Plan Review Notes For Permit 06101031
Permit Number 06101031
Review Stop E
Sequence Number 3
Notes
Date Text
2007-01-21 12:50:23** UNSAT 3RD REVIEW **
  
  
 ** PLEASE SEE SOME COMMENTS FROM THE PREVIOUS REVIEW
 ARE STILL IN NEED OF ADDRESSING ALONG WITH NEW COMMENTS
 BASED ON A COMPLETELY NEW ELECTRICAL RISER DIAGRAM
 BEING SUBMITTED.
  
  
 1) NOTE: PLEASE SEE THE PLANS NOW HAVE THE SITE
 LIGHTING FIXTURES AND CIRCUITS REMOVED WHEN BOTH THE
 PREVIOUS REVIEWS INDICATED THESE. PLEASE SEE ENERGY
 CALCULATIONS ARE STILL INDICATING THESE TO BE
 INSTALLED.
 PLEASE SEE THAT PLANS MUST SHOW THESE, POLE DETAIL,
 CIRCUITS, AND APPROPRIATE WIND LOADS.
 PLEASE KNOW ANY SHOP PLANS FOR THE POLES MAY BE
 SUBMITTED AT A LATER DATE AS A *PROVISO*; HOWEVER THE
 BASE INFORMATION ABOVE MUST BE SHOWN. (IF THESE ARE
 GOING TO BE DONE)??
 FBC 106.1.2, 106.3.5.1.2
 408.4, 310.16, 240.4 ETC.
 THIS WAS A COMMENT ON PREVIOUS REVIEW.
  
 2) NOTE: PLEASE SEE PREVIOUS NOTE MENTIONED THAT THE
 ENERGY CALCULATIONS DID NOT CORRELATE WITH THE
 ELECTRICAL FIXTURES AND LIGHTING AS SHOWN ON PLANS.
 THIS IS STILL THE CASE. PLEASE SEE THE AMOUNT AND TYPE
 OF FIXTURES AS SHOWN ON PLANS FAR EXCEED THAT OF ENERGY
 CALCULATIONS.
 PLEASE SEE 13-415.1.AB.1.1.
 PLEASE SEE CHAPTER 13, ALL, AS COMPLIANCE MUST BE MET
 FOR ALL AREAS. 106.1.2, 106.3.5.1.2
 THIS WAS THE SAME COMMENT ON PREVIOUS REVIEW.
 ** PLEASE KNOW AS THE COMMENT IS BEING REPEATED AND
 COMPLIANCE IS NOT BEING MET, PLEASE SUBMIT A COMPLETE
 FIXTURE LEGEND AND CORRELATE WITH ALL FIXTURE
 DESIGNATIONS ON PLANS.
 106.1.2, 106.3.5.1.2
  
 3) NOTE: PLEASE SEE 220.12, 220 AS STATED ON THE
 PREVIOUS REVIEW FOR TRACK LIGHTING LOADS AND HOW AND
 WHERE THESE ARE BEING FIGURED INTO CALCULATIONS.
  
 4) NOTE: PLEASE SEE RISER HAS BEEN COMPLETELY REVISED.
 PLEASE INCLUDE MISSING CONDUCTOR FROM METER TO GUTTER
 AND FROM GUTTER TO EACH OF THE NEW MAIN DISCONNECTS AS
 NOW SHOWN.
 240.4, 310.16, ETC.
 FBC 106.1.2 AND 106.3.5.1.2 ADMIN SECTIONS.
  
 5) NOTE: PLEASE SEE MISSING EQUIPMENT GROUNDING
 CONDUCTORS FROM NEW MAINS TO PANELS. PLEASE KNOW EVEN
 AS THE USE OF EMT IS BEING SHOWN, UNLESS THE NEW LISTED
 CONNECTORS RATED FOR *EQUIPMENT GROUNDING * IS BEING
 USED AND EQUIPMENT GROUNDING CONDUCTOR SIZED PER
 250.122 SHALL BE INSTALLED.
 *THIS WOULD HAVE BEEN REDLINED IF THIS WERE THE ONLY
 COMMENT.
  
 6) NOTE: PLEASE SEE AS THE RISER IS NOW SHOWING A NEW
 PANEL *B*, THE PLANS DO NOT INCLUDE THIS? PLEASE SHOW
 THE LOCATION OF THE NEW PANEL WHICH IS NOW ADDED.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]