2007-01-05 16:28:39 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBCFLORIDA BUILDING CODE 2004 |
| FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL |
| FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| CODE |
| FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE |
| FBC2004 |
| |
| |
| 1.)A NOTICE OF COMMENCEMENT WILL BE REQUIRED PRIOR TO |
| PERMIT PICKUP, FS713.13. |
| |
| 2.)IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY |
| PRIOR TO PERMIT ISSUANCE, 2300 N JOG RD.THE PLANS |
| MUST BE STAMPED AND THE RECEIPT ATTACHED TO THE |
| APPLICATION.PLEASE CALL 561-233-5025 FOR MORE |
| INFORMATION. |
| |
| 3.)INCLUDE FBC EB IN GOVERNING CODE.DECLARE LEVEL |
| OF ALTERATION, FBC EB CHAPTER 3. |
| |
| 4.)PRODUCT APPROVALS ARE TO BE APPROVED BY DESIGNER |
| OF RECORD, FBC*106.3.3. |
| |
| 5.)FLORIDA STATE OR LOCAL PRODUCT APPROVALS REQUIRED |
| IN ADDITION TO THE NOAS SUBMITTED, FAC9B72. |
| WWW.FLORIDABUILDING.ORG.THE FLORIDA STATE PRODUCT |
| APPROVALS PROVIDED ARE EXPIRED; FBC2001 RATHER THAN |
| FBC2004.PLEASE PRINT CURRENT APPROVALS. |
| |
| 6.)PROVIDE AREA CALCULATIONS ON THE PLAN; EXISTING, |
| PROPOSED, NEW TOTALS FOR CONDITIONED AND UNCONDITIONED |
| SPACE. |
| |
| 7.)SHOW REQUIRED HEAD CLEARANCE FOR THE ATTIC ACCESS, |
| R807.IT DOES NOT APPEAR TO BE COMPLIANT IN THIS |
| LOCATION. |
| |
| 8.)SMOKE DETECTORS REQUIRED FBC R313. |
| |
| 9.)SHOW REQUIRED SAFETY GLAZING FBCR308.4. |
| |
| 10.)SPECIFY WINDOW SIZE AND TYPE FOR REQUIRED |
| EMERGENCY EGRESS, FBC R310. |
| |
| 11.)SHOW DRAINAGE TO COMPLY WITH FBC R401. |
| |
| 12.)DECLARE LEVEL OF ALTERATION, FBC EB CHAPTER 3. |
| |
| 13.)PROVIDE A SOILS INVESTIGATION REPORT, FBC |
| R401.4. |
| |
| 14.)PROVIDE A SITE PLAN SHOWING THE EXISTING HOUSE |
| AND THE PROPOSED ADDITION, FBC*106.3.5. |
| |
| 15.)SIGN THE OWNER/AGENT LINE OF THE ENERGY CALCS, |
| FBC13. |
| |
| 16.)DOES THE GARAGE DOOR HAVE GLAZING?NOTE THAT |
| GLAZING IS AN OPTION ON THE PRODUCT APPROVAL SUBMITTED |
| BUT REQUIRES IMPACT PROTECTION. |
| |
| 17.)PROVIDE INFORMATION IN REGARDS TO FASTENING FOR |
| THE IMPACT PROTECTION.PROVIDE A KEY PLAN WITH |
| INFORMATION FOR EACH OPENING.SEE ATTACHED FORM FOR A |
| SUGGESTED FORMAT.IF ALL INFORMATION IS NOT PROVIDED |
| PRIOR TO PERMIT ISSUANCE, A SEPARATE PERMIT WILL BE |
| REQUIRED FOR THE SHUTTERS. |
| |
| 18.)CHANGES TO THE PLAN MUST BE DONE BY THE DESIGNER |
| OF RECORD, CLOUDED, INITIALLED AND DATED.REVISIONS |
| WERE DONE ON A1 AND A3 APPARENTLY BY SOMEONE OTHER THAN |
| THE ENGINEER. |
| |
| 19.)ELEVATIONS ON A1 SHOULD NOTE EXISTING AND |
| ADDITION AREAS. |
| |
| 20.)THE ADDING STRAP DETAIL S2 DOES NOT COMPLY WITH |
| THE SIMPSON CATALOG.ADDRESS.CHECK ALL CONNECTORS. |
| |
| 21.)SHEET D-2, HIB-91 HAS BEEN REPLQCED BY TPI/WTCA |
| BCSI 1-03.CHECK ALL REFERENCES.FOR INSTANCE, |
| CONCRETE NOTE REFERS TO ACI 544.1R-82.THERE ARE OTHER |
| EXPIRED REFERENCES.SEE FBC35. |
| |
| 22.)GARAGE/RESIDENCE SEPARATION TO COMPLY WITH FBC |
| R309. |
| |