2008-01-09 15:49:05PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) COULD NOT FIND A/C SYSTEM 1 & 2 IN THE ARI DIRECTORY
 WEB-SITE, PLEASE SUBMIT THE ARI REFERENCE NUMBER OR
 CERTIFICATE, SEE 2004 FBC 13-607.1.ABC.3.1.1.
  
 2) PLEASE SHOW AND SIZE THE SUPPLY AIR DUCT (FLEX) TO
 THE 10"X10" SUPPLY AIR GRILL IN THE KITCHEN, SEE 2004
 WPB AMEND. 106.3.5.4 (10).
  
 3) PLEASE LABEL THE CONDENSER UNITS 1, 2, & 3 ON THE
 MECHANICAL PLAN.
  
 4) AS BOTH AIR HANDLER UNITS ARE FEEDING THE SAME
 SUPPLY AND RETURN AIR DUCTS, PLEASE SUBMIT DETAILED
 MANUFACTURER'S SPECIFICATION'S AND INSTALLATION
 INSTRUCTIONS TO SUPPORT THIS DESIGN OR IF AN
 ENGINEERING SYSTEM, PLEASE SUBMIT THE COMPLETE
 ENGINEERING SIGNED AND SEALED BY THE ENGINEER, SEE 2004
 FBC/R M1401.1. AND WPB AMEND. 106.1.2.
  
 5) PLEASE SUBMIT MANUAL D CALCULATIONS TO SUPPORT THIS
 DESIGN, SEE 2004 FBC/R M1601.1.
  
 6) THE MECHANICAL PLANS NEED THE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN ON
 THEM, SEE W.P.B. AMEND. 106.1.3.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]