2007-02-11 13:34:16 | *** UNSAT 4TH REVIEW*** |
| |
| ** PLEASE SEE NOTES FROM PREVIOUS REVIEWS WHICH STILL |
| NEED TO BE ADDRESSED ALONG WITH NEW NOTES AS STATED |
| BELOW. |
| |
| |
| 1) NOTE: PLEASE SEE IN ALL PREVIOUS REVIEWS IT WAS |
| REQUESTED THAT ALL OLD/VOIDED SHEETS BE REMOVED FROM |
| SETS AND TO INSERT NEW REVISED SHEETS INTO SETS, PLEASE |
| INSERT NEW SHEETS AND ATTACH INTO SETS. PLEASE DO NOT |
| ONLY INSERT SHEET LOOSELY INTO SETS. |
| THIS WILL HELP IN PROCESSING THE PLANS FOR PERMITTING. |
| |
| 2) NOTE: PLEASE SEE THE ORIGINAL REVIEW REQUESTED |
| ENERGY CALCULATIONS AND PERFORMANCE CALCULATIONS WHICH |
| MET THE 2004 FBC AND CHAPTER 13. THESE WERE SUBMITTED |
| FOR REVIEW FOR THE 2ND REVIEW AND 3RD REVIEW WHICH |
| NOTES REQUESTED FOR COMPLIANCE AND FOR ALL CALCULATIONS |
| TO CORRELATE WITH THE PLANS SUBMITTED AND THERE WERE |
| SUBSTANTIAL DIFFERENCES IN THE NUMBER OF FIXTURES, |
| LOADS, WATTAGE(S), ETC. |
| PLEASE SEE THAT THIS COMMENT IS STILL BEING MADE AS THE |
| ENERGY CALCULATIONS DO NOT CORRELATE WITH PLANS OR |
| FIXTURE LEGEND FOR FIXTURES, NUMBER OF FIXTURES, |
| WATTAGES OF FIXTURES ETC. |
| PLEASE SEE THERE ARE SEVERAL ITEMS WHICH DO NOT MATCH. |
| PLEASE SEE OUTSIDE/EXTERIOR FIXTURES, PLEASE SEE |
| INTERIOR FIXTURES ETC |
| PLEASE SEE ALL. |
| THE TOTALS DO NOT CORRELATE, TOTALS ON SOME OF THE |
| FIXTURES ON FIXTURE LEGEND DOES NOT MATCH WITH PLANS |
| AND # OF FIXTURES AS SHOWN. ETC. |
| THIS WAS STATED IN ALL REVIEWS AFTER THE 1ST REVIEW AS |
| THESE WERE SUBMITTED ON THE FIRST REVIEW WHICH WAS |
| STILL REQUIRED UNDER THE 2004 FBC. |
| PLEASE SEE THAT A METHOD A IS STILL BEING SHOWN, |
| HOWEVER IT IS NOT CLEAR HOW THIS IS BEING USED WHEN |
| THIS IS FOR TOTAL BUILDING COMPLIANCE AND OTHER AREAS |
| AND TRADES OFFS ARE NOT BEING SHOWN OR INDICATED. |
| (PREVIOUS REVIEWS). |
| PLEASE SEE THE ELECTRICAL PLANS FOR FIXTURES WERE |
| REVISED TO DELETE MANY FIXTURES HOWEVER THE |
| ARCHITECTURAL AND LIFE SAFETY SHEETS WERE NOT REVISED |
| TO REFLECT THESE CHANGES. |
| PLEASE SEE FBC 2004 13-415.1.AB.1. |
| PLEASE SEE 13-415.2. |
| |
| 3) NOTE: PLEASE SEE THE WIND LOADS SEEMS TO BE OK, |
| HOWEVER WILL BE REVIEWED BY THE STRUCTURAL REVIEWER. |
| PLEASE SEE THE ELECTRICAL SHEETS STILL NOT INDICATE ANY |
| REFERENCE TO THE 140MPH WIND LOAD REQUESTED ON PREVIOUS |
| REVIEW. |
| |
| ** NEW NOTES DUE TO PLANS SUBMITTED AND CHANGES WHICH |
| WERE NOT ON PREVIOUS PLANS. |
| |
| 3) NOTE: PLEASE SEE RISER NOW SHOWS *EQUIPMENT |
| GROUNDING CONDUCTORS FROM THE GUTTER TO THE FIRST MEANS |
| OF DISCONNECT IS NOT PERMITTED PER 250.6. |
| PLEASE SEE THE PREVIOUS COMMENTS REQUESTED TO SHOW THE |
| CONDUCTORS FROM THE GUTTER TO EACH MAIN AND FOR * |
| EQUIPMENT GROUNDING CONDUCTORS* AFTER THE FIRST MEANS |
| OF DISCONNECT. |
| PLEASE SEE 250.6 AND 250.24B AS THIS NOW CREATES |
| OBJECTIONABLE CURRENTS BY PARALLELING THE NEUTRAL. |
| PLEASE SEE THIS WOULD HAVE BEEN REDLINED, HOWEVER AS |
| PLANS ARE COMING BACK FOR COMMENT #2, PLEASE CORRECT AT |
| THIS TIME. |
| |
| 4) NOTE: PLEASE SEE AS COMMENT #2 HAS BEEN REPEATED FOR |
| CODE COMPLIANCE REVIEW THREE OR MORE TIMES FOR THE SAME |
| CODE COMPLIANT COMMENT AND IT IS NECESSARY FOR THIS |
| OFFICE TO REJECT PLANS FOR THIS, THE FS 553.80(2)(B) IS |
| IN EFFECT AND A 4X FEE FOR THE PLAN REVIEW PORTION OF |
| THE PERMIT FEE HAS NOW BEEN ASSESSED. |
| THIS FEE IS A REQUIRED FEE PER THE FLORIDA STATUTES TO |
| THE DESIGNER(S) OF RECORD AND MUST BE PAID BEFORE PLANS |
| CAN BE RESUBMITTED FOR REVIEW. |
| PLEASE SEE THAT ONE SET OF EACH ELECTRICAL PLAN AND |
| ENERGY CALCULATIONS ARE BEING RETAINED BY THIS OFFICE. |
| ONE SET OF THE ARCHITECTURAL AND LS PLANS MAY ALSO BE |
| RETAINED. |
| THE AMOUNT OF $1620 WILL BE DUE BEFORE PLANS CAN BE |
| RESUBMITTED. |
| |
| ** IT IS RECOMMENDED THAT COMMENT #2 BE REVIEWED AND |
| GONE THROUGH THOROUGHLY. |
| |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| |
| |
| |