Plan Review Notes
Plan Review Notes For Permit 06110087
Permit Number 06110087
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-12-27 15:37:01*****DENIED*****
  
  
  
 1.THE INSTALLATION OF FUEL TANKS AND REFUELING
 PROCESSES SHALL COMPLY WITH NFPA 30.
  
 2.THE SCOPE OF WORK SHALL NOT HINDER OR INTERFERE
 WITH EMERGENCY RESPONSE ACCESS TO THE SAID PROPERTY OR
 VICINITY THEROF.
  
 3.PROVIDE THE DISTANCE OF THE PROPOSED TANK TO THE
 BUILDING'S WINDOWS, DOORS, OPENINGS, ETC.
  
 4.PROVIDE FIRE PROTECTION APPLIANCE LOCATIONS I.E.
 FIRE EXTINGUISHER(S) EMERGENCY SHUT-OFF VALVE(S), ETC.
  
 5.HOW WILL VEHICLE IMPACT PROTECTION BE
 ACCOMPLISHED.
  
 6.PROVIDE ANY OTHER INFORMATION THAT MAY
 INSTRUMENTAL IN THIS FIRE PLAN REVIEW.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETEER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  