Plan Review Notes
Plan Review Notes For Permit 06110105
Permit Number 06110105
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-11-20 13:12:57****DENIED****
  
  
  
 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2.COMPLIANCE WITH FLORIDA FIRE PREVENTION CODE 2004
 EDITION SHALL BE REFERENCED.
  
 3.PLEASE INDICATE/DISPLAY/SHOW THE LOCATION OF ANY
 FIRE PROTECTION SYSTEM DEVICES INCLUDING FIRE
 EXTINGUISHER(S).HOW WILL THEY BE AFFECTED BY THE
 SCOPE OF THE WORK?
  
 4.IF THE FIRE ALARM AND (OR) FIRE SRINKLER SYSTEM ARE
 TO BE MODIFIED DUE TO THE SCOPE OF WORK, SEPARATE PLANS
 AND PERMIT ARE REQUIRED.
  
 5.PLEASE EXPLAIN THE LACK OF EXIT LIGHTS IN THE AREA
 OF DOORS LEADING TO THE COMMON CORRIDOR FROM EXISTING
 RECEPTION [605] AND OPEN OFFICE [622].
  
 6.PLEASE PROVIDE INTERIOR FINISH CLASSIFICATION FOR
 WALLS AND CEILING.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING,
 INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH
 ITEM WAS ADDRESSED
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  