2007-07-09 17:04:49 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBCFLORIDA BUILDING CODE 2004 |
| FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC EB |
| FLORIDA BUILDING CODE 2004 EXISTING BUILDING CODE FBC* |
| CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| |
| |
| COMMENTS FROM PREVIOUS LIST: |
| |
| 1.)A NOTICE OF COMMENCEMENT WILL BE REQUIRED PRIOR TO |
| PERMIT PICKUP, FS713.13. |
| |
| 2.)IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY |
| PRIOR TO PERMIT ISSUANCE, 2300 N JOG RD.THE PLANS |
| MUST BE STAMPED AND THE RECEIPT ATTACHED TO THE |
| APPLICATION.PLEASE CALL 561-233-5025 FOR MORE |
| INFORMATION. |
| |
| 3.)INCLUDE FBC EB IN GOVERNING CODE.DECLARE LEVEL |
| OF ALTERATION, FBC EB CHAPTER 3. |
| |
| 4.)PRODUCT APPROVALS ARE TO BE APPROVED BY DESIGNER |
| OF RECORD, FBC*106.3.3. |
| |
| 2ND REVIEW - THIS MAY BE DONE WITH A SHOP DRAWING |
| REVIEW STAMP OR A LETTER. |
| |
| 5.)FLORIDA STATE OR LOCAL PRODUCT APPROVALS REQUIRED |
| IN ADDITION TO THE NOAS SUBMITTED, FAC9B72. |
| WWW.FLORIDABUILDING.ORG.THE FLORIDA STATE PRODUCT |
| APPROVALS PROVIDED ARE EXPIRED; FBC2001 RATHER THAN |
| FBC2004.PLEASE PRINT CURRENT APPROVALS. |
| |
| 2001 APPROVALS WERE SUBMITTED FOR PGT PW701, WINDSOR |
| DOOR (2004 REQUIRED).NONE PROVIDED FOR THE PGT |
| MULLION. |
| |
| 6.)ADDRESSED. |
| |
| 7.)SHOW REQUIRED HEAD CLEARANCE FOR THE ATTIC ACCESS, |
| R807.IT DOES NOT APPEAR TO BE COMPLIANT IN THIS |
| LOCATION. |
| |
| 2ND REVIEW -IT IS NOT CLEAR HOW THIS WAS ADDRESSED. |
| |
| 8-10.)ADDRESSED. |
| |
| 11.)SHOW DRAINAGE TO COMPLY WITH FBC R401. |
| |
| 12.)DECLARE LEVEL OF ALTERATION, FBC EB CHAPTER 3. |
| |
| 13.)PROVIDE A SOILS INVESTIGATION REPORT, FBC |
| R401.4. |
| |
| 2ND REVIEW - THIS WAS NOT SUBMITTED.THE SOILS REPORT |
| SHOULD ALSO ADDRESS THE EXISTING POOL AREA. |
| |
| 14-15.)ADDRESSED. |
| |
| 16.)DOES THE GARAGE DOOR HAVE GLAZING?NOTE THAT |
| GLAZING IS AN OPTION ON THE PRODUCT APPROVAL SUBMITTED |
| BUT REQUIRES IMPACT PROTECTION. |
| |
| THIS MAY BE ADDRESSED BY WRITING "NO GLAZING" ON THE |
| PRODUCT APPROVAL.IF YOU ARE USING THE GLAZING OPTION, |
| IMPACT PROTECTION REQUIRED (WITH PRODUCT APPROVALS AND |
| ATTACHED INSTALLATION SCHEDULE COMPLETED). |
| |
| 17.)ADDRESSED. |
| |
| 18.)CHANGES TO THE PLAN MUST BE DONE BY THE DESIGNER |
| OF RECORD, CLOUDED, INITIALLED AND DATED.REVISIONS |
| WERE DONE ON A1 AND A3 APPARENTLY BY SOMEONE OTHER THAN |
| THE ENGINEER. |
| |
| 2ND REVIEW - CHANGES WERE NOT CLOUDED.THIS REQUIRES |
| AN ENTIRELY NEW PLAN REVIEW AND WILL CAUSE DELAYS. ALL |
| REVISIONS/CHANGES TO THE PLAN ARE TO BE CLOUDED AND |
| NUMBERED. |
| |
| 19.)ELEVATIONS ON A1 SHOULD NOTE EXISTING AND |
| ADDITION AREAS. |
| |
| 20.)THE ADDING STRAP DETAIL S2 DOES NOT COMPLY WITH |
| THE SIMPSON CATALOG.ADDRESS.CHECK ALL CONNECTORS. |
| |
| 21.)SHEET D-2, HIB-91 HAS BEEN REPLACED BY TPI/WTCA |
| BCSI 1-03.CHECK ALL REFERENCES.FOR INSTANCE, |
| CONCRETE NOTE REFERS TO ACI 544.1R-82.THERE ARE OTHER |
| EXPIRED REFERENCES.SEE FBC35. |
| |
| 22.)GARAGE/RESIDENCE SEPARATION TO COMPLY WITH FBC |
| R309. |
| |
| NEW COMMENT: |
| |
| 23.)SEE ATTACHED FS553.80(2)9B). |