Plan Review Notes For Permit 06110105 |
Permit Number |
06110105 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-11-20 13:12:57 | ****DENIED**** | | | | | | | | 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | 2.COMPLIANCE WITH FLORIDA FIRE PREVENTION CODE 2004 | | EDITION SHALL BE REFERENCED. | | | | 3.PLEASE INDICATE/DISPLAY/SHOW THE LOCATION OF ANY | | FIRE PROTECTION SYSTEM DEVICES INCLUDING FIRE | | EXTINGUISHER(S).HOW WILL THEY BE AFFECTED BY THE | | SCOPE OF THE WORK? | | | | 4.IF THE FIRE ALARM AND (OR) FIRE SRINKLER SYSTEM ARE | | TO BE MODIFIED DUE TO THE SCOPE OF WORK, SEPARATE PLANS | | AND PERMIT ARE REQUIRED. | | | | 5.PLEASE EXPLAIN THE LACK OF EXIT LIGHTS IN THE AREA | | OF DOORS LEADING TO THE COMMON CORRIDOR FROM EXISTING | | RECEPTION [605] AND OPEN OFFICE [622]. | | | | 6.PLEASE PROVIDE INTERIOR FINISH CLASSIFICATION FOR | | WALLS AND CEILING. | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING, | | INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH | | ITEM WAS ADDRESSED | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 | | |
|