN.
  
 ** PLEASE KNOW AS THERE ARE MANY ITEMS NOT SHOWN OR
 MISSING, THERE MAY BE COMMENTS ON THE FOLLOWING
 REVIEW.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 **PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]