Plan Review Notes For Permit 06101122 |
Permit Number |
06101122 |
|
Review Stop |
B |
Sequence Number |
10 |
|
Notes |
Date |
Text |
2008-12-29 13:04:49 | BUILDING SUBMITTAL CHECKLIST: | | | | 1- ENGINEER'S NAIL ENHANCING LETTER SUBMITTED FOR | | POLYGLASS MODIFIED BITUMEN ROOFING SYSTEM DOESN'T WORK | | FOR ZONE #3. ENGINEER TO PROVIDE THE CALCULATED DESIGN | | PRESSURES FOR ALL ZONES IN EXPOSURE "C" AS SPECIFIED ON | | LETTER SUBMITTED. AND, PROVIDE ACTUAL RAS 117 | | CALCULATIONS. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004 | | TO VERIFY COMPLIANCE WITH RAS 117 CALCULATIONS AND | | DESIGN PRESSURES OF SEC. R301 OF 2004 FLORIDA | | RESIDENTIAL CODE. | | NOTE: ENGINEER TO REVIEW SEC. 8.1 OF RAS 117 FOR | | MINIMUM FASTENER SEPARATION SPACING ALLOWED. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|