Permit Number 06110087
Review Stop E
Sequence Number 1
Notes
Date Text
2006-11-17 12:55:19**** UNSAT *****
  
 1) NOTE: PLEASE SEE AS THE MAJORITY OF THE INSTALLATION
 OF THE WORK INVOLVED IS NOT ELECTRICAL. PLEASE SEE
 SCOPE APPEARS TO BE OUT OF THAT OF AN ELECTRICAL
 CONTRACTOR. PLEASE KNOW A CONTRACTOR LICENSED TO
 INSTALL THIS SIZE FUEL TANK CAN BE THE PRIME
 CONTRACTOR, AND THE ELECTRICAL CAN BE THE SUB FOR THE
 ELECTRICAL HOOK UP.
 ** PLEASE SEE COMMENTS FROM OTHER TRADES WITH RESPECT
 TO WHO CAN INSTALL ETC.
 PLEASE SEE FS 489.
  
 2) NOTE: PLEASE PROVIDE A COMPLETE LAYOUT FOR THE
 ENTIRE INSTALLATION OF THE ELECTRICAL SYSTEM INCLUDING
 ALL HAZARDOUS LOCATIONS, CLEARANCES HEIGHTS/ELEVATIONS
 ETC.
 PLEASE SEE FUEL DISPENSING IN THE NEC,514.
 PLEASE ALSO SEE COMMENTS FROM OTHER TRADES AS THIS IS A
 750 GAL UNIT. PLEASE SEE MINIMUM CLEARANCES REQUIRED
 FROM BUILDINGS ETC WHICH WILL BE IN OTHER REVIEW
 COMMENTS.
  
 3) NOTE: PLEASE KNOW, EVEN WHEN PLANS ARE NOT REQUIRED
 TO BE DONE BY ARCHITECT OR ENGINEER, THEY ARE REQUIRED
 TO CONTAIN A PRINTED NAME AND SIGNATURE FOR THE
 DESIGNS.
 PLEASE KNOW BASED ON SCOPE OF WORK AND REQUIREMENTS FOR
 WIND LOADS AND THE SPECIALIZED REQUIREMENTS SHOWN,
 PLANS WILL BE REQUIRED TO BE DONE BY AN ARCHITECT OR
 ENGINEER.
 FBC ADMIN SECTION 106.3.1.2(5).
 PLEASE SEE COMMENTS FROM OTHER REVIEWER(S) AS THESE
 WILL GREATLY AFFECT THE PLANS SUBMITTED.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 **PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW.
 **IF THERE ARE ANY QUESTIONS, COMMENTSOR IF ANY OF
 THE NOTES TYPEDWHICH ARE UNCLEAR IN ANY WAY, PLEASE
 DO NOT HESITATEIN CONTACTING THIS REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  