Plan Review Notes
Plan Review Notes For Permit 06101122
Permit Number 06101122
Review Stop M
Sequence Number 8
Notes
Date Text
2008-12-20 13:52:08 
 ACTION: DENIED
  
 REVIEWED FOR COMPLIANCE WITH THE FOLLOWING:
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 TWO COPIES OF REVISED "A-2" WERE SUBMITTED FOR REVIEW.
 A REVIEW OF THESE PLANS CAN NOT BE COMPLETED AT THIS
 TIME FOR THE FOLLOWING REASONS:
  
 1. THE TWO COPIES SHOW DUCT DESIGNS WHICH DO NOT MATCH.
 EXAMPLE: ONE COPY SHOWS TWO SUPPLY DROPS IN THE KITCHEN
 WHILE THE OTHER COPY SHOWS NONE. EXAMPLE: THE HALF-BATH
 NEAR BEDROOM #3 SHOWS AN EXHAUST FAN ON ONE COPY BUT
 NOT THE OTHER. THESE ARE GIVEN AS EXAMPLES AND ARE NOT
 INTENDED TO BE AN EXHAUSTIVE LIST. CHECK ALL ASPECTS OF
 BOTH COPIES AND MAKE NECESSARY CORRECTIONS PRIOR TO
 RESUBMITTING (PERHAPS DRAWING THE PLAN ONCE AND COPYING
 IT RATHER THAN DRAWING IT TWICE WILL RESOLVE THIS
 PROBLEM). PLEASE PROVIDED TWO IDENTICAL PLANS SO ONE
 CAN BE INCORPORATED INTO THE PERMIT SET OF PLANS AND
 THE OTHER CAN BE USED IN THE FIELD FOR INSPECTIONS.
 FBCB 106.1.3.
  
 2. SEVERAL DUCTS ARE MISSING SIZES ON PLANS. THIS
 CONDITION VARIES FROM ONE PLAN TO THE OTHER. PLEASE
 PROVIDED TWO IDENTICAL PLANS SO ONE CAN BE INCORPORATED
 INTO THE PERMIT SET OF PLANS AND THE OTHER CAN BE USED
 IN THE FIELD FOR INSPECTIONS. FBCB 106.1.3.
  
 3. SOME OF THE DUCT SIZES ARE NOT LEGIBLE. PROVIDE
 PLANS OF SUFFICIENT CLARITY TO DESCRIBE THE SCOPE AND
 NATURE OF WORK PROPOSED IN ACCORDANCE WITH FBCB
 106.1.1.
  