2006-10-30 08:41:17PROVISO:
 PLEASE NOTE, PER 2004 FMC 606.2.1, DUCT SMOKE DETECTORS
 REQUIRED IN SYSTEMS WITH THE DESIGN CAPACITY GREATER
 THAN 2,000 CFM.FAN SHUTDOWN BY DUCT SMOKE DETECTORS
 SHALL HAVE NOTIFICATION TO ALARM/STROBE IN NORMALLY
 OCCUPIED AREAS IN ACCORDANCE WITH 2002 NFPA 90A SECTION
 6.4.4.3 (1).
  