2006-11-20 15:58:31*** DENIED ***
 1) MECHANICAL PLAN ARE DIFFICULT TO READ. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY. PER 2004 FBC
 106.1.1.
 .
 2) THE MECHANICAL PLANS NEED TO BE SEALED BY THE
 ENGINEER JOHN M. AVERKAMP AS HIS NAME AND INFORMATION
 IS IN THE TITLE BLOCK, PER FAC 61G15-23.002 .
  
 3) PLEASE SHOW AN EQUIPMENT LISTING WITH ALL PERTINENT
 INFORMATION ON THE MECHANICAL PLANS.
  
 4) PLANS SHOW 3,061 SQUARE FEET UNDER AIR, ENERGY
 CAL'S. AND MANUAL J CAL'S. SHOW 3,361 SQUARE FEET UNDER
 AIR THE TWO MUST COINCIDE, PLEASE CORRECT ENERGY CAL'S.
 AND MANUAL J CAL'S.
  
 5) ONE 8" SUPPLY AIR DUCT IS GOING OUT-SIDE TO THE
 COVERED PATIO KITCHEN, PLEASE CORRECT.
  
 6) NEED ATTIC ACCESS WITH-IN 6 FEET OF AHU #1, PER 2004
 FBC/R M1305.1.3, PLEASE SHOW ACCESS ON MECHANICAL AND
 BUILDING PLANS.
  
 7) PLEASE SHOW ON MECHANICAL PLANS THE LOCATION OF THE
 A/C CONDENSER UNITS, AND BATHROOM EXHAUST FANS.
  
 8) PLEASE SUBMIT A COMPLETE MANUAL J CALCULATION, PER
 2004 FBC 13-607.1.ABC.1. NOT JUST A SUMMARY PAGE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.