2008-02-05 13:50:08 | BUILDING REVIEW APPROVED WITH PROVISO: |
| 1- REVISE SOIL TEST REPORT TO REFLECT REVISED PROPOSED |
| SCOPE OF WORK. |
| 2- PROVIDE MANUFACTURER SPECS FOR BBQ GRILL TO BE |
| INSTALLED IN PORCH.PAGE III OF SPECSSUBMITTED DON'T |
| ALLOWBBQ GRILL ON PORCH. |
| 3- PROVIDE CLEAR DETAILS AND SPECS FOR STAIRS TO SHOW |
| COMPLIANCE WITH WINDERS DIMENSIONS OF SEC. R311.5.3.2 |
| OF 2004 FLORIDA RESIDENTIAL CODE AND LIVE LOADS AS |
| REQUIRED BY TABLE R301.5. |
| ALSO, REVISE CODE REFERENCES SHOWN ON TYPICAL STAIR |
| DETAIL ON SHEET D-1. SEE SEC. R311.5 OF 2004 FLORIDA |
| RESIDENTIAL CODE FOR PROPER CODE SECTIONS TO BE |
| REFERENCED. |
| 4- SPECIFY DRAFSTOPPING ON SECOND FLOOR PLANAS |
| REQUIRED BY SEC. R502.1.2 OF 2004 FLORIDA RESIDENTIAL |
| CODE. |
| 5- THIS PROPERTY IS LOCATED ON FLOOD ZONE "C", NOT "B". |
| REVISE SURVEY AS REQUIRED. |
| 6- PROVIDE COMPLETE WALL SECTION THRU BALCONY |
| PROVIDINGCOMPLETE SPECSFOR FLOOR (INCLUDING BALCONY |
| DECK)AND CEILINGS AS REQ'DBY SEC. 106.3.5.4 OF CITY |
| AMENDMENTS TO FBC 2004 TO VERIFY COMPLIANCE WITH SEC. |
| R301 OF 2004FLORIDA RESIDENTIAL CODE. |
| 7- PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING AT |
| PERIMETER AND CORNER AREAS FOR POLYGLASS MODIFIED |
| BITUMEN AS REQ'DBY GENERAL LIMITATION #7.SEE |
| GENERAL LIMITATION #7 TO SEE WHO CAN PREPARE SUCH |
| CALCULATIONS. |
| 8- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) PRODUCT APPROVAL FOR |
| POLYGLASS MODIFIED BITUMEN AS REQ'DBY SEC. 106.3.3 |
| CITY AMENDMENTS TO FBC 2004. |
| 9- REVISE TYPO ON ENERGY CALCULATIONS ITEM 9(B).THERE |
| IS NOT INSULATION R-219. |
| |
| ***NOTE: PROVIDE ABOVE INFORMATION PRIOR TO INSPECTIONS |
| TO AVOID CONFLICTS ORDELAYS. |