2006-11-29 07:32:54PROVISO:
 1.PLAN SHEET M-1 NOTE 3 INDICATES THE RETURN AIR TO
 BE DUCTED.THE DUCT LAYOUT INDICATES TRANSFER GRILLES
 WITH THE RETURN AIR GRILLE IS DIRECTRLY UNDER THE AHU.
 PLEASE NOTE,THE ATTIC SHALL NOT SERVE AS A RETURN AIR
 PLENUM.THE PLANS DO NOT REFLECT THE RETURN AIR BEING
 DUCTED FROM THE BOTTOM.HOW WILL THIS BE DONE WITH THE
 UNISTRUT AND DRAIN PAN THIS UNDER THE AHU.IF THE
 RETURN AIR IS DUCTED PLEASE PROVIDE A REVISION SHOWING
 LAYOUT, THE GRILLE AND DUCT SIZES.PLEASE PROVIDE A
 REVISION PRIOR TO INSPECTION.
  
 2.ACCESS TO THE AHU SHALL COMPLY WITH 2004 FMC
 306.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS
 AT (561)805-6719 OR E-MAIL [email protected].