| PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE |
| COMPLIANCE AND RESUBMIT FOR REVIEW |
| |
| THE PLAN RESUBMITTED FOR REVIEW IS NOT THE SAME FLOOR |
| PLAN AS PREVIOUSLY REVIEWED, SEE "OLD SET". |
| |
| 1} THE OVEN AND DRYER CIRCUITS BOTH HAVE INCORRECTLY |
| SIZED OVERCURRENT PROTECTION ON THE PANEL SCHEDULE, |
| CIRCUITS 11,13 AN D15,17. ARTICLE 240. |
| |
| 2} LOCATE THE METER AND MAIN DISCONNECT AND ALL SERVICE |
| EQUIPMENT, ON THE PLAN, SHEET E-1. |
| |
| 3} RECEPTACLES MUST BE ADDED TO THE ISLAND (KTTCHEN) |
| FOR REQUIRED SPACING PER 210.52(C), |
| |
| 4} THE WALL BETWEEN THE MASTER BATH AND THE GREAT ROOM |
| IS MISSING, SHEET E-1. |
| |
| 5} A GFI PROTCTED RECEPTACLE IS REQUIRED AT THE BACK OF |
| THE DWELLING PER 210.52(E), 2108(A)(3). |
| |
| 6} RECEPTACLES MUST BE ADDED TO COMPLY WITH 210.52 IN |
| THE DINING ROOM, BEDROOMS #2 AND #3, AND THE MASTER |
| BEDROOM. SEE REVIEWED PLAN. |
| |
| 7} THE NOTE UNDER THE RISER DIAGRAM AND NOTE #6, |
| ELECTRICAL NOTES,REGARDING SMOKE ALARM CIRCUITS, |
| SHOULD INDICATE ARC FAULT CIRCUITS REQUIRED. |
| |
| 8} THERE ARE 3 GARAGE DOOR OPENERS IN THE LOAD |
| CALCULATION, AND ONLY 1 ON THE PANEL SCHEDULE AND IN |
| THE GARAGE.PLEASE CORRELATE. |
| |
| 9} PROVIDE A PANEL SCHEDULE FOR THE 400 AMP MAIN. IT |
| INDICATES A 400 AMP MAIN AND 2-200 AMP BREAKERS BUT IS |
| AN 8 CIRCUIT PANEL. PROVIDE THE AIC RATING ALSO.110.9. |
| |
| PLEASE REMOVE ALL OLD OR VOIDED SHEETS AND REPLACE WITH |
| CORRECTED ONES WHEN RESUBMITTING. INCLUDE THEM |
| SEPARATELY TO EXPEDITE THE REVIEW PROCESS. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |