2007-02-13 09:39:49BUILDING PLAN REVIEW
 PERMIT: 06101031
 ADD:2501 N.FLAGLER DR.
 CONT:G.A. RAY INC.
 TEL: (561)630-4861
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)F.A.C. 61G15-23.002A COVER OR INDEX SHEET FOR
 ENGINEERING SPECIFICATIONS MAY BE USED AND THAT SHEET
 MUST BE SIGNED, SEALED AND DATED BY THE ENGINEER IN
 RESPONSIBLE CHARGE OF THE PRODUCTION AND PREPARATION OF
 EACH SECTION OF THE ENGINEERING SPECIFICATION WITH
 SUFFICIENT INFORMATION ON THE COVER SHEET OR INDEX SO
 THAT THE WILL BE AWARE OF EACH PORTION OF THE
 SPECIFICATIONS FOR WHICH EACH PROFESSIONAL ENGINEER IS
 RESPONSIBLE. (INDICATE EACH PAGE ON THE COVER OR INDEX
 SHEET)
  
 3) THE ASCE REFERENCE STANDARD (ASCE 7-04) STATED IN
 THE ENGINEERING REPORT FOR THE LIGHT POLE IS INCORRECT.
 SEE FBC. 35.6R FOR MORE INFORMATION.
  
 4)2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726