Date |
Text |
2006-11-17 12:55:19 | **** UNSAT ***** |
| |
| 1) NOTE: PLEASE SEE AS THE MAJORITY OF THE INSTALLATION |
| OF THE WORK INVOLVED IS NOT ELECTRICAL. PLEASE SEE |
| SCOPE APPEARS TO BE OUT OF THAT OF AN ELECTRICAL |
| CONTRACTOR. PLEASE KNOW A CONTRACTOR LICENSED TO |
| INSTALL THIS SIZE FUEL TANK CAN BE THE PRIME |
| CONTRACTOR, AND THE ELECTRICAL CAN BE THE SUB FOR THE |
| ELECTRICAL HOOK UP. |
| ** PLEASE SEE COMMENTS FROM OTHER TRADES WITH RESPECT |
| TO WHO CAN INSTALL ETC. |
| PLEASE SEE FS 489. |
| |
| 2) NOTE: PLEASE PROVIDE A COMPLETE LAYOUT FOR THE |
| ENTIRE INSTALLATION OF THE ELECTRICAL SYSTEM INCLUDING |
| ALL HAZARDOUS LOCATIONS, CLEARANCES HEIGHTS/ELEVATIONS |
| ETC. |
| PLEASE SEE FUEL DISPENSING IN THE NEC,514. |
| PLEASE ALSO SEE COMMENTS FROM OTHER TRADES AS THIS IS A |
| 750 GAL UNIT. PLEASE SEE MINIMUM CLEARANCES REQUIRED |
| FROM BUILDINGS ETC WHICH WILL BE IN OTHER REVIEW |
| COMMENTS. |
| |
| 3) NOTE: PLEASE KNOW, EVEN WHEN PLANS ARE NOT REQUIRED |
| TO BE DONE BY ARCHITECT OR ENGINEER, THEY ARE REQUIRED |
| TO CONTAIN A PRINTED NAME AND SIGNATURE FOR THE |
| DESIGNS. |
| PLEASE KNOW BASED ON SCOPE OF WORK AND REQUIREMENTS FOR |
| WIND LOADS AND THE SPECIALIZED REQUIREMENTS SHOWN, |
| PLANS WILL BE REQUIRED TO BE DONE BY AN ARCHITECT OR |
| ENGINEER. |
| FBC ADMIN SECTION 106.3.1.2(5). |
| PLEASE SEE COMMENTS FROM OTHER REVIEWER(S) AS THESE |
| WILL GREATLY AFFECT THE PLANS SUBMITTED. |
| |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| **PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. |
| **IF THERE ARE ANY QUESTIONS, COMMENTSOR IF ANY OF |
| THE NOTES TYPEDWHICH ARE UNCLEAR IN ANY WAY, PLEASE |
| DO NOT HESITATEIN CONTACTING THIS REVIEWER. |
| |
| |
| |
| |