Plan Review Notes
Plan Review Notes For Permit 06101031
Permit Number 06101031
Review Stop E
Sequence Number 4
Notes
Date Text
2007-02-11 13:34:16*** UNSAT 4TH REVIEW***
  
 ** PLEASE SEE NOTES FROM PREVIOUS REVIEWS WHICH STILL
 NEED TO BE ADDRESSED ALONG WITH NEW NOTES AS STATED
 BELOW.
  
  
 1) NOTE: PLEASE SEE IN ALL PREVIOUS REVIEWS IT WAS
 REQUESTED THAT ALL OLD/VOIDED SHEETS BE REMOVED FROM
 SETS AND TO INSERT NEW REVISED SHEETS INTO SETS, PLEASE
 INSERT NEW SHEETS AND ATTACH INTO SETS. PLEASE DO NOT
 ONLY INSERT SHEET LOOSELY INTO SETS.
 THIS WILL HELP IN PROCESSING THE PLANS FOR PERMITTING.
  
 2) NOTE: PLEASE SEE THE ORIGINAL REVIEW REQUESTED
 ENERGY CALCULATIONS AND PERFORMANCE CALCULATIONS WHICH
 MET THE 2004 FBC AND CHAPTER 13. THESE WERE SUBMITTED
 FOR REVIEW FOR THE 2ND REVIEW AND 3RD REVIEW WHICH
 NOTES REQUESTED FOR COMPLIANCE AND FOR ALL CALCULATIONS
 TO CORRELATE WITH THE PLANS SUBMITTED AND THERE WERE
 SUBSTANTIAL DIFFERENCES IN THE NUMBER OF FIXTURES,
 LOADS, WATTAGE(S), ETC.
 PLEASE SEE THAT THIS COMMENT IS STILL BEING MADE AS THE
 ENERGY CALCULATIONS DO NOT CORRELATE WITH PLANS OR
 FIXTURE LEGEND FOR FIXTURES, NUMBER OF FIXTURES,
 WATTAGES OF FIXTURES ETC.
 PLEASE SEE THERE ARE SEVERAL ITEMS WHICH DO NOT MATCH.
 PLEASE SEE OUTSIDE/EXTERIOR FIXTURES, PLEASE SEE
 INTERIOR FIXTURES ETC
 PLEASE SEE ALL.
 THE TOTALS DO NOT CORRELATE, TOTALS ON SOME OF THE
 FIXTURES ON FIXTURE LEGEND DOES NOT MATCH WITH PLANS
 AND # OF FIXTURES AS SHOWN. ETC.
 THIS WAS STATED IN ALL REVIEWS AFTER THE 1ST REVIEW AS
 THESE WERE SUBMITTED ON THE FIRST REVIEW WHICH WAS
 STILL REQUIRED UNDER THE 2004 FBC.
 PLEASE SEE THAT A METHOD A IS STILL BEING SHOWN,
 HOWEVER IT IS NOT CLEAR HOW THIS IS BEING USED WHEN
 THIS IS FOR TOTAL BUILDING COMPLIANCE AND OTHER AREAS
 AND TRADES OFFS ARE NOT BEING SHOWN OR INDICATED.
 (PREVIOUS REVIEWS).
 PLEASE SEE THE ELECTRICAL PLANS FOR FIXTURES WERE
 REVISED TO DELETE MANY FIXTURES HOWEVER THE
 ARCHITECTURAL AND LIFE SAFETY SHEETS WERE NOT REVISED
 TO REFLECT THESE CHANGES.
 PLEASE SEE FBC 2004 13-415.1.AB.1.
 PLEASE SEE 13-415.2.
  
 3) NOTE: PLEASE SEE THE WIND LOADS SEEMS TO BE OK,
 HOWEVER WILL BE REVIEWED BY THE STRUCTURAL REVIEWER.
 PLEASE SEE THE ELECTRICAL SHEETS STILL NOT INDICATE ANY
 REFERENCE TO THE 140MPH WIND LOAD REQUESTED ON PREVIOUS
 REVIEW.
  
 ** NEW NOTES DUE TO PLANS SUBMITTED AND CHANGES WHICH
 WERE NOT ON PREVIOUS PLANS.
  
 3) NOTE: PLEASE SEE RISER NOW SHOWS *EQUIPMENT
 GROUNDING CONDUCTORS FROM THE GUTTER TO THE FIRST MEANS
 OF DISCONNECT IS NOT PERMITTED PER 250.6.
 PLEASE SEE THE PREVIOUS COMMENTS REQUESTED TO SHOW THE
 CONDUCTORS FROM THE GUTTER TO EACH MAIN AND FOR *
 EQUIPMENT GROUNDING CONDUCTORS* AFTER THE FIRST MEANS
 OF DISCONNECT.
 PLEASE SEE 250.6 AND 250.24B AS THIS NOW CREATES
 OBJECTIONABLE CURRENTS BY PARALLELING THE NEUTRAL.
 PLEASE SEE THIS WOULD HAVE BEEN REDLINED, HOWEVER AS
 PLANS ARE COMING BACK FOR COMMENT #2, PLEASE CORRECT AT
 THIS TIME.
  
 4) NOTE: PLEASE SEE AS COMMENT #2 HAS BEEN REPEATED FOR
 CODE COMPLIANCE REVIEW THREE OR MORE TIMES FOR THE SAME
 CODE COMPLIANT COMMENT AND IT IS NECESSARY FOR THIS
 OFFICE TO REJECT PLANS FOR THIS, THE FS 553.80(2)(B) IS
 IN EFFECT AND A 4X FEE FOR THE PLAN REVIEW PORTION OF
 THE PERMIT FEE HAS NOW BEEN ASSESSED.
 THIS FEE IS A REQUIRED FEE PER THE FLORIDA STATUTES TO
 THE DESIGNER(S) OF RECORD AND MUST BE PAID BEFORE PLANS
 CAN BE RESUBMITTED FOR REVIEW.
 PLEASE SEE THAT ONE SET OF EACH ELECTRICAL PLAN AND
 ENERGY CALCULATIONS ARE BEING RETAINED BY THIS OFFICE.
 ONE SET OF THE ARCHITECTURAL AND LS PLANS MAY ALSO BE
 RETAINED.
 THE AMOUNT OF $1620 WILL BE DUE BEFORE PLANS CAN BE
 RESUBMITTED.
  
 ** IT IS RECOMMENDED THAT COMMENT #2 BE REVIEWED AND
 GONE THROUGH THOROUGHLY.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]