2007-01-05 16:28:39****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE
 FBC2004
  
  
 1.)A NOTICE OF COMMENCEMENT WILL BE REQUIRED PRIOR TO
 PERMIT PICKUP, FS713.13.
  
 2.)IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY
 PRIOR TO PERMIT ISSUANCE, 2300 N JOG RD.THE PLANS
 MUST BE STAMPED AND THE RECEIPT ATTACHED TO THE
 APPLICATION.PLEASE CALL 561-233-5025 FOR MORE
 INFORMATION.
  
 3.)INCLUDE FBC EB IN GOVERNING CODE.DECLARE LEVEL
 OF ALTERATION, FBC EB CHAPTER 3.
  
 4.)PRODUCT APPROVALS ARE TO BE APPROVED BY DESIGNER
 OF RECORD, FBC*106.3.3.
  
 5.)FLORIDA STATE OR LOCAL PRODUCT APPROVALS REQUIRED
 IN ADDITION TO THE NOAS SUBMITTED, FAC9B72.
 WWW.FLORIDABUILDING.ORG.THE FLORIDA STATE PRODUCT
 APPROVALS PROVIDED ARE EXPIRED; FBC2001 RATHER THAN
 FBC2004.PLEASE PRINT CURRENT APPROVALS.
  
 6.)PROVIDE AREA CALCULATIONS ON THE PLAN; EXISTING,
 PROPOSED, NEW TOTALS FOR CONDITIONED AND UNCONDITIONED
 SPACE.
  
 7.)SHOW REQUIRED HEAD CLEARANCE FOR THE ATTIC ACCESS,
 R807.IT DOES NOT APPEAR TO BE COMPLIANT IN THIS
 LOCATION.
  
 8.)SMOKE DETECTORS REQUIRED FBC R313.
  
 9.)SHOW REQUIRED SAFETY GLAZING FBCR308.4.
  
 10.)SPECIFY WINDOW SIZE AND TYPE FOR REQUIRED
 EMERGENCY EGRESS, FBC R310.
  
 11.)SHOW DRAINAGE TO COMPLY WITH FBC R401.
  
 12.)DECLARE LEVEL OF ALTERATION, FBC EB CHAPTER 3.
  
 13.)PROVIDE A SOILS INVESTIGATION REPORT, FBC
 R401.4.
  
 14.)PROVIDE A SITE PLAN SHOWING THE EXISTING HOUSE
 AND THE PROPOSED ADDITION, FBC*106.3.5.
  
 15.)SIGN THE OWNER/AGENT LINE OF THE ENERGY CALCS,
 FBC13.
  
 16.)DOES THE GARAGE DOOR HAVE GLAZING?NOTE THAT
 GLAZING IS AN OPTION ON THE PRODUCT APPROVAL SUBMITTED
 BUT REQUIRES IMPACT PROTECTION.
  
 17.)PROVIDE INFORMATION IN REGARDS TO FASTENING FOR
 THE IMPACT PROTECTION.PROVIDE A KEY PLAN WITH
 INFORMATION FOR EACH OPENING.SEE ATTACHED FORM FOR A
 SUGGESTED FORMAT.IF ALL INFORMATION IS NOT PROVIDED
 PRIOR TO PERMIT ISSUANCE, A SEPARATE PERMIT WILL BE
 REQUIRED FOR THE SHUTTERS.
  
 18.)CHANGES TO THE PLAN MUST BE DONE BY THE DESIGNER
 OF RECORD, CLOUDED, INITIALLED AND DATED.REVISIONS
 WERE DONE ON A1 AND A3 APPARENTLY BY SOMEONE OTHER THAN
 THE ENGINEER.
  
 19.)ELEVATIONS ON A1 SHOULD NOTE EXISTING AND
 ADDITION AREAS.
  
 20.)THE ADDING STRAP DETAIL S2 DOES NOT COMPLY WITH
 THE SIMPSON CATALOG.ADDRESS.CHECK ALL CONNECTORS.
  
 21.)SHEET D-2, HIB-91 HAS BEEN REPLQCED BY TPI/WTCA
 BCSI 1-03.CHECK ALL REFERENCES.FOR INSTANCE,
 CONCRETE NOTE REFERS TO ACI 544.1R-82.THERE ARE OTHER
 EXPIRED REFERENCES.SEE FBC35.
  
 22.)GARAGE/RESIDENCE SEPARATION TO COMPLY WITH FBC
 R309.
  