Plan Review Notes
Plan Review Notes For Permit 06101122
Permit Number 06101122
Review Stop B
Sequence Number 10
Notes
Date Text
2008-12-29 13:04:49BUILDING SUBMITTAL CHECKLIST:
  
 1- ENGINEER'S NAIL ENHANCING LETTER SUBMITTED FOR
 POLYGLASS MODIFIED BITUMEN ROOFING SYSTEM DOESN'T WORK
 FOR ZONE #3. ENGINEER TO PROVIDE THE CALCULATED DESIGN
 PRESSURES FOR ALL ZONES IN EXPOSURE "C" AS SPECIFIED ON
 LETTER SUBMITTED. AND, PROVIDE ACTUAL RAS 117
 CALCULATIONS. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004
 TO VERIFY COMPLIANCE WITH RAS 117 CALCULATIONS AND
 DESIGN PRESSURES OF SEC. R301 OF 2004 FLORIDA
 RESIDENTIAL CODE.
 NOTE: ENGINEER TO REVIEW SEC. 8.1 OF RAS 117 FOR
 MINIMUM FASTENER SEPARATION SPACING ALLOWED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712