Plan Review Notes For Permit 06101122 |
Permit Number |
06101122 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-11-20 15:58:31 | *** DENIED *** | | 1) MECHANICAL PLAN ARE DIFFICULT TO READ. CONSTRUCTION | | DOCUMENTS SHALL BE OF SUFFICIENT CLARITY. PER 2004 FBC | | 106.1.1. | | . | | 2) THE MECHANICAL PLANS NEED TO BE SEALED BY THE | | ENGINEER JOHN M. AVERKAMP AS HIS NAME AND INFORMATION | | IS IN THE TITLE BLOCK, PER FAC 61G15-23.002 . | | | | 3) PLEASE SHOW AN EQUIPMENT LISTING WITH ALL PERTINENT | | INFORMATION ON THE MECHANICAL PLANS. | | | | 4) PLANS SHOW 3,061 SQUARE FEET UNDER AIR, ENERGY | | CAL'S. AND MANUAL J CAL'S. SHOW 3,361 SQUARE FEET UNDER | | AIR THE TWO MUST COINCIDE, PLEASE CORRECT ENERGY CAL'S. | | AND MANUAL J CAL'S. | | | | 5) ONE 8" SUPPLY AIR DUCT IS GOING OUT-SIDE TO THE | | COVERED PATIO KITCHEN, PLEASE CORRECT. | | | | 6) NEED ATTIC ACCESS WITH-IN 6 FEET OF AHU #1, PER 2004 | | FBC/R M1305.1.3, PLEASE SHOW ACCESS ON MECHANICAL AND | | BUILDING PLANS. | | | | 7) PLEASE SHOW ON MECHANICAL PLANS THE LOCATION OF THE | | A/C CONDENSER UNITS, AND BATHROOM EXHAUST FANS. | | | | 8) PLEASE SUBMIT A COMPLETE MANUAL J CALCULATION, PER | | 2004 FBC 13-607.1.ABC.1. NOT JUST A SUMMARY PAGE. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|