Plan Review Notes For Permit 06101150 |
Permit Number |
06101150 |
|
Review Stop |
Z |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-11-07 15:25:39 | DENIED, | | 1. THE SUBMITTED SURVEY IS BEYOND THE 1 YEAR | | REQUIREMENT FOR SURVEYS TO BE USED FOR REVIEW OF A | | PROPOSED WORK. SURVEY SUBMITTED IS 1955 | | 2. PLEASE SUBMIT 2 COPIES OF CURRENT SURVEYS SHOWING | | THE LOT DIMENSION, SETBACKS OF STRUCTURE (CLEARLY) WITH | | THE PROPOSED WORK. | | | | NOTE: SEC 94-303 MECHANICAL/POOL EQUIPMENT/GENERATOR | | MAY NOT PROJECT MORE THAN FOUR FEET INTO A SETBACK. | | | | 3. THE PROPOSED GENERATOR SHALL NOT BE CLOSER THAN | | 5.4FT FROM REAR PROPERTY LINE. | | | | MICHELLE MCLEAN | | ZONING TECHNICIAN | | 805-6720 | | |
|