2007-08-16 09:09:26 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| REFERENCED CODES WITH 2005, 2006 REVISIONS, AND CHAPTER |
| 1 CITY OF WEST PALM BEACH AMENDMENTS. |
| |
| *** DENIED *** |
| 1) MECHANICAL PLANS NEED THE JOB ADDRESS, AND THE |
| INFORMATION OF THE PERSON RESPONSIBLE FOR THE DESIGN ON |
| THEM. SEE WPB AMEND. 106.1.3. |
| |
| 2) MECHANICAL PLAN EQUIPMENT SUMMARY NEEDS THE TOTAL |
| AND SENSIBLE BTU'S FOR THE SYSTEMS IN IT. |
| |
| 3) NEED TO SIZE ALL THE RETURN AIR GRILLS ON THE |
| MECHANICAL PLAN. |
| |
| 4) THE 10X8" SUPPLY AIR GRILL IN BEDROOM #3 HAS TWO 7" |
| SUPPLY AIR DUCTS GOING TO IT. PLEASE CORRECT. |
| |
| 5) SHOW THE LOCATION OF THE CLOTHES DRYER VENT AND WERE |
| IT WILL TERMINATE AT ON MECHANICAL PLAN, SEE FBC RES. M |
| 501.2. |
| |
| 6) PROVIDE COMBUSTION AIR CALCULATIONS FOR GAS CLOSE |
| DRYER AND COMBUSTION AIR TO LAUNDRY ROOM IF REQUIRED, |
| SEE FBC RES. G2407.1. |
| |
| 7) ELECTRICAL PLAN SHOWS THE TWO A/C CONDENSER UNITS |
| SIDE BY SIDE, THE MECHANICAL PLAN SHOWS THEM AT |
| DIFFERENT SIDES OF THE HOUSE, THE PLANS MUST COINCIDE |
| PLEASE CORRECT. |
| |
| 8) SUBMIT DETAILED MANUFACTURER'S SPECIFICATION'S AND |
| INSTALLATION INSTRUCTIONS FOR THE GAS COOK-TOP IN THE |
| LANAI AS IT MAY REQUIRE AN APPROVED EXHAUST HOOD, SEE |
| FBC RES. M1504.1. |
| |
| MECHANICAL PLAN REVIEW BY; |
| TOM GORDON (561) 805-6729 |
| E-MAIL: [email protected]. |