2008-10-06 10:05:29 | RESIDENTIAL (R3) REVISION BUILDING REVIEW THIRD |
| CHECKLIST: |
| |
| OLD COMMENT: |
| 1- STAIR DETAIL ON SHEET D-1 CALLS FOR 18 RISERS, WHILE |
| FLOOR PLANS SHOW 17 RISERS. REVISE AS REQUIRED TO MATCH |
| AND SHOW COMPLIANCE WITH SEC. R311.5.3.2 OF 2004 |
| FLORIDA RESIDENTIAL CODE. (REPEAT COMMENT). |
| |
| ***COMMENT BASED ON RESPONSE: |
| NOW STAIRS SHOW 19 RISERS WITH 7 3/4" RISERS AND 10" |
| TREADS. THIS STAIR RISER/TREAD RATION DOESN'T COMPLY |
| WITH SEC. R311.5.3.2 OF 2004 RESIDENTIAL CODE. REVISE |
| AS REQUIRED TO COMPLY WITH THIS CODE SECTION. |
| |
| OLD COMMENT: |
| 2- ENGINEER TO REVISE RAS 117 CALCULATIONS. (REPEAT |
| COMMENT). FASTENERS CAN'T BE SPACED LESS THAN 4"O.C.. |
| SEE SEC. 8.1 OF RAS 117. 2 ROWS IN THE LAP WILL HAVE |
| THE FASTENERS SPACED AT LESS THAN 4" O.C.. |
| PROVIDE CALCULATIONS SHOWING HOW THE 2 ROWS AT LAP AND |
| THE 3 ROWS IN THE CENTER OF THE SHEET WILL SATISFY THE |
| NAIL ENHANCEMENT CALCULATIONS TO RESIST THE |
| CALCULATED DESIGN PRESSURES. SEC. 106.1.2 CITY |
| AMENDMENTS TO FBC 2004 TO VERIFY COMPLIANCE WITH THE |
| DESIGN PRESSURES OF SEC. R301 OF 2004 FLORIDA |
| RESIDENTIAL CODE. |
| |
| ***COMMENT BASED ON RESPONSE: |
| ENGINEER STILL SHOWS TWO ROWS AT THE LAP. THIS IS NOT |
| ALLOWED BECAUSE FASTENERS CAN'T BE SPACED LESS THAN |
| 4"O.C.. |
| IN ADDITION, ENGINEER'S RESPONSE IN WRITING IS NOT |
| CLEAR. PROVIDE DRAWING SHOWING THE NAILING SPACING AND |
| NUMBER OF ROWS. SEC. 106.1.2 CITY AMENDMENTS TO FBC |
| 2004 TO VERIFY COMPLIANCE WITH CALCULATED DESIGN |
| PRESSURES OF SEC. R301 OF 2004 FLORIDA RESIDENTIAL |
| CODE. |
| |
| OLD COMMENT: |
| 3- PROVIDE COMPLETE PRODUCT APPROVAL REPORT. ONLY THE |
| PAGE 43 OF 44 WAS SUBMITTED. SUBMIT THE FRONT COVER |
| PAGES OF THE NOA , THE SHEET WHERE SELECTED ASSEMBLY IS |
| SHOWN AND THE LAST PAGE OF THE NOA WITH THE GENERAL |
| LIMITATIONS. |
| |
| ***COMMENT BASED ON RESPONSE: |
| INFORMATION WAS NOT PROVIDED AT ALL. |
| |
| 4- OWES $70.00. REVISION SUBMITTED HAS 9 DRAWINGS AND |
| ONE ENGINEER LETTER/PRODUCT APPROVAL. REVISION FEES ARE |
| $50.00 PLUS $10.00 PER PLAN/PAGE. |
| |
| JULIO GOMEZ |
| BUILDING PLANS EXAMINER |
| (561)805-6712 |