2006-11-28 09:09:37UNSAT
 REFERENCE: FBC-2004 FUEL GAS
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR GAS PLAN
 REVIEW TO MEET CODE COMPLIANCE:
  
 1. A GAS PERMIT CAN NOT BE ISSUED UNTIL
 A GEN/RES PERMIT APPLICATION HAS BEEN
 APPROVED BY ZONING FOR
 THE GENERATOR LOCATION.
 NOTE: PLEASE BE AWARE THAT IF GENERATOR LOCATION
 CHANGES BECAUSE OF ZONING ISSUES THE GAS DRAWING MUST
 CORRELATE WITH THESE CHANGES.
  
 2. PLEASE PROVIDE MANUFACTURER INSTALLATION
 INSTRUCTIONS OF GENERATOR REGAURDING CLEARENCES TO
 STRUCTURES.
  
 3. PLEASE PROVIDE A CURRENT SURVEY (2 COPIES) WITH
 DIMENSIONS OF PROPOSED GENERATOR TO STRUCTURES AND
 PROPERTY LINES.
  
 4. PLEASE INDICATE THE TYPE OF GAS, (LP OR NATURAL) ON
 THE GAS ISOMETRIC DRAWINGS.
  
 5. PLEASE BE AWARE THAT IF THE GAS SYSTEM IS NATURAL
 GAS FOR THE PROPOSED GENERATOR THAT THE BTU LOAD
 INDICATED ON THE GAS ISOMETRIC DRAWING IS WRONG, IT
 SHOULD BE 723,000 NOT 698,000 PER THE SUBMITTED
 MANUFACTURER SPECIFICATIONS. PLEASE CORRECT FOR THE
 RESUBMITTAL.
  
 6. NOTE: PLEASE BE AWARE THAT A GAS PERMIT IS REQUIRED
 FOR THE PROPOSED GENERATOR AND THAT THERE WAS NOT A GAS
 CONTRACTOR SIGNED ON THE GEN/RES PERMIT APPLICATION
 EVEN THOUGH THERE WAS A GAS ISOMETRIC DRAWING
 SUBMITTED. PLEASE CLARIFY THIS ON THE RESUBMITTAL.
  
  
 END OF COMMENTS:
  