Plan Review Notes For Permit 06101087 |
Permit Number |
06101087 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-11-03 10:28:04 | DENIED: | | 1.PLEASE INDICATE IF THE AHU IS ABOVE THE CEILING OR | | IN A CLOSET.THE PLAN SHOWS A 24"X24" RAF 6" AFF | | WHICH WOULD INDICATE THE AHU IS IN A CLOSET.HOW DO | | YOU ENTER THE BEDROOM AREA THROUGH THE AHU CLOSET OR IS | | THE BEDROOM DOOR MISSING, PLEASE CLARIFY.THE | | APPROVED ARCHITECTURAL PLANS INDICATE AHU IS IN THE | | ATTIC. | | | | 2.PROVIDE HANGING DETAIL FOR HORIZONTAL INSTALLATION | | OR A SUPPORT DETAIL FOR A VERTICAL UNIT. | | | | 3.PLEASE INDICATE IF THE RETURN AIR IS DUCTED OR IF | | THE CLOSET OR CEILING IS A PLENUM.PLEASE NOTE PER | | 2004 FMC 602.2.1,MATERIALS EXPOSED IN A PLENUM SHALL | | BE NON-COMBUSTIBLE . | | | | 4.PLAN STATES EXHAUST FAN NOT REQUIRED, OPERABLE | | WINDOW EXCEPTION (2004 FMC 402.3.1) WILL BE TAKEN. | | PLEASE NOTE, 3 SQUARE FEET OF CLEAR OPENING IS REQUIRED | | TO TAKE THIS EXCEPTION. | | | | 5.12"X8" TRANSFER GRILL FOR THE MASTER BEDROOM IS NOT | | SIZED IN ACCORDANCE WITH 2004 FMC EXCEPTION 2 & 3. | | | | 6.PLEASE PROVIDE A COPY OF THE APPROVED ENERGY | | CALCULATIONS. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS | | AT (561)805-6719 OR E-MAIL [email protected]. |
|