Plan Review Notes For Permit 06110087 |
Permit Number |
06110087 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-11-17 13:54:43 | DENIED: | | 1.INSTALLATION OF FUEL TANKS NEED APPROVAL FROM | | DEPARTMENT OF EVIRONMENTAL REGULATION.PLEASE SUBMIT | | PLANS AT 3323 BELVEDERE RD, BUILDING #502, TO THE | | ATTENTION OF CHIP GREEN.YOU MAY CONTACT MR. GREEN AT | | 233-2400 PRIOR TO SUBMITTAL OF PLANS.PLEASE RESUBMIT | | PLANS FOR REVIEW AFTER APPROVAL FROM DERM. | | | | 2.PLEASE PROVIDE ANCHORING DETAIL SHOW COMPLIANCE | | WITH 2004 FMC 301.13. | | | | 3.PLEASE INDICATE LOCATION OF FUEL TANKS IN RELATION | | TO BUILDINGS, WINDOWS, DOORS FRESH AIR INTAKES & | | PROPERTY LINES.SURVEY PROVIDED INDICATES PROPOSED | | TANKS ON THE RAISED CURB. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS | | AT (561)805-6719 OR E-MAIL [email protected]. |
|