2008-12-20 13:52:08 | |
| ACTION: DENIED |
| |
| REVIEWED FOR COMPLIANCE WITH THE FOLLOWING: |
| FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS |
| FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| |
| TWO COPIES OF REVISED "A-2" WERE SUBMITTED FOR REVIEW. |
| A REVIEW OF THESE PLANS CAN NOT BE COMPLETED AT THIS |
| TIME FOR THE FOLLOWING REASONS: |
| |
| 1. THE TWO COPIES SHOW DUCT DESIGNS WHICH DO NOT MATCH. |
| EXAMPLE: ONE COPY SHOWS TWO SUPPLY DROPS IN THE KITCHEN |
| WHILE THE OTHER COPY SHOWS NONE. EXAMPLE: THE HALF-BATH |
| NEAR BEDROOM #3 SHOWS AN EXHAUST FAN ON ONE COPY BUT |
| NOT THE OTHER. THESE ARE GIVEN AS EXAMPLES AND ARE NOT |
| INTENDED TO BE AN EXHAUSTIVE LIST. CHECK ALL ASPECTS OF |
| BOTH COPIES AND MAKE NECESSARY CORRECTIONS PRIOR TO |
| RESUBMITTING (PERHAPS DRAWING THE PLAN ONCE AND COPYING |
| IT RATHER THAN DRAWING IT TWICE WILL RESOLVE THIS |
| PROBLEM). PLEASE PROVIDED TWO IDENTICAL PLANS SO ONE |
| CAN BE INCORPORATED INTO THE PERMIT SET OF PLANS AND |
| THE OTHER CAN BE USED IN THE FIELD FOR INSPECTIONS. |
| FBCB 106.1.3. |
| |
| 2. SEVERAL DUCTS ARE MISSING SIZES ON PLANS. THIS |
| CONDITION VARIES FROM ONE PLAN TO THE OTHER. PLEASE |
| PROVIDED TWO IDENTICAL PLANS SO ONE CAN BE INCORPORATED |
| INTO THE PERMIT SET OF PLANS AND THE OTHER CAN BE USED |
| IN THE FIELD FOR INSPECTIONS. FBCB 106.1.3. |
| |
| 3. SOME OF THE DUCT SIZES ARE NOT LEGIBLE. PROVIDE |
| PLANS OF SUFFICIENT CLARITY TO DESCRIBE THE SCOPE AND |
| NATURE OF WORK PROPOSED IN ACCORDANCE WITH FBCB |
| 106.1.1. |
| |