Plan Review Notes
Plan Review Notes For Permit 06101122
Permit Number 06101122
Review Stop B
Sequence Number 4
Notes
Date Text
2008-02-05 13:50:08BUILDING REVIEW APPROVED WITH PROVISO:
 1- REVISE SOIL TEST REPORT TO REFLECT REVISED PROPOSED
 SCOPE OF WORK.
 2- PROVIDE MANUFACTURER SPECS FOR BBQ GRILL TO BE
 INSTALLED IN PORCH.PAGE III OF SPECSSUBMITTED DON'T
 ALLOWBBQ GRILL ON PORCH.
 3- PROVIDE CLEAR DETAILS AND SPECS FOR STAIRS TO SHOW
 COMPLIANCE WITH WINDERS DIMENSIONS OF SEC. R311.5.3.2
 OF 2004 FLORIDA RESIDENTIAL CODE AND LIVE LOADS AS
 REQUIRED BY TABLE R301.5.
 ALSO, REVISE CODE REFERENCES SHOWN ON TYPICAL STAIR
 DETAIL ON SHEET D-1. SEE SEC. R311.5 OF 2004 FLORIDA
 RESIDENTIAL CODE FOR PROPER CODE SECTIONS TO BE
 REFERENCED.
 4- SPECIFY DRAFSTOPPING ON SECOND FLOOR PLANAS
 REQUIRED BY SEC. R502.1.2 OF 2004 FLORIDA RESIDENTIAL
 CODE.
 5- THIS PROPERTY IS LOCATED ON FLOOD ZONE "C", NOT "B".
 REVISE SURVEY AS REQUIRED.
 6- PROVIDE COMPLETE WALL SECTION THRU BALCONY
 PROVIDINGCOMPLETE SPECSFOR FLOOR (INCLUDING BALCONY
 DECK)AND CEILINGS AS REQ'DBY SEC. 106.3.5.4 OF CITY
 AMENDMENTS TO FBC 2004 TO VERIFY COMPLIANCE WITH SEC.
 R301 OF 2004FLORIDA RESIDENTIAL CODE.
 7- PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING AT
 PERIMETER AND CORNER AREAS FOR POLYGLASS MODIFIED
 BITUMEN AS REQ'DBY GENERAL LIMITATION #7.SEE
 GENERAL LIMITATION #7 TO SEE WHO CAN PREPARE SUCH
 CALCULATIONS.
 8- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) PRODUCT APPROVAL FOR
 POLYGLASS MODIFIED BITUMEN AS REQ'DBY SEC. 106.3.3
 CITY AMENDMENTS TO FBC 2004.
 9- REVISE TYPO ON ENERGY CALCULATIONS ITEM 9(B).THERE
 IS NOT INSULATION R-219.
  
 ***NOTE: PROVIDE ABOVE INFORMATION PRIOR TO INSPECTIONS
 TO AVOID CONFLICTS ORDELAYS.