Plan Review Notes For Permit 06101122 |
Permit Number |
06101122 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-11-16 16:42:11 | | | | | NONCOMPLIANT | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | 1} THE OVEN AND DRYER CIRCUITS BOTH HAVE INCORRECTLY | | SIZED OVERCURRENT PROTECTION ON THE PANEL SCHEDULE, | | CIRCUITS 11,13 AN D15,17. ARTICLE 240. | | | | 2} LOCATE THE METER AND MAIN DISCONNECT ON THE PLAN, | | SHEET E-1. | | | | 3} NOTE #1 REFERS TO "IAW" PLEASE NOTE THAT THE STATE | | OF FLORIDA HAS ADOPTED NFPA 70 OR THE NEC. REMOVE THE | | REFERENCE. | | | | 4} SMOKE DETECTORS MUST BE INSTALLED TO COMPLY WITH | | R313.1 RESIDENTIAL FLORIDA BUILDING CODE. | | | | 5} THE GARAGE RECEPTACLES ARE REQUIRED TO BE GFI | | PROTECTED PER 210.8(A)(2). | | | | 6} RECEPTACLES MUST BE ADDED TO THE KITCHEN COUNTER | | TOPS FOR REQUIRED SPACING PER 210.52(C),(INCLUDING | | THE ISLAND). | | | | 7} THE BATHROOM OFF BEDROOM #2 AN DBEDROOM #3 MUST HAVE | | OUTLETS SPACED PER 210.52(D), AND GFI PROTECTED PER | | 210.8(A)(1). | | | | 8} A GFI PROTCTED RECEPTACLE IS REQUIRED AT THE BACK OF | | THE DWELLING PER 210.52(E), 2108(A)(3). | | | | THERE ARE RECEPTACLES PLACED OFF THE WALL IN THE DINING | | ROOM AND IN THE WALL AT TEH STORAGE CLOSET. PLEASE | | LOCATE WHERE INTENDED. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW. | | CITY OF WEST PALM BEACH | | 561/805-6718 | | [email protected] |
|