Plan Review Notes For Permit 06101087 |
Permit Number |
06101087 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2006-11-29 07:32:54 | PROVISO: | | 1.PLAN SHEET M-1 NOTE 3 INDICATES THE RETURN AIR TO | | BE DUCTED.THE DUCT LAYOUT INDICATES TRANSFER GRILLES | | WITH THE RETURN AIR GRILLE IS DIRECTRLY UNDER THE AHU. | | PLEASE NOTE,THE ATTIC SHALL NOT SERVE AS A RETURN AIR | | PLENUM.THE PLANS DO NOT REFLECT THE RETURN AIR BEING | | DUCTED FROM THE BOTTOM.HOW WILL THIS BE DONE WITH THE | | UNISTRUT AND DRAIN PAN THIS UNDER THE AHU.IF THE | | RETURN AIR IS DUCTED PLEASE PROVIDE A REVISION SHOWING | | LAYOUT, THE GRILLE AND DUCT SIZES.PLEASE PROVIDE A | | REVISION PRIOR TO INSPECTION. | | | | 2.ACCESS TO THE AHU SHALL COMPLY WITH 2004 FMC | | 306.3. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS | | AT (561)805-6719 OR E-MAIL [email protected]. |
|