Plan Review Notes For Permit 06101031 |
Permit Number |
06101031 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-11-21 10:07:10 | *****DENIED***** | | | | | | | | 1.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT | | HINDER OR INTERFERE WITH EMERGENCY ACCESS TO THE SAID | | PROPERTY OR THE VICINITY THEREOF. | | | | 2.WHAT TYPE OF OCCUPANCY WILL THE PROPOSED STRUCTURE | | BE? | | | | 3.DOES THE EXISTING BUILDING HAVE FIRE PROTECTION | | SYSTEM IN PLACE?IF SO, HOW WILL THEY BE AFFECTED BY | | THE SCOPE OF THE WORK? | | | | 4.IF THE FIRE PROTECTION SYSTEM IS MODIFIED OR IS | | ADDED TO THE BUILDING, SEPARATE PERMIT AND PLANS ARE | | REQUIRED. | | | | 5.PROVIDE A LIFE SAFETY PLAN WHICH INCLUDES ALL | | COMMON PATHS OF TRAVEL TO EXITS. | | | | 6.INDICATE LOCATION OF 2A-10BC FIRE EXTINGUISHERS AT | | DISTANCES TO SATISFY THE 75' TRAVEL DISTANCE | | REQUIREMENT. | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED. | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|