Notes
Date Text
2007-06-04 08:09:12 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW
  
 THE PLAN RESUBMITTED FOR REVIEW IS NOT THE SAME FLOOR
 PLAN AS PREVIOUSLY REVIEWED, SEE "OLD SET".
  
 1} THE OVEN AND DRYER CIRCUITS BOTH HAVE INCORRECTLY
 SIZED OVERCURRENT PROTECTION ON THE PANEL SCHEDULE,
 CIRCUITS 11,13 AN D15,17. ARTICLE 240.
  
 2} LOCATE THE METER AND MAIN DISCONNECT AND ALL SERVICE
 EQUIPMENT, ON THE PLAN, SHEET E-1.
  
 3} RECEPTACLES MUST BE ADDED TO THE ISLAND (KTTCHEN)
 FOR REQUIRED SPACING PER 210.52(C),
  
 4} THE WALL BETWEEN THE MASTER BATH AND THE GREAT ROOM
 IS MISSING, SHEET E-1.
  
 5} A GFI PROTCTED RECEPTACLE IS REQUIRED AT THE BACK OF
 THE DWELLING PER 210.52(E), 2108(A)(3).
  
 6} RECEPTACLES MUST BE ADDED TO COMPLY WITH 210.52 IN
 THE DINING ROOM, BEDROOMS #2 AND #3, AND THE MASTER
 BEDROOM. SEE REVIEWED PLAN.
  
 7} THE NOTE UNDER THE RISER DIAGRAM AND NOTE #6,
 ELECTRICAL NOTES,REGARDING SMOKE ALARM CIRCUITS,
 SHOULD INDICATE ARC FAULT CIRCUITS REQUIRED.
  
 8} THERE ARE 3 GARAGE DOOR OPENERS IN THE LOAD
 CALCULATION, AND ONLY 1 ON THE PANEL SCHEDULE AND IN
 THE GARAGE.PLEASE CORRELATE.
  
 9} PROVIDE A PANEL SCHEDULE FOR THE 400 AMP MAIN. IT
 INDICATES A 400 AMP MAIN AND 2-200 AMP BREAKERS BUT IS
 AN 8 CIRCUIT PANEL. PROVIDE THE AIC RATING ALSO.110.9.
  
 PLEASE REMOVE ALL OLD OR VOIDED SHEETS AND REPLACE WITH
 CORRECTED ONES WHEN RESUBMITTING. INCLUDE THEM
 SEPARATELY TO EXPEDITE THE REVIEW PROCESS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]