2008-01-09 15:49:05 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM |
| BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA |
| ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES |
| (F.S.). |
| |
| *** DENIED *** |
| 1) COULD NOT FIND A/C SYSTEM 1 & 2 IN THE ARI DIRECTORY |
| WEB-SITE, PLEASE SUBMIT THE ARI REFERENCE NUMBER OR |
| CERTIFICATE, SEE 2004 FBC 13-607.1.ABC.3.1.1. |
| |
| 2) PLEASE SHOW AND SIZE THE SUPPLY AIR DUCT (FLEX) TO |
| THE 10"X10" SUPPLY AIR GRILL IN THE KITCHEN, SEE 2004 |
| WPB AMEND. 106.3.5.4 (10). |
| |
| 3) PLEASE LABEL THE CONDENSER UNITS 1, 2, & 3 ON THE |
| MECHANICAL PLAN. |
| |
| 4) AS BOTH AIR HANDLER UNITS ARE FEEDING THE SAME |
| SUPPLY AND RETURN AIR DUCTS, PLEASE SUBMIT DETAILED |
| MANUFACTURER'S SPECIFICATION'S AND INSTALLATION |
| INSTRUCTIONS TO SUPPORT THIS DESIGN OR IF AN |
| ENGINEERING SYSTEM, PLEASE SUBMIT THE COMPLETE |
| ENGINEERING SIGNED AND SEALED BY THE ENGINEER, SEE 2004 |
| FBC/R M1401.1. AND WPB AMEND. 106.1.2. |
| |
| 5) PLEASE SUBMIT MANUAL D CALCULATIONS TO SUPPORT THIS |
| DESIGN, SEE 2004 FBC/R M1601.1. |
| |
| 6) THE MECHANICAL PLANS NEED THE PRINTED NAME AND |
| SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN ON |
| THEM, SEE W.P.B. AMEND. 106.1.3. |
| |