Plan Review Notes
Plan Review Notes For Permit 06101122
Permit Number 06101122
Review Stop M
Sequence Number 2
Notes
Date Text
2007-06-08 09:52:22*** DENIED ***
 ** ALL OF THE BELOW CORRECTIONS WERE REQUESTED IN THE
 LAST REVIEW 11-20-07 AND STILL NEED TO BE CORRECTED.**
  
 1) MECHANICAL PLAN ARE DIFFICULT TO READ THEIR IS TO
 MUCH FLOOR PLAN DETAIL ON THEM. CONSTRUCTION DOCUMENTS
 SHALL BE OF SUFFICIENT CLARITY. PLEASE SUBMIT BETTER
 MECHANICAL PLANS. PER 2004 FBC 106.1.1.
 .
 2) THE MECHANICAL PLANS NEED TO BE SEALED BY THE
 ENGINEER JOHN M. AVERKAMP AS HIS NAME AND INFORMATION
 IS IN THE TITLE BLOCK, PER FAC 61G15-23.002 .
  
 3) PLEASE SHOW AN EQUIPMENT LISTING WITH ALL PERTINENT
 INFORMATION ON THE MECHANICAL PLANS.
  
 4) WAS NOTE 6, NEED ATTIC ACCESS WITH-IN 6 FEET OF AHU
 #1, PER 2004 FBC/R M1305.1.3, PLEASE SHOW ACCESS ON
 MECHANICAL AND BUILDING PLANS.
  
 5) WAS NOTE 7, PLEASE SHOW ON MECHANICAL PLANS THE
 LOCATION OF THE A/C CONDENSER UNITS, AND BATHROOM
 EXHAUST FANS.
  
 6) SEE ATTACHED NOTICE FS 553.80(2)(B) REGARDING FOUR
 TIMES THE FEE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.