2008-08-08 16:06:47RESIDENTIAL (R3) REVISION BUILDING REVIEW SECOND
 CHECKLIST:
  
 1- STAIR DETAIL ON SHEET D-1 CALLS FOR 18 RISERS, WHILE
 FLOOR PLANS SHOW 17 RISERS. REVISE AS REQUIRED TO MATCH
 AND SHOW COMPLIANCE WITH SEC. R311.5.3.2 OF 2004
 FLORIDA RESIDENTIAL CODE. (REPEAT COMMENT).
  
 2- ENGINEER TO REVISE RAS 117 CALCULATIONS. (REPEAT
 COMMENT). FASTENERS CAN'T BE SPACED LESS THAN 4"O.C..
 SEE SEC. 8.1 OF RAS 117. 2 ROWS IN THE LAP WILL HAVE
 THE FASTENERS SPACED AT LESS THAN 4" O.C..
 PROVIDE CALCULATIONS SHOWING HOW THE 2 ROWS AT LAP AND
 THE 3 ROWS IN THE CENTER OF THE SHEET WILL SATISFY THE
 NAIL ENHANCEMENT CALCULATIONS TO RESIST THE
 CALCULATED DESIGN PRESSURES. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004 TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC. R301 OF 2004 FLORIDA
 RESIDENTIAL CODE.
  
 3- PROVIDE COMPLETE PRODUCT APPROVAL REPORT. ONLY THE
 PAGE 43 OF 44 WAS SUBMITTED. SUBMIT THE FRONT COVER
 PAGES OF THE NOA , THE SHEET WHERE SELECTED ASSEMBLY IS
 SHOWN AND THE LAST PAGE OF THE NOA WITH THE GENERAL
 LIMITATIONS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712